Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Motor reactors

  • Заказные данные
    (22)
  • Информационные материалы

    Информационные материалы

    Motor reactors reduce the voltage load on the motor windings by reducing the voltage gradients at the motor terminals that occur during converter operation. At the same time, the capacitive charge/discharge currents that place an additional load on the converter output when long motor cables are used, are reduced. For group drives, output reactors should always be used. The maximum permissible output frequency when a motor reactor is used is 150 Hz.

    The motor reactor must be installed as close as possible to the Motor Module or Power Module. Up to two motor reactors can be connected in series.

    Motor reactors are approved for use only in conjunction with Vector and V/f control modes.

    For additional notes on the use of motor reactors, please refer to the SINAMICS Low Voltage Configuration Manual.

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    Motor reactor (for pulse frequencies of 2 kHz to 4 kHz)

     

    6SL3000-2BE32-1AA0

    6SL3000-2BE32-6AA0

    6SL3000-2BE33-2AA0

    6SL3000-2BE33-8AA0

    6SL3000-2BE35-0AA0

    Rated current

    A

    210

    260

    310

    380

    490

    Power loss, max. 1)

    kW

    0.486

    0.5

    0.47

    0.5

    0.5

    Load connection

     

    1 × hole for M10

    1 × hole for M10

    1 × hole for M10

    1 × hole for M10

    1 × hole for M12

    PE connection

     

    M8 screw

    M8 screw

    M8 screw

    M8 screw

    M8 screw

    Cable length, max.

    between the motor reactor and motor

     

     

     

     

     

     

     

     

     

     

     

    (number of reactors in series)

     

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    • Shielded

    m (ft)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    • Unshielded

    m (ft)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    300 (11.8)

    300 (11.8)

    300 (11.8)

    300 (11.8)

    300 (11.8)

    • Height

    mm (in)

    285 (11.2)

    315 (12.4)

    285 (11.2)

    285 (11.2)

    365 (14.4)

    • Depth

    mm (in)

    257 (10.1)

    277 (10.9)

    257 (10.1)

    277 (10.9)

    277 (10.9)

    Weight, approx.

    kg (lb)

    66 (146)

    66 (146)

    66 (146)

    73 (161)

    100 (220)

    Suitable for Power Module

     

    6SL3310-1TE32-1AA3

    6SL3315-1TE32-1AA3

    6SL3310-1TE32-6AA3

    6SL3315-1TE32-6AA3

    6SL3310-1TE33-1AA3

    6SL3315-1TE33-1AA3

    6SL3310-1TE33-8AA3

    6SL3310-1TE35-0AA3

    6SL3315-1TE35-0AA3

    Suitable for Motor Module

     

    6SL3320-1TE32-1AA3

    6SL3325-1TE32-1AA3

    6SL3320-1TE32-6AA3

    6SL3325-1TE32-6AA3

    6SL3320-1TE33-1AA3

    6SL3325-1TE33-1AA3

    6SL3320-1TE33-8AA3

    6SL3320-1TE35-0AA3

    6SL3325-1TE35-0AA3

    • Rated current of Motor Module or Power Module

    A

    210

    260

    310

    380

    490

    • Type rating of Motor Module or Power Module

    kW

    110

    132

    160

    200

    250



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    Line voltage 380 ... 480 V 3 AC

    Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

     

    6SL3000-2AE36-1AA0

    6SL3000-2AE38-4AA0

    6SL3000-2AE41-0AA0

    6SL3000-2AE41-4AA0

    Rated current

    A

    605

    745

    840

    985

    1260

    1405

    Power loss, max. 1)

    kW

    0.9

    0.84

    0.943

    1.062

    0.9

    1.054

    Load connection

     

    1 × hole for M12

    1 × hole for M12

    1 × hole for M12

    1 × hole for M12

    2 × hole for M12

    2 × hole for M12

    PE connection

     

    M10 screw

    M10 screw

    M10 screw

    M10 screw

    M10 screw

    M10 screw

    Cable length, max.

    between the motor reactor and motor

     

     

     

     

     

     

     

     

     

     

     

     

     

    (number of reactors in series)

     

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    • Shielded

    m (ft)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    • Unshielded

    m (ft)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    410 (16.1)

    410 (16.1)

    410 (16.1)

    410 (16.1)

    460 (18.1)

    460 (18.1)

    • Height

    mm (in)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    • Depth

    mm (in)

    292 (11.5)

    292 (11.5)

    292 (11.5)

    302 (11.9)

    326 (12.8)

    326 (12.8)

    Weight, approx.

    kg (lb)

    130 (287)

    140 (309)

    140 (309)

    146 (322)

    179 (395)

    179 (395)

    Suitable for Motor Module

     

    6SL3320-1TE36-1AA3

    6SL3325-1TE36-1AA3

    6SL3320-1TE37-5AA3

    6SL3325-1TE37-5AA3

    6SL3320-1TE38-4AA3

    6SL3325-1TE38-4AA3

    6SL3320-1TE41-0AA3

    6SL3325-1TE41-0AA3

    6SL3320-1TE41-2AA3

    6SL3325-1TE41-2AA3

    6SL3320-1TE41-4AA3

    6SL3325-1TE41-4AA3

    6SL3325-1TE41-4AS3 2)

    • Rated current of the Motor Module

    A

    605

    745

    840

    985

    1260

    1405

    • Type rating of the Motor Module

    kW

    315

    400

    450

    560

    710

    800



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    2) This Motor Module has been specifically designed for loads demanding a high dynamic performance.

