Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Line filters

  • Заказные данные
    (16)
  • Информационные материалы

    Информационные материалы

    In conjunction with line reactors and a logically consistent configuration of the plant or system, line filters limit the interference conducted by the Basic Line Modules and Power Modules to the limit values of Category C2 acc. to EN 61800-3.

    The line filters are suitable for TN and TT supply systems grounded at the neutral point.

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    Line filter

     

    6SL3000-0BE32-5AA0

    6SL3000-0BE34-4AA0

    6SL3000-0BE36-0AA0

    6SL3000-0BE41-2AA0

    6SL3000-0BE41-6AA0

    Rated current

    A

    250

    440

    600

    1200

    1600

    Power loss 1)

    At 50 Hz

    kW

    0.015

    0.047

    0.053

    0.119

    0.153

    Load/line supply connection

     

    1 × hole for M10

    Provided for busbar connection

    1 × hole for M10

    Provided for busbar connection

    1 × hole for M10

    Provided for busbar connection

    1 × hole for M12

    Provided for busbar connection

    1 × hole for M12

    Provided for busbar connection

    PE connection

     

    Hole for M8

    Hole for M8

    Hole for M10

    Hole for M10

    Hole for M10

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    360 (14.2)

    360 (14.2)

    400 (15.7)

    425 (16.7)

    505 (19.9)

    • Height

    mm (in)

    240 (9.45)

    240 (9.45)

    265 (10.4)

    265 (10.4)

    265 (10.4)

    • Depth

    mm (in)

    116 (4.57)

    116 (4.57)

    140 (5.51)

    145 (5.71)

    145 (5.71)

    Weight, approx.

    kg (lb)

    12.3 (27)

    12.3 (27)

    19 (42)

    25.2 (56)

    28.8 (63)

    Suitable for Power Module in chassis format

    • Air-cooled
      (type rating)

    6SL3310-...

    1TE32-1AA3
    (110 kW)

    1TE32-6AA3
    (132 kW)

    1TE33-1AA3
    (160 kW)

    1TE33-8AA3
    (200 kW)

    1TE35-0AA3
    (250 kW)

    Suitable for Basic Line Module in chassis format

    • Air-cooled
      (rated power)

    6SL3330-...

    1TE34-2AA3
    (200 kW)

    1TE35-3AA3
    (250 kW)

    1TE38-2AA3
    (400 kW)

    1TE41-2AA3
    (560 kW)

    1TE41-5AA3
    (710 kW)

    1TE41-8AA3
    (900 kW)



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    Line voltage 500 ... 690 V 3 AC

    Line filter

     

    6SL3000-0BG34-4AA0

    6SL3000-0BG36-0AA0

    6SL3000-0BG41-2AA0

    6SL3000-0BG41-6AA0

    Rated current

    A

    440

    600

    1200

    1600

    Power loss 1)

    At 50 Hz

    kW

    0.047

    0.053

    0.119

    0.153

    Load/line supply connection

     

    1 × hole for M10

    Provided for busbar connection

    1 × hole for M10

    Provided for busbar connection

    2 × hole for M12

    Provided for busbar connection

    2 × hole for M12

    Provided for busbar connection

    PE connection

     

    Hole for M8

    Hole for M10

    Hole for M10

    Hole for M10

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    360 (14.2)

    400 (15.7)

    425 (16.7)

    505 (19.9)

    • Height

    mm (in)

    240 (9.45)

    265 (10.4)

    265 (10.4)

    265 (10.4)

    • Depth

    mm (in)

    116 (4.57)

    140 (5.51)

    145 (5.71)

    145 (5.71)

    Weight, approx.

    kg (lb)

    12.3 (27)

    19 (42)

    25.2 (56)

    28.8 (63)

    Suitable for Basic Line Module in chassis format

     
    • Air-cooled
      (rated power)

    6SL3330-...

