    Basic Line Modules (BLM) are compact line infeeds for two-quadrant operation, i.e. no regenerative feedback.

    They are used when energy need not be fed back into the network.

    If regenerative conditions occur in the drive line-up, Braking Modules must be used because they convert the excess energy into heat in braking resistors.

    Basic Line Modules are suitable for connection to grounded TN/TT and non-grounded IT systems. The following voltages and power ratings are available:

    Line voltage

    Rated power

    380 ... 480 V 3 AC

    200 ... 900 kW

    500 ... 690 V 3 AC

    250 ... 1500 kW



    The power ratings can be increased by connecting up to four identical Basic Line Modules in parallel.

    For an infeed with the Basic Line Modules, depending on the line short-circuit power, a line reactor should be provided at the connection point. This reactor is available as standard in the Line Connection Module. However, it can be omitted if it is not required (option L22).
    For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    Дизайн

    The Basic Line Modules are available in different frame sizes.

    With frame sizes FB and GB, a fully controlled thyristor bridge is used to pre-charge the Basic Line Modules and connected Motor Modules. The thyristors normally operate with a trigger delay angle of 0°.

    Basic Line Modules, frame size GD for 900 kW (400 V) or 1500 kW (690 V) include a diode bridge, and the DC link is pre-charged via a separate line-side pre-charging device that is located in the Line Connection Module (option L43, Line Connection Module for Basic Line Module).

    Parallel connection of Basic Line Modules to increase power rating

    Line Modules can be connected in parallel (relative to the line supply) in two ways for the purpose of creating drive line-ups with a higher power rating.

    Two Basic Line Modules supplied with power via two separate Line Connection Modules

    With this arrangement, each Basic Line Module is supplied via a Line Connection Module and the Basic Line Modules are protected by fuses or circuit breakers (at I > 800 A) in the Line Connection Module. A Basic Line Module is assigned to a Line Connection Module and is mechanically coupled. It is not necessary to mechanically directly couple both "groups" comprising Line Connection Module and Basic Line Module. Other modules can also be inserted in between.

    Two Basic Line Modules supplied with power via a single Line Connection Module

    Basic Line Modules are available that can be operated on a single Line Connection Module. These can be connected to the left and right of the Line Connection Module. The power connections on the Basic Line Module on the left of the Line Connection Module are a mirror image (article no. with "C" in the next to last position, example: 6SL3730-1T.41-.BC3), which results in a very compact design for the line infeed.

    For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    These module versions feature integrated line-side fuses which are required because the circuit breaker in the Line Connection Module is not capable of providing selective protection for the Basic Line Modules. They are therefore 200 mm wider in each case than version 6SL3730‑1T...‑.AA3.

    Note:

    If the Basic Line Modules are supplied with power via the same circuit breaker, line-side fuses are provided to ensure selective individual protection of the modules. This arrangement increases the cabinet width by 200 mm (dimension data in selection tables includes extra width).

    Please note that only Basic Line Modules with exactly the same output rating may be connected in parallel. The potential for imbalances in current distribution means that current derating of 7.5 % applies and this must be taken into account when the modules are dimensioned.

    A connection of the Basic Line Modules connected in parallel using DRIVE-CLiQ must be taken into consideration.

    For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    Интеграция

    Connection example of a Basic Line Module

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    Basic Line Modules

     

    6SL3730-1TE34-2AA3

    6SL3730-1TE35-3AA3

    6SL3730-1TE38-2AA3

    6SL3730-1TE41-2AA3

    6SL3730-1TE41-5AA3

    6SL3730-1TE41-8AA3

    For a parallel circuit configuration,
    mounted to the right of the Line Connection Module

     

     

     

    6SL3730-1TE41-2BA3

    6SL3730-1TE41-5BA3

    6SL3730-1TE41-8BA3

    For a parallel circuit configuration,
    mounted to the left of the Line Connection Module

     

     

     

    6SL3730-1TE41-2BC3

    6SL3730-1TE41-5BC3

    6SL3730-1TE41-8BC3

    Rated power

     

     

     

     

     

     

     

    • At Irated DC (50 Hz 400 V)

    kW

    200

    250

    400

    560

    710

    900

    • At IH DC (50 Hz 400 V)

    kW

    160

    200

    315

    450

    560

    705

    • At Irated DC (60 Hz 460 V)

    hp

    305

    385

    615

    860

    1090

    1390

    • At IH DC (60 Hz 460 V)

    hp

    245

    305

    485

    690

    860

    1090

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC

    A

    420

    530

    820

    1200

    1500

    1880

    • Base-load current IH DC1)

