    Basic Line Modules are available for applications in which no energy is returned to the supply or where the energy exchange between motor and generator axes takes place in the DC link. Basic Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.

    The Basic Line Modules are available in different frame sizes. With frame sizes FB and GB, a fully controlled thyristor bridge is used to pre-charge the Basic Line Modules and connected Motor Modules. The thyristors normally operate with a trigger delay angle of 0°.

    Basic Line Modules, frame size GD for 900 kW (400 V) or 1500 kW (690 V) include a diode bridge, and the DC link is pre-charged via a separate line-side pre-charging circuit.

    A Braking Module of the appropriate frame size can be integrated into a Basic Line Module in order to permit, in conjunction with an external braking resistor, regenerative operation of the drive system.

    Дизайн

    The Basic Line Modules have the following interfaces as standard:

    • 1 line supply connection
    • 1 connection for the 24 V DC electronics power supply
    • 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
    • 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
    • 3 DRIVE‑CLiQ sockets
    • 1 temperature sensor input for KTY84‑130, Pt1000 or PTC (Pt1000 can be used from firmware V4.7 HF17)
    • 1 PE connection

    The status of the Basic Line Modules is indicated via three LEDs.

    The scope of supply of the Basic Line Modules includes:

    • DRIVE‑CLiQ cable to connect to a Control Unit
    • DRIVE‑CLiQ cable to connect the Control Unit to the first Motor Module
    • 1 set of warning labels in 30 languages
      (BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
    Pre-charging circuit for the Basic Line Modules, frame size GD

    Unlike Basic Line Modules in frame sizes FB and GB, a Basic Line Module in frame size GD requires a separate precharging circuit. The pre-charging circuit components must be ordered separately.

    During startup, the pre-charging circuit ensures that the DC link capacitors of the Basic Line Module and the connected Motor Modules are pre-charged with current limiting. After pre-charging has been completed, the circuit breaker is closed and the pre-charging circuit bypassed; the Basic Line Module is then directly connected to the line supply.

    The pre-charging circuit comprises a pre-charging contactor and pre-charging resistors; the circuit must be protected against overcurrent using suitable protection measures. To increase the permissible DC link capacitance, the pre-charging resistors can also be connected in parallel in each phase.

    More information on the pre-charging circuit is to be found in the SINAMICS Low Voltage Engineering Manual.

    For components for the pre-charging circuit and for recommended line-side system components, see System components.

    Интеграция

    The Basic Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate Basic Line Modules.

    Connection example of a Basic Line Module, frame sizes FB, GB

    Connection example of a Basic Line Module, frame size GD

    Технические данные

    General technical specifications

    Electrical specifications

    Line power factor

    at rated power

     

    • Basic fundamental (cos φ1)

    >0.96

    • Total (λ)

    0.75 ... 0.93

    Efficiency

    >99 %

    DC link voltage, approx. 1)

    1.35 × line voltage under partial load
    1.32 × line voltage under full load

    Main contactor control

     

    • Terminal block -X9/5-6

    240 V AC, max. 8 A
    30 V DC, max. 1 A



    1) The DC link voltage is unregulated and load-dependent. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    Line voltage 380 ... 480 V 3 AC

    Basic Line Modules

     

    6SL3330-1TE34-2AA3

    6SL3330-1TE35-3AA3

    6SL3330-1TE38-2AA3

    6SL3330-1TE41-2AA3

    6SL3330-1TE41-5AA3

    6SL3330-1TE41-8AA3

    Rated power

     

     

     

     

     

     

     

    • At Irated DC (50 Hz 400 V)

    kW

    200

    250

    400

    560

    710

    900

    • At IH DC (50 Hz 400 V)

    kW

    160

    200

    315

    450

    560

    705

    • At Irated DC (60 Hz 460 V)

    hp

    305

    385

    615

    860

    1090

    1390

    • At IH DC (60 Hz 460 V)

    hp

    245

    305

    485

    690

    860

    1090

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC

    A

    420

    530

    820

    1200

    1500

    1880

    • Base-load current IH DC 1)

    A

    328

    413

    640

    936

    1170

    1467

    • Maximum current Imax DC

    A

    630

    795

    1230

    1800

    2250

    2820

    Input current

     

     

     

     

     

     

     

    • Rated current Irated I

    A

    365

    460

    710

    1010

    1265

    1630

    • Maximum current Imax I

    A

    547

    690

    1065

    1515

    1897

    2380

    • Max. pre-charging current (max. 3 s)

    A

    Internal

    Internal

    Internal

    Internal

    Internal

    308

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.1

    1.1

    1.1

    1.1

    1.1

    1.1

    DC link capacitance

     

     

     

     

     

     

     

    • Basic Line Module

    μF

    7200

    9600

    14600

    23200

    29000

    34800

    • Drive line-up, max.

    μF

    57600

    76800

    116800

    185600

    232000

    139200/278400 2)

    Power loss, max. 3)

     

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    1.9

    2.1

    3.2

    4.6

    5.5

    6.9

    • At 60 Hz 460 V

    kW

    1.9

    2.1

    3.2

    4.6

    5.5

    6.9

    Cooling air requirement

    m3/s (ft3/s)

    0.17 (6.00)

    0.17 (6.00)

    0.17 (6.00)

    0.36 (12.7)

    0.36 (12.7)

    0.36 (12.7)

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    66/68

    66/68

    66/68

    71/73

    71/73

    71/73

    Line connection

    U1, V1, W1

     

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    2 × 240

    6 × 185

    6 × 185

    6 × 185

    DC link connection

    DCP, DCN

     

    M10 screw

    M10 screw

    M10 screw

    3 × hole for M12

    3 × hole for M12

    3 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    2 × 240

    6 × 185

    6 × 185

    6 × 185

    PE/GND connection

     

