    Motor Modules in chassis format are available in the power range from 75 kW to 1200 kW.

    Line voltage

    DC link voltage

    Type rating

    380 ... 480 V 3 AC

    510 ... 720 V DC

    110 ... 800 kW

    500 ... 690 V 3 AC

    675 ... 1035 V DC

    75 ... 1200 kW



    By connecting in parallel up to four Motor Modules operated on one Control Unit and which supply one motor, it is possible to increase the available shaft power to a maximum of approx. 4500 kW (taking into account the derating factors according to the SINAMICS Low Voltage Engineering Manual).

    SINAMICS S120 Motor Modules in chassis format can also be used as a Braking Module if, instead of a motor, a 3-phase braking resistor is connected.
    For more detailed information on this topic, please refer to the SINAMICS Low Voltage Engineering Manual.

    Дизайн

    Motor Modules in chassis format contain the following components as standard:

    • Retaining device for the DC busbar, including the connection to the DC connections of the Motor Module
    • Nickel-plated connection busbars for motor cables for Motor Modules, frame sizes FX and GX; for Motor Modules, frame sizes HX and JX, the connection is made directly on the unit
    • Cable retaining bar for the power cables
    • DRIVE-CLiQ interface (3 DRIVE‑CLiQ sockets), without Control Unit
    • Customer interface -X55
    • Auxiliary power supply system (6-pole) for the auxiliary power supply, including cable connections for looping through to the next Cabinet Module
    • Nickel-plated PE busbar (60 x 10 mm), including jumper for looping through to the next Cabinet Module
    • EMC-compliant design thanks to additional shielding measures and appropriately routed cables

    Интеграция

    Motor Modules are controlled by the CU320‑2 DP or CU320‑2 PN Control Unit. Communication between the Control Unit and Modules is established via a DRIVE‑CLiQ connection.

    If the Control Unit is integrated in the same cabinet as an option with order code K90 or K95, these communication cables will already be installed. If the Control Unit is to be mounted externally, the DRIVE‑CLiQ cable will not be included in the scope of delivery and must be configured on site.

    For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    For a description of the terminal block, see section Customer terminal block -X55.

    Connection example: Motor Module in chassis format

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    DC link voltage 510 ... 720 V DC

    Motor Modules in chassis format

     

    6SL3720-1TE32-1AA3

    6SL3720-1TE32-6AA3

    6SL3720-1TE33-1AA3

    6SL3720-1TE33-8AA3

    6SL3720-1TE35-0AA3

    6SL3720-1TE36-1AA3

    Type rating

     

     

     

     

     

     

     

    • At IL (50 Hz 400 V) 1)

    kW

    110

    132

    160

    200

    250

    315

    • At IH (50 Hz 400 V) 1)

    kW

    90

    110

    132

    160

    200

    250

    • At IL (60 Hz 460 V) 2)

    hp

    150

    200

    250

    300

    400

    500

    • At IH (60 Hz 460 V) 2)

    hp

    150

    200

    200

    250

    350

    350

    Output current

     

     

     

     

     

     

     

    • Rated current Irated O

    A

    210

    260

    310

    380

    490

    605

    • Base-load current IL3)

    A

    205

    250

    302

    370

    477

    590

    • Base-load current IH4)

    A

    178

    233

    277

    340

    438

    460

    • Maximum current Imax O

    A

    307

    375

    453

    555

    715

    885

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    252

    312

    372

    456

    588

    726

    • Active Line Module

    A

    227

    281

    335

    411

    529

    653

    • Base-load current IL DC 3)
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    245

    304

    362

    444

    573

    707

    • Active Line Module

    A

    221

    273

    326

    400

    515

    636

    • Base-load current IH DC 4)
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    224

    277

    331

    405

    523

    646

    • Active Line Module

    A

    202

    250

    298

    365

    470

    581

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    0.8

    0.8

    0.9

    0.9

    0.9

    1.0

    • 400 V AC

    A

    0.63

    1.13

    1.8

    1.8

    1.8

    3.6

    DC link capacitance

    μF

    4200

    5200

    6300

    7800

    9600

    12600

    Pulse frequency 5)

     

     

     

     

     

     

     

    • Rated frequency

    kHz

    2

    2

    2

    2

    2

    1.25

    • Pulse frequency, max.
           
