Active Interface Modules in booksize format

  • Заказные данные
    (5)
  • Аксессуары
    (7)
  • Информационные материалы

    Информационные материалы

    Active Interface Modules for 16 kW, 36 kW, 55 kW and 80 kW/120 kW

    The Active Interface Modules combine with the Active Line Modules to form a functional unit and are required for operation of the associated Active Line Module. The Active Interface Modules contain a Clean Power Filter and basic interference suppression to ensure compliance with Category C3 in accordance with EN 61800-3 with respect to emitted interference.

    The Clean Power Filter protects the mains connection from switching-frequency harmonics. The drive system therefore draws a sinusoidal current from the supply and causes almost no harmonics.

    The Active Line Modules in combination with the Active Interface Module can also be operated with supply systems with an isolated star point (IT supply systems).

    Дизайн

    The scope of supply of the Active Interface Modules includes:

    • Connector X21 for temperature evaluation and fan control
    • Connector X24 for connecting the 24 V supply for the integrated fan
    • DRIVE‑CLiQ cable for connecting the Control Unit to the Active Line Module; length of the DRIVE‑CLiQ cable = width of the Active Interface Module + 0.11 m (4.33 in)
    • Shield connection plate for Active Interface Module 16 kW
    • 1 set of warning signs in 30 languages

    Характеристика

    Overload capability

    Duty cycle with previous load

    S6 duty cycle with previous load

    S6 duty cycle with previous load

    55 kW Active Line Module only:

    Peak power load duty cycle with previous load

    Derating characteristics

    Output power as a function of ambient temperature

    Installation altitude

    • >1000 ... 4000 m (3281 ... 13124 ft) above sea level
      • Reduction of the output current by 10 % per 1000 m (3281 ft), or
      • Reduction of the ambient temperature by 5 °C (41 °F) per 1000 m (3281 ft)
    • >2000 ... 4000 m (6562 ... 13124 ft) above sea level
      • Operation on line supply systems with grounded neutral point, or
      • Operation with an isolating transformer with secondary grounded neutral point

    Интеграция

    Connection example for Active Interface Module

    The Active Interface Module requires a 24 V DC supply for operation of the integral fan.
    The fan rotates after the 24 V DC supply is applied and can, if necessary (service life, noise), be disconnected from the Control Unit over the "Fan off" input. It is only permitted to switch off the fan when the infeed of the drive system is not operating, otherwise the Active Interface Module will overheat.

    The thermostatic switch installed in the Active Interface Module is evaluated over the connected Active Line Module.

    The power cables between the Active Interface Module and Active Line Module must be shielded if limit values for interference suppression are to be complied with. The cable shield can be routed over the shield connection plate (option) to the Active Interface Module or Active Line Module.

    Depending on the position of the Active Interface Module in the drive system, additional DRIVE-CLiQ cables may be required. If it is separately installed next to the left side of the Control Unit and Active Line Module, no additional DRIVE-CLiQ cables are required. If the Active Interface Module is placed between the Control Unit and Active Line Module, the DRIVE-CLiQ cables supplied with the Active Line Modules are suitable for setting up a line topology, i.e. Active Line Module and all Motor Modules in series on one DRIVE-CLiQ line. If the Active Line Module is connected over a separate DRIVE-CLiQ line, the DRIVE-CLiQ cable marked with (1) must be ordered. A DRIVE-CLiQ cable suitable for connection (2) is included in the scope of supply of the Active Line Module.

    For DRIVE-CLiQ cables for different configurations, see section MOTION-CONNECT connection systems.

    Separate Active Interface Module

    Active Interface Module integrated in the drive line-up

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    Active Interface Module

    Internal air cooling

    6SL3100-0BE21-6AB0

    6SL3100-0BE23-6AB0

    6SL3100-0BE25-5AB0

    6SL3100-0BE28-0AB0

    6SL3100-0BE31-2AB0

    Rated current

    A

    26

    58

    88

    128

    192

    Current requirement

    24 V DC electronics power supply, max.

    A

    0.25

    0.49

    0.6

    1.2

    1.2

    Internal resistance

    Digital input
    "Fan off" (X21/Pin 4)

    Ω 

    1440 ±10 %

    1440 ±10 %

    1440 ±10 %

    1440 ±10 %

    1440 ±10 %

    Power loss

    kW

    0.27

    0.34

    0.38

    0.49

    0.585

    Cooling air requirement

    m3/s (ft3/s)

    0.03 (1.1)

    0.04 (1.4)

    0.083 (2.9)

    0.167 (5.9)

    0.167 (5.9)

    Sound pressure level

    LpA (1 m)

    dB

    57

    60

    66

    68

    68

    Line supply/load connection

    L1, L2, L3/U2, V2, W2

     

    Connector

    Screw terminals

    Screw terminals

    M8 screw studs

    M8 screw studs

    • Conductor cross-section

    mm2

    16

    50

    50

    2.5 … 120 or 2 × 50

    2.5 … 120 or 2 × 50

    Thermostatic switch

    (NC contact)

     

     

     

     

     

     

    • Switching capacity

     

    250 V AC/1.6 A
    60 V DC/0.75 A

    250 V AC/1.6 A
    60 V DC/0.75 A

    250 V AC/1.6 A
    60 V DC/0.75 A

    250 V AC/1.6 A
    60 V DC/0.75 A

    250 V AC/1.6 A
    60 V DC/0.75 A

    PE connection

     

    M5 screw

    M6 screw

    M6 screw

    M8 screw

    M8 screw

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    100 (3.94)

    150 (5.91)

    200 (7.87)

    300 (11.81)

    300 (11.81)

    • Height

    mm (in)

    380 (14.96)

    380 (14.96)

    380 (14.96)

    380 (14.96)

    380 (14.96)

    • Depth

    mm (in)

    270 (10.63)

    270 (10.63)

    270 (10.63)

    270 (10.63)

    270 (10.63)

    Weight, approx.

    kg (lb)

    11.6 (25.6)

    19 (41.9)

    23.2 (51.2)

    31.9 (70.3)

    36.6 (80.7)

    Certificate of suitability

     

    cURus

    cURus

    cURus

    cURus

    cURus

    Suitable for Active Line Module in booksize format

    Type

    6SL3130-7TE21-6AA4

    6SL3130-7TE23-6AA3

    6SL3130-7TE25-5AA3

    6SL3130-7TE28-0AA3

    6SL3130-7TE31-2AA3

    • Rated power of the Active Line Module

    kW (hp)

    16 (18)

    36 (40)

    55 (60)

    80 (100)

    120 (150)