    2 × hole for M10

    2 × hole for M10

    2 × hole for M10

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    2 × 240

    4 × 240

    4 × 240

    4 × 240

    Cable length, max. 4)

     

     

     

     

     

     

     

    • Shielded

    m (ft)

    2600 (8531)

    2600 (8531)

    2600 (8531)

    4000 (13124)

    4000 (13124)

    4800 (15749)

    • Unshielded

    m (ft)

    3900 (12796)

    3900 (12796)

    3900 (12796)

    6000 (19686)

    6000 (19686)

    7200 (23623)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    • Height

    mm (in)

    1164 (45.8)

    1164 (45.8)

    1164 (45.8)

    1653 (65.1)

    1653 (65.1)

    1653 (65.1)

    • Depth

    mm (in)

    352 (13.9)

    352 (13.9)

    352 (13.9)

    550 (21.6)

    550 (21.6)

    550 (21.6)

    Weight, approx.

    kg (lb)

    96 (212)

    96 (212)

    96 (212)

    214 (472)

    214 (472)

    214 (472)

    Frame size

     

    FB

    FB

    FB

    GB

    GB

    GD

    Minimum short-circuit current 5)

    A

    4400

    5200

    10000

    12400

    18400

    18600



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The first value applies for one precharging resistor for each phase, the second value for two precharging resistors connected in parallel for each phase.

    3) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    5) Current required for reliably triggering protective devices.

    Line voltage 500 ... 690 V 3 AC

    Basic Line Modules

     

    6SL3330-1TG33-0AA3

    6SL3330-1TG34-3AA3

    6SL3330-1TG36-8AA3

    6SL3330-1TG41-1AA3

    6SL3330-1TG41-4AA3

    6SL3330-1TG41-8AA3

    Rated power

     

     

     

     

     

     

     

    • At Irated DC (50 Hz 690 V)

    kW

    250

    355

    560

    900

    1100

    1500

    • At IH DC (50 Hz 690 V)

    kW

    195

    280

    440

    710

    910

    1220

    • At Irated DC (50 Hz 500 V)

    kW

    175

    250

    390

    635

    810

    1085

    • At IH DC (50 Hz 500 V)

    kW

    165

    235

    365

    595

    755

    1015

    • At Irated DC (60 Hz 575 V)

    hp

    250

    350

    600

    900

    1250

    1500

    • At IH DC (60 Hz 575 V)

    hp

    200

    300

    450

    800

    1000

    1250

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC

    A

    300

    430

    680

    1100

    1400

    1880

    • Base-load current IH DC 1)

    A

    234

    335

    530

    858

    1092

    1467

    • Maximum current Imax DC

    A

    450

    645

    1020

    1650

    2100

    2820

    Input current

     

     

     

     

     

     

     

    • Rated current Irated I

    A

    260

    375

    575

    925

    1180

    1580

    • Maximum current Imax I

    A

    390

    563

    863

    1388

    1770

    2370

    • Max. pre-charging current (max. 3 s)

    A

    Internal

    Internal

    Internal

    Internal

    Internal

    234

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.1

    1.1

    1.1

    1.1

    1.1

    1.1

    DC link capacitance

     

     

     

     

     

     

     

    • Basic Line Module

    μF

    3200

    4800

    7300

    11600

    15470

    19500

    • Drive line-up, max.

    μF

    25600

    38400

    58400

    92800

    123760

    78000/156000 2)

    Power loss, max. 3)

     

     

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    1.5

    2.1

    3.0

    5.4

    5.8

    7.3

    • At 60 Hz 575 V

    kW

    1.5

    2.1

    3.0

    5.4

    5.8

    7.3

    Cooling air requirement

    m3/s (ft3/s)

    0.17 (6.00)

    0.17 (6.00)

    0.17 (6.00)

    0.36 (12.7)

    0.36 (12.7)

    0.36 (12.7)

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    66/68

    66/68

    66/68

    71/73

    71/73

    71/73

    Line connection

    U1, V1, W1

     

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    2 × 240

    6 × 185

    6 × 185

    6 × 185

    DC link connection

    DCP, DCN

     

    M10 screw

    M10 screw

    M10 screw

    3 × hole for M12

    3 × hole for M12

    3 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    2 × 240

    6 ×185

    6 × 185

    6 × 185

    PE/GND connection

     

    2 × hole for M10

    2 × hole for M10

    2 × hole for M10

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    2 × 240

    4 × 240

    4 × 240

    4 × 240

    Cable length, max. 4)

     

     

     

     

     

     

     

    • Shielded

    m (ft)

    1500 (4921)

    1500 (4921)

    1500 (4921)

    2250 (7382)

    2250 (7382)

    2750 (9023)

    • Unshielded

    m (ft)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    3375 (11073)

    3375 (11073)

    4125 (13534)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    310 (12.2)

    • Height

    mm (in)

    1164 (45.8)

    1164 (45.8)

    1164 (45.8)

    1653 (65.1)

    1653 (65.1)

    1653 (65.1)

    • Depth

    mm (in)

    352 (13.9)

    352 (13.9)

    352 (13.9)

    550 (21.6)

    550 (21.6)

    550 (21.6)

    Weight, approx.

    kg (lb)

    96 (212)

    96 (212)

    96 (212)

    214 (472)

    214 (472)

    214 (472)

    Frame size

     

    FB

    FB

    FB

    GB

    GB

    GD

    Minimum short-circuit current 5)

    A

    3000

    4400

    8000

    10400

    16000

    18600



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The first value applies for one pre-charging resistor for each phase, the second value for two precharging resistors connected in parallel for each phase.

    3) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    5) Current required for reliably triggering protective devices.