    • Without current derating

    kHz

    2

    2

    2

    2

    2

    1.25

    • With current derating

    kHz

    8

    8

    8

    8

    8

    7.5

    Power loss, max. 6)

     

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    1.86

    2.5

    2.96

    3.67

    4.28

    5.84

    • At 60 Hz 460 V

    kW

    1.94

    2.6

    3.1

    3.8

    4.5

    6.3

    Cooling air requirement

    m3/s

    0.17

    0.23

    0.36

    0.36

    0.36

    0.78

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    67

    69

    69

    69

    69

    72

    Motor connection

    U2, V2, W2

     

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    • Conductor cross section, max. (IEC)

    mm2

    2 × 185

    2 × 185

    2 × 240

    2 × 240

    2 × 240

    4 × 240

    Cable length, max. 7)

     

     

     

     

     

     

     

    • Shielded

    m

    300

    300

    300

    300

    300

    300

    • Unshielded

    m

    450

    450

    450

    450

    450

    450

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    240

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

     

    • Width 8)

    mm

    400

    400

    400

    400

    400

    600

    • Height 9)

    mm

    2200

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    145

    145

    286

    286

    286

    490

    Frame size

     

    FX

    FX

    GX

    GX

    GX

    HX

    Short-circuit current rating according to IEC

    kA

    65

    65

    65

    65

    65

    65



    1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

    2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

    3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

    4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

    5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

    6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

    With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

    - Frame size HX/JX: Additional cabinet 600 mm wide.

    9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

     

    Line voltage 380 ... 480 V 3 AC

    DC link voltage 510 ... 720 V DC

    Motor Modules in chassis format

     

    6SL3720-1TE37-5AA3

    6SL3720-1TE38-4AA3

    6SL3720-1TE41-0AA3

    6SL3720-1TE41-2AA3

    6SL3720-1TE41-4AA3

    Type rating

     

     

     

     

     

     

    • At IL (50 Hz 400 V) 1)

    kW

    400

    450

    560

    710

    800

    • At IH (50 Hz 400 V) 1)

    kW

    315

    400

    450

    560

    710

    • At IL (60 Hz 460 V) 2)

    hp

    600

    700

    800

    1000

    1150

    • At IH (60 Hz 460 V) 2)

    hp

    450

    600

    700

    900

    1000

    Output current

     

     

     

     

     

     

    • Rated current Irated O

    A

    745

    840

    985

    1260

    1405

    • Base-load current IL3)

    A

    725

    820

    960

    1230

    1370

    • Base-load current IH4)

    A

    570

    700

    860

    1127

    1257

    • Maximum current Imax O

    A

    1087

    1230

    1440

    1845

    2055

    DC link current

     

     

     

     

     

     

    • Rated current Irated DC
      when supplied via

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    894

    1008

    1182

    1512

    1686

    • Active Line Module

    A

    805

    907

    1064

    1361

    1517

    • Base-load current IL DC 3)
      when supplied via

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    871

    982

    1152

    1474

    1643

    • Active Line Module

    A

    784

    884

    1037

    1326

    1479

    • Base-load current IH DC 4)
      when supplied via

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    795

    897

    1051

    1345

    1500

    • Active Line Module

    A

    716

    807

    946

    1211

    1350

    Current demand

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.0

    1.0

    1.25

    1.4

    1.4

    • 400 V AC

    A

    3.6

    3.6

    5.4

    5.4

    5.4

    DC link capacitance

    μF

    15600

    16800

    18900

    26100

    28800

    Pulse frequency 5)

     

     

     

     

     

     

    • Rated frequency

    kHz

    1.25

    1.25

    1.25

    1.25

    1.25

    • Pulse frequency, max.