    1TG33-0AA3
    (250 kW)

    1TG34-3AA3
    (355 kW)

    1TG36-8AA3
    (560 kW)

    1TG41-1AA3
    (900 kW)

    1TG41-4AA3
    (1100 kW)

    1TG41-8AA3
    (1500 kW)



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    Line voltage 380 ... 480 V 3 AC

    Line filter

     

    6SL3000-0BE33-1AA0

    6SL3000-0BE35-0AA0

    6SL3760-0MB00-0AA0

    6SL3760-0MC00-0AA0

    Rated current

    A

    400

    600

    840

    1405

    Power loss 1)

    At 50 Hz

    kW

    0.042

    0.06

    0.058

    0.111

    Load/line supply connection

     

    M10 connecting lugs

    M10 connecting lugs

    M10 connecting lugs

    M10 connecting lugs

    PE connection

     

    Hole for M8

    Hole for M10

    Hole for M10

    Hole for M10

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    360 (14.2)

    390 (15.3)

    425 (16.7)

    505 (19.9)

    • Height

    mm (in)

    240 (9.45)

    265 (10.4)

    265 (10.4)

    265 (10.4)

    • Depth

    mm (in)

    116 (4.57)

    140 (5.51)

    145 (5.71)

    145 (5.71)

    Weight, approx.

    kg (lb)

    12.7 (28)

    19.9 (44)

    25.9 (57)

    28.9 (64)

    Suitable for Smart Line Module in chassis format

    • Air-cooled
      (rated power)

    6SL3330-...

    6TE35-5AA3
    (250 kW)

    6TE37-3AA3
    (355 kW)

    6TE41-1AA3
    (500 kW)

    6TE41-3AA3
    (630 kW)

    6TE41-7AA3
    (800 kW)

    Suitable for Active Line Module in chassis format

    • Air-cooled
      (rated power)

    6SL3330-...

    7TE32-1AA3
    (132 kW)

    7TE32-6AA3
    (160 kW)

    7TE33-8AA3
    (235 kW)

    7TE35-0AA3
    (300 kW)

    7TE36-1AA3
    (380 kW)

    7TE37-5AA3
    (450 kW)

    7TE38-4AA3
    (500 kW)

    7TE41-0AA3
    (630 kW)

    7TE41-2AA3
    (800 kW)

    7TE41-4AA3
    (900 kW)



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    Line voltage 500 ... 690 V 3 AC

    Line filter

     

    6SL3760-0ME00-0AA0

    6SL3760-0MN00-0AA0

    6SL3760-0MG00-0AA0

    Rated current

    A

    600

    1025

    1270

    Power loss 1)

    At 50 Hz

    kW

    0.063

    0.063

    0.097

    Load/line supply connection

     

    M10 connecting lugs

    M12 connecting lugs

    M12 connecting lugs

    PE connection

     

    Hole for M10

    Hole for M10

    Hole for M10

    Degree of protection

     

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

    • Width

    mm (in)

    400 (15.7)

    425 (16.7)

    505 (19.9)

    • Height

    mm (in)

    365 (14.4)

    365 (14.4)

    365 (14.4)

    • Depth

    mm (in)

    140 (5.51)

    145 (5.71)

    145 (5.71)

    Weight, approx.

    kg (lb)

    27 (60)

    36.7 (81)

    36.7 (81)

    Suitable for Smart Line Module in chassis format

    • Air-cooled
      (rated power)

    6SL3330-...

    6TG35-5AA3
    (450 kW)

    6TG38-8AA3
    (710 kW)

    6TG41-2AA3
    (1000 kW)

    6TG41-7AA3
    (1400 kW)

    Suitable for Active Line Module in chassis format

    • Air-cooled
      (rated power)

    6SL3330-...

    7TG35-8AA3
    (630 kW)

    7TG37-4AA3
    (800 kW)

    7TG41-0AA3
    (1100 kW)

    7TG41-3AA3
    (1400 kW)



    1) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.