Товаров
  
корзина пуста
  • Каталог оборудования Siemens

DC link fuses

  • Заказные данные
    (24)
  • Информационные материалы

    Информационные материалы

    Suitable DC link fuses are assigned depending on the power rating of the Motor Modules.

    Further information about the fuses listed is provided in the Catalogs IC 10 and LV 10.

    Assignment of the DC link fuses to the Motor Modules chassis format, liquid-cooled

    Type rating
    at 400 V

    Rated DC link current for power supplied via Basic Line Module / Active Line Module

    Suitable for Motor Module chassis format

    DC link fuse according to IEC

    DC link fuse according to UL 1)

     

     

     

    Rated current

    Quantity/
    Phase

    Frame size

     

    Rated current

    Quantity/
    Phase

    Frame size

     

    kW (hp)

    A

    6SL3325-...

    A

     

     

    Article No.

    A

     

     

    Article No.

    Line voltage 380 V ... 480 V 3 AC

    110 (150)

    256/230

    1TE32-1AA3

    315

    1

    1

    3NE3230-0B

    315

    1

    1

    3NE3230-0B

    315

    1

    2L

    3NB1231-4KK11

    132 (200)

    317/287

    1TE32-6AA3

    400

    1

    1

    3NE3232-0B

    400

    1

    1

    3NE3232-0B

    400

    1

    2L

    3NB1234-4KK11

    160 (250)

    380/340

    1TE33-1AA3

    450

    1

    1

    3NE3233

    450

    1

    1

    3NE3233

    500

    1

    3L

    3NB1337-4KK11

    250 (400)

    600/538

    1TE35-0AA3

    630

    1

    2

    3NE3236

    630

    1

    2

    3NE3236

    800

    1

    3L

    3NB1345-4KK11

    315 (500)

    738/664

    1TE36-1AA3

    800

    1

    2

    3NE3338-8

    800

    1

    2

    3NE3338-8

    800

    1

    3L

    3NB2345-4KK16

    400 (600)

    894/805

    1TE37-5AA3

    500

    2

    2

    3NE3334-0B

    1000

    1

    3L

    3NB2350-4KK16

    450 (700)

    1025/922

    1TE38-4AA3

    560

    2

    2

    3NE3335

    560

    2

    2

    3NE3335

    1000

    1

    3L

    3NB2350-4KK16

    560 (800)

    1202/1080

    1TE41-0AA3

    630

    2

    2

    3NE3336

    630

    2

    2

    3NE3336

    1400

    1

    3L

    3NB2355-4KK16

    710 (1000)

    1512/1361

    1TE41-2AA3

    900

    2

    2

    3NE3340-8

    2100

    1

    3L

    3NB2364-4KK17

    800 (1150)

    1714/1544

    1TE41-4AA3

    900

    2

    2

    3NE3340-8

    900

    2

    2

    3NE3340-8

    2100

    1

    3L

    3NB2364-4KK17

    800 (1000)

    1550/1403

    1TE41-4AS3 2)

    900

    2

    2

    3NE3340-8

    2100

    1

    3L

    3NB2364-4KK17



    1) To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.

    2) This Motor Module has been specifically designed for loads demanding a high dynamic performance.

    Type rating
    at 690 V

    Rated DC link current for power supplied via Basic Line Module / Active Line Module

    Suitable for Motor Module chassis format

    DC link fuse according to IEC

    DC link fuse according to UL 1)

     

     

     

    Rated current

    Quantity/
    Phase

    Frame size

     

    Rated current

    Quantity/
    Phase

    Frame size

     

    kW (hp)

    A

    6SL3325-...

    A

     

     

    Article No.

    A

     

     

    Article No.

    Line voltage 500 … 690 V 3 AC

    90 (75)

    122/110

    1TG31-0AA3

    160

    1

    1

    3NE3224

    160

    1

    1

    3NE3224

    200

    1

    1L

    3NB1126-4KK11

    132 (150)

    183/165

    1TG31-5AA3

    200

    1

    1

    3NE3225

    200

    1

    1

    3NE3225

    250

    1

    1L

    3NB1128-4KK11

    200 (200)

    263/237

    1TG32-2AA3

    315

    1

    1

    3NE3230-0B

    315

    1

    1

    3NE3230-0B

    315

    1

    2L

    3NB1231-4KK11

    315 (300)

    403/363

    1TG33-3AA3

    450

    1

    2

    3NE3233

    450

    1

    2

    3NE3233

    500

    1

    3L

    3NB1337-4KK11

    450 (450)

    558/502

    1TG34-7AA3

    630

    1

    2

    3NE3336

    800

    1

    3L

    3NB1345-4KK11

    560 (600)

    702/632

    1TG35-8AA3

    400

    2

    1

    3NE3232-0B

    400

    2

    1

    3NE3232-0B

    800

    1

    3L

    3NB2345-4KK16

    710 (700)

    903/759

    1TG37-4AA3

    560

    2

    2

    3NE3335

    1000

    1

    3L

    3NB2350-4KK16

    800 (800)

    990/891

    1TG38-0AA3 2)

    560

    2

    2

    3NE3335

    1000

    1

    3L

    3NB2350-4KK16

    800 (800)

    990/891

    1TG38-1AA3

    560

    2

    2

    3NE3335

    560

    2

    2

    3NE3335

    1000

    1

    3L

    3NB2350-4KK16

    1000 (1000)

    1250/1125

    1TG41-0AA3

    710

    2

    2

    3NE3337-8

    710

    2

    2

    3NE3337-8

    1600

    1

    3L

    3NB2357-4KK16

    1200 (1250)

    1550/1395

    1TG41-3AA3

    900

    2

    2

    3NE3340-8

    900

    2

    2

    3NE3340-8

    2100

    1

    3L

    3NB2364-4KK17

    1500 (1500)

    1903/1605

    1TG41-6AA3

    710

    3

    2

    3NE3337-8

    2400

    1

    3L

    3NB2366-4KK17



    1) To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.

    2) Device 6SL3325-1TG38-0AA3 is optimized for a base pulse frequency of 1.25 kHz, for an increased pulse frequency, the derating factor is higher than for the device 6SL3325-1TG38-1AA3.