    Line voltage 500 ... 690 V 3 AC

    Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

     

    6SL3000-2AH31-0AA0

    6SL3000-2AH31-5AA0

    6SL3000-2AH31-8AA0

    6SL3000-2AH32-4AA0

    Rated current

    A

    85

    100

    120

    150

    175

    215

    Power loss, max. 1)

    kW

    0.257

    0.3

    0.318

    0.335

    0.4

    0.425

    Load connection

     

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    PE connection

     

    M6 screw

    M6 screw

    M6 screw

    M6 screw

    M6 screw

    M6 screw

    Cable length, max.

    between the motor reactor and motor

     

     

     

     

     

     

     

     

     

     

     

     

     

    (number of reactors in series)

     

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    • Shielded

    m (ft)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    • Unshielded

    m (ft)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    270 (10.6)

    270 (10.6)

    270 (10.6)

    270 (10.6)

    300 (11.8)

    300 (11.8)

    • Height

    mm (in)

    248 (9.76)

    248 (9.76)

    248 (9.76)

    248 (9.76)

    285 (11.2)

    285 (11.2)

    • Depth

    mm (in)

    200 (7.87)

    200 (7.87)

    200 (7.87)

    200 (7.87)

    212 (8.35)

    212 (8.35)

    Weight, approx.

    kg (lb)

    25 (55)

    25 (55)

    25.8 (56.9)

    25.8 (56.9)

    34 (75)

    34 (75)

    Suitable for Motor Module

     

    6SL3320-1TG28-5AA3

    6SL3320-1TG31-0AA3

    6SL3325-1TG31-0AA3

    6SL3320-1TG31-2AA3

    6SL3320-1TG31-5AA3

    6SL3325-1TG31-5AA3

    6SL3320-1TG31-8AA3

    6SL3320-1TG32-2AA3

    6SL3325-1TG32-2AA3

    • Rated current of the Motor Module

    A

    85

    100

    120

    150

    175

    215

    • Type rating of the Motor Module

    kW

    75

    90

    110

    132

    160

    200



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    Line voltage 500 ... 690 V 3 AC

    Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

     

    6SL3000-2AH32-6AA0

    6SL3000-2AH33-6AA0

    6SL3000-2AH34-5AA0

    6SL3000-2AH34-7AA0

    6SL3000-2AH35-8AA0

    6SL3000-2AH38-1AA0

    Rated current

    A

    260

    330

    410

    465

    575

    735

    Power loss, max. 1)

    kW

    0.44

    0.45

    0.545

    0.72

    0.8

    0.96

    Load connection

     

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    PE connection

     

    M6 screw

    M6 screw

    M8 screw

    M8 screw

    M8 screw

    M8 screw

    Cable length, max.

    between the motor reactor and motor

     

     

     

     

     

     

     

     

     

     

     

     

     

    (number of reactors in series)

     

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    • Shielded

    m (ft)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    • Unshielded

    m (ft)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    300 (11.8)

    300 (11.8)

    350 (13.8)

    410 (16.1)

    410 (16.1)

    410 (16.1)

    • Height

    mm (in)

    285 (11.2)

    285 (11.2)

    330 (13.0)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    • Depth

    mm (in)

    212 (8.35)

    212 (8.35)

    215 (8.46)

    292 (11.5)

    292 (11.5)

    279 (11.0)

    Weight, approx.

    kg (lb)

    40 (88)

    46 (101)

    68 (150)

    80 (176)

    80 (176)

    146 (322)

    Suitable for Motor Module

     

    6SL3320-1TG32-6AA3

    6SL3320-1TG33-3AA3

    6SL3325-1TG33-3AA3

    6SL3320-1TG34-1AA3

    6SL3320-1TG34-7AA3

    6SL3325-1TG34-7AA3

    6SL3320-1TG35-8AA3

    6SL3325-1TG35-8AA3

    6SL3320-1TG37-4AA3

    6SL3325-1TG37-4AA3

    • Rated current of the Motor Module

    A

    260

    330

    410

    465

    575

    735

    • Type rating of the Motor Module

    kW

    250

    315

    400

    450

    560

    710



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    Line voltage 500 ... 690 V 3 AC

    Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)

     

    6SL3000-2AH38-1AA0

    6SL3000-2AH41-0AA0

    6SL3000-2AH41-1AA0

    6SL3000-2AH41-3AA0

    Rated current

    A

    810

    910

    1025

    1270

    Power loss, max. 1)

    kW

    1.0

    0.97

    1.05

    0.95

    Load connection

     

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    PE connection

     

    M8 screw

    M8 screw

    M8 screw

    M8 screw

    Cable length, max.

    between the motor reactor and motor

     

     

     

     

     

     

     

     

     

    (number of reactors in series)

     

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    (1)

    (2)

    • Shielded

    m (ft)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    300 (984)

    525 (1723)

    • Unshielded

    m (ft)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    450 (1476)

    787 (2582)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    410 (16.1)

    410 (16.1)

    410 (16.1)

    460 (18.1)

    • Height

    mm (in)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    392 (15.4)

    • Depth

    mm (in)

    279 (11.0)

    279 (11.0)

    317 (12.5)

    296 (11.6)

    Weight, approx.

    kg (lb)

    146 (322)

    150 (331)

    163 (359)

    153 (337)

    Suitable for Motor Module

     

    6SL3320-1TG38-1AA3

    6SL3325-1TG38-0AA3

    6SL3325-1TG38-1AA3

    6SL3320-1TG38-8AA3

    6SL3320-1TG41-0AA3

    6SL3325-1TG41-0AA3

    6SL3320-1TG41-3AA3

    6SL3325-1TG41-3AA3

    • Rated current of the Motor Module

    A

    810

    910

    1025

    1270

    • Type rating of the Motor Module

    kW

    800

    900

    1000

    1200



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.