     

     

     

     

     

     

    • Without current derating

    kHz

    1.25

    1.25

    1.25

    1.25

    1.25

    • With current derating

    kHz

    7.5

    7.5

    7.5

    7.5

    7.5

    Power loss, max. 6)

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    6.68

    7.15

    9.5

    11.1

    12.0

    • At 60 Hz 460 V

    kW

    7.3

    7.8

    10.2

    12.0

    13.0

    Cooling air requirement

    m3/s

    0.78

    0.78

    1.08

    1.08

    1.08

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    72

    72

    72

    72

    72

    Motor connection

    U2, V2, W2

     

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    • Conductor cross section, max. (IEC)

    mm2

    4 × 240

    4 × 240

    6 × 240

    6 × 240

    6 × 240

    Cable length, max. 7)

     

     

     

     

     

     

    • Shielded

    m

    300

    300

    300

    300

    300

    • Unshielded

    m

    450

    450

    450

    450

    450

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

    • Width 8)

    mm

    600

    600

    800

    800

    800

    • Height 9)

    mm

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    490

    490

    700

    700

    700

    Frame size

     

    HX

    HX

    JX

    JX

    JX

    Short-circuit current rating according to IEC

    kA

    65

    84

    84

    100

    100



    1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

    2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

    3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

    4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

    5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

    6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

    With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

    - Frame size HX/JX: Additional cabinet 600 mm wide.

    9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

     

    Line voltage 500 ... 690 V 3 AC

    DC link voltage 675 … 1035 V DC

    Motor Modules in chassis format

     

    6SL3720-1TG28-5AA3

    6SL3720-1TG31-0AA3

    6SL3720-1TG31-2AA3

    6SL3720-1TG31-5AA3

    6SL3720-1TG31-8AA3

    6SL3720-1TG32-2AA3

    Type rating

     

     

     

     

     

     

     

    • At IL (50 Hz 690 V) 1)

    kW

    75

    90

    110

    132

    160

    200

    • At IH (50 Hz 690 V) 1)

    kW

    55

    75

    90

    110

    132

    160

    • At IL (50 Hz 500 V) 1)

    kW

    55

    55

    75

    90

    110

    132

    • At IH (50 Hz 500 V) 1)

    kW

    45

    55

    75

    90

    90

    110

    • At IL (60 Hz 575 V) 2)

    hp

    75

    75

    100

    150

    150

    200

    • At IH (60 Hz 575 V) 2)

    hp

    75

    75

    100

    125

    150

    200

    Output current

     

     

     

     

     

     

     

    • Rated current Irated O

    A

    85

    100

    120

    150

    175

    215

    • Base-load current IL3)

    A

    80

    95

    115

    142

    170

    208

    • Base-load current IH4)

    A

    76

    89

    107

    134

    157

    192

    • Maximum current Imax O

    A

    120

    142

    172

    213

    255

    312

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    102

    120

    144

    180

    210

    258

    • Active Line Module

    A

    92

    108

    130

    162

    189

    232

    • Base-load current IL DC 3)
      when supplied via

     

          
    • Basic/Smart Line Module

    A

    99

    117

    140

    175

    204

    251

    • Active Line Module

    A

    89

    105

    126

    157

    184

    226

    • Base-load current IH DC 4)
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    90

    106

    128

    160

    186

    229

    • Active Line Module

    A

    81

    96

    115

    144

    168

    206

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    0.8

    0.8

    0.8

    0.8

    0.9

    0.9

    • 690 V AC

    A

    0.4

    0.4

    0.4

    0.4

    1.0

    1.0

    DC link capacitance

    μF

    1200

    1200

    1600

    2800

    2800

    2800

    Pulse frequency 5)

     

     

     

     

     

     

     

    • Rated frequency

    kHz

    1.25

    1.25

    1.25

    1.25

    1.25

    1.25

    • Pulse frequency, max.

     

     

     

     

     

     

     

    • Without current derating

    kHz

    1.25

    1.25

    1.25

    1.25

    1.25

    1.25

    • With current derating

    kHz

    7.5

    7.5

    7.5

    7.5

    7.5

    7.5

    Power loss, max. 6)

     

     

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    1.17

    1.43

    1.89

    1.8

    2.67

    3.09

    • At 60 Hz 575 V

    kW

    1.1

    1.3

    1.77

    1.62

    2.5

    2.91

    Cooling air requirement

    m3/s

    0.17

    0.17

    0.17

    0.17

    0.36

    0.36

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    67

    67

    67

    67

    69

    69

    Motor connection

    U2, V2, W2

     

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    • Conductor cross section, max. (IEC)

    mm2

    2 × 185

    2 × 185

    2 × 185

    2 × 185

    2 × 240

    2 × 240

    Cable length, max. 7)

     

     

     

     

     

     

     

    • Shielded

    m

    300

    300

    300

    300

    300

    300

    • Unshielded

    m

    450

    450

    450

    450

    450

    450

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    240

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

     

    • Width 8)

    mm

    400

    400

    400

    400

    400

    400

    • Height 9)

    mm

    2200

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    145

    145

    145

    145

    286

    286

    Frame size

     

    FX

    FX

    FX

    FX

    GX

    GX

    Short-circuit current rating according to IEC

    kA

    65

    65

    65

    65

    65

    65



    1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz. 

    2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

    3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

    4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

    5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

    6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

    With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

    - Frame size HX/JX: Additional cabinet 600 mm wide.

    9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

     

    Line voltage 500 ... 690 V 3 AC

    DC link voltage 675 … 1035 V DC

    Motor Modules in chassis format

     

    6SL3720-1TG32-6AA3

    6SL3720-1TG33-3AA3

    6SL3720-1TG34-1AA3

    6SL3720-1TG34-7AA3

    6SL3720-1TG35-8AA3

    6SL3720-1TG37-4AA3

    Type rating

     

     

     

     

     

     

     

    • At IL (50 Hz 690 V) 1)

    kW

    250

    315

    400

    450

    560

    710

    • At IH (50 Hz 690 V) 1)

    kW

    200

    250

    315

    400

    450

    630

    • At IL (50 Hz 500 V) 1)

    kW

    160

    200

    250

    315

    400

    500

    • At IH (50 Hz 500 V) 1)

    kW

    132

    160

    200

    250

    315

    450

    • At IL (60 Hz 575 V) 2)

    hp

    250

    300

    400

    450

    600

    700

    • At IH (60 Hz 575 V) 2)

    hp

    200

    250

    350

    450

    500

    700

    Output current

     

     

     

     

     

     

     

    • Rated current Irated O

    A

    260

    330

    410

    465

    575

    735

    • Base-load current IL3)

    A

    250

    320

    400

    452

    560

    710

    • Base-load current IH4)

    A

    233

    280

    367

    416

    514

    657

    • Maximum current Imax O

    A

    375

    480

    600

    678

    840

    1065

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    312

    396

    492

    558

    690

    882

    • Active Line Module

    A

    281

    356

    443

    502

    621

    794

    • Base-load current IL DC 3)
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    304

    386

    479

    544

    672

    859

    • Active Line Module

    A

    273

    347

    431

    489

    605

    774

    • Base-load current IH DC 4)
      when supplied via

     

     

     

     

     

     

     

    • Basic/Smart Line Module

    A

    277

    352

    437

    496

    614

    784

    • Active Line Module

    A

    250

    316

    394

    446

    552

    706

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    0.9

    0.9

    1.0

    1.0

    1.0

    1.25

    • 690 V AC

    A

    1.0

    1.0

    2.1

    2.1

    2.1

    3.1

    DC link capacitance

    μF

    3900

    4200

    7400

    7400

    7400

    11100

    Pulse frequency 5)

     

     

     

     

     

     

     

    • Rated frequency

    kHz

    1.25

    1.25

    1.25

    1.25

    1.25

    1.25

    • Pulse frequency, max.

     

     

     

     

     

     

     

    • Without current derating

    kHz

    1.25

    1.25

    1.25

    1.25

    1.25

    1.25

    • With current derating

    kHz

    7.5

    7.5

    7.5

    7.5

    7.5

    7.5

    Power loss, max. 6)

     

     

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    3.62

    4.34

    6.13

    6.8

    10.3

    10.9

    • At 60 Hz 575 V

    kW

    3.38

    3.98

    5.71

    6.32

    9.7

    10.0

    Cooling air requirement

    m3/s

    0.36

    0.36

    0.78

    0.78

    0.78

    1.08

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    69

    69

    72

    72

    72

    72

    Motor connection

    U2, V2, W2

     

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    4 × 240

    4 × 240

    4 × 240

    6 × 240

    Cable length, max. 7)

     

     

     

     

     

     

     

    • Shielded

    m

    300

    300

    300

    300

    300

    300

    • Unshielded

    m

    450

    450

    450

    450

    450

    450

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    240

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

     

    • Width 8)

    mm

    400

    400

    600

    600

    600

    800

    • Height 9)

    mm

    2200

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    286

    286

    490

    490

    490

    700

    Frame size

     

    GX

    GX

    HX

    HX

    HX

    JX

    Short-circuit current rating according to IEC

    kA

    65

    65

    65

    84

    84

    100



    1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

    2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

    3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

    4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

    5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

    6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

    With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

    - Frame size HX/JX: Additional cabinet 600 mm wide.

    9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

     

    Line voltage 500 ... 690 V 3 AC

    DC link voltage 675 … 1035 V DC

    Motor Modules in chassis format

     

    6SL3720-1TG38-1AA3

    6SL3720-1TG38-8AA3

    6SL3720-1TG41-0AA3

    6SL3720-1TG41-3AA3

    Type rating

     

     

     

     

     

    • At IL (50 Hz 690 V) 1)

    kW

    800

    900

    1000

    1200

    • At IH (50 Hz 690 V) 1)

    kW

    710

    800

    900

    1000

    • At IL (50 Hz 500 V) 1)

    kW

    560

    630

    710

    900

    • At IH (50 Hz 500 V) 1)

    kW

    500

    560

    630

    800

    • At IL (60 Hz 575 V) 2)

    hp

    800

    900

    1000

    1250

    • At IH (60 Hz 575 V) 2)

    hp

    700

    800

    900

    1000

    Output current

     

     

     

     

     

    • Rated current Irated O

    A

    810

    910

    1025

    1270

    • Base-load current IL3)

    A

    790

    880

    1000

    1230

    • Base-load current IH4)

    A

    724

    814

    917

    1136

    • Maximum current Imax O

    A

    1185

    1320

    1500

    1845

    DC link current

     

     

     

     

     

    • Rated current Irated DC
      when supplied via

     

     

     

     

     

    • Basic/Smart Line Module

    A

    972

    1092

    1230

    1524

    • Active Line Module

    A

    875

    983

    1107

    1372

    • Base-load current IL DC 3)
      when supplied via

     

     

     

     

     

    • Basic/Smart Line Module

    A

    947

    1064

    1199

    1485

    • Active Line Module

    A

    853

    958

    1079

    1337

    • Base-load current IH DC 4)
      when supplied via

     

     

     

     

     

    • Basic/Smart Line Module

    A

    865

    971

    1094

    1356

    • Active Line Module

    A

    778

    874

    985

    1221

    Current demand

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.25

    1.4

    1.4

    1.4

    • 690 V AC

    A

    3.1

    3.1

    3.1

    3.1

    DC link capacitance

    μF

    11100

    14400

    14400

    19200

    Pulse frequency 5)

     

     

     

     

     

    • Rated frequency

    kHz

    1.25

    1.25

    1.25

    1.25

    • Pulse frequency, max.

     

     

     

     

     

    • Without current derating

    kHz

    1.25

    1.25

    1.25

    1.25

    • With current derating

    kHz

    7.5

    7.5

    7.5

    7.5

    Power loss, max. 6)

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    11.5

    11.7

    13.2

    16.0

    • At 60 Hz 575 V

    kW

    10.5

    10.6

    12.0

    14.2

    Cooling air requirement

    m3/s

    1.08

    1.08

    1.08

    1.08

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    72

    72

    72

    72

    Motor connection

    U2, V2, W2

     

    M12 screws

    M12 screws

    M12 screws

    M12 screws

    • Conductor cross section, max. (IEC)

    mm2

    6 x 240

    6 x 240

    6 x 240

    6 x 240

    Cable length, max. 7)

     

     

     

     

     

    • Shielded

    m

    300

    300

    300

    300

    • Unshielded

    m

    450

    450

    450

    450

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

    • Width 8)

    mm

    800

    800

    800

    800

    • Height 9)

    mm

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    Weight, approx.

    kg

    700

    700

    700

    700

    Frame size

     

    JX

    JX

    JX

    JX

    Short-circuit current rating according to IEC

    kA

    100

    100

    100

    100



    1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

    2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

    3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

    4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

    5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

    6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

    With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

    - Frame size HX/JX: Additional cabinet 600 mm wide.

    9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.