    A

    328

    413

    640

    936

    1170

    1467

    • Maximum current Imax DC

    A

    630

    795

    1230

    1800

    2250

    2820

    Input current

     

     

     

     

     

     

     

    • Rated current Irated I

    A

    365

    460

    710

    1010

    1265

    1630

    • Maximum current Imax I

    A

    547

    690

    1065

    1515

    1897

    2380

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.1

    1.1

    1.1

    1.1

    1.1

    1.1

    • 400 V AC 2)

    A

    Internal

    Internal

    Internal

    Internal

    Internal

    Internal

    DC link capacitance

     

     

     

     

     

     

     

    • Basic Line Module

    μF

    7200

    9600

    14600

    23200

    29000

    34800

    • Drive line-up, max.

    μF

    57600

    76800

    116800

    185600

    232000

    139200

    Power loss, max. 3)

     

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    1.9

    2.1

    3.2

    4.6

    5.5

    6.9

    • At 60 Hz 460 V

    kW

    1.9

    2.1

    3.2

    4.6

    5.5

    6.9

    Cooling air requirement

    m3/s

    0.17

    0.17

    0.17

    0.36

    0.36

    0.36

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    66/68

    66/68

    66/68

    71/73

    71/73

    71/73

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    240

    Cable length, max. 4)

     

     

     

     

     

     

     

    • Shielded

    m

    2600

    2600

    2600

    4000

    4000

    4800

    • Unshielded

    m

    3900

    3900

    3900

    6000

    6000

    7200

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm

    400

    400

    400

    400/600/600

    400/600/600

    400/600/600

    • Height 5)

    mm

    2200

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    166

    166

    166

    320/440/480

    320/440/480

    320/440/480

    Frame size

     

    FB

    FB

    FB

    GB

    GB

    GD

    Short-circuit current rating according to IEC

    kA

    65

    65

    65

    84

    100

    100

    Minimum short-circuit current 6)

    A

    4400

    5200

    10000

    2500

    3200

    4000

    • For connection in parallel

    A

    4000

    5000

    6400



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The current demand for the 400 V AC auxiliary power supply is drawn from the line input voltage.

    3) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request.

    5) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 or IP54.

    6) Current required to ensure reliable tripping of installed protective devices.

     

    Line voltage 500 ... 690 V 3 AC

    Basic Line Modules

     

    6SL3730-1TG33-0AA3

    6SL3730-1TG34-3AA3

    6SL3730-1TG36-8AA3

    6SL3730-1TG41-1AA3

    6SL3730-1TG41-4AA3

    6SL3730-1TG41-8AA3

    For a parallel circuit configuration,
    mounted to the right of the Line Connection Module

     

     

     

    6SL3730-1TG41-1BA3

    6SL3730-1TG41-4BA3

    6SL3730-1TG41-8BA3

    For a parallel circuit configuration,
    mounted to the left of the Line Connection Module

     

     

     

    6SL3730-1TG41-1BC3

    6SL3730-1TG41-4BC3

    6SL3730-1TG41-8BC3

    Rated power

     

     

     

     

     

     

     

    • At Irated DC (50 Hz 690 V)

    kW

    250

    355

    560

    900

    1100

    1500

    • At IH DC (50 Hz 690 V)

    kW

    195

    280

    440

    710

    910

    1220

    • At Irated DC (50 Hz 500 V)

    kW

    175

    250

    390

    635

    810

    1085

    • At IH DC (50 Hz 500 V)

    kW

    165

    235

    365

    595

    755

    1015

    • At Irated DC (60 Hz 575 V)

    hp

    250

    350

    600

    900

    1250

    1500

    • At IH DC (60 Hz 575 V)

    hp

    200

    300

    450

    800

    1000

    1250

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC

    A

    300

    430

    680

    1100

    1400

    1880

    • Base-load current IH DC1)

    A

    234

    335

    530

    858

    1092

    1467

    • Maximum current Imax DC

    A

    450

    645

    1020

    1650

    2100

    2820

    Input current

     

     

     

     

     

     

     

    • Rated current Irated I

    A

    260

    375

    575

    925

    1180

    1580

    • Maximum current Imax I

    A

    390

    563

    863

    1388

    1770

    2370

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.1

    1.1

    1.1

    1.1

    1.1

    1.1

    • 500 V/690 V AC 2)

    A

    Internal

    Internal

    Internal

    Internal

    Internal

    Internal

    DC link capacitance

     

     

     

     

     

     

     

    • Basic Line Module

    μF

    3200

    4800

    7300

    11600

    15470

    19500

    • Drive line-up, max.

    μF

    25600

    38400

    58400

    92800

    123760

    78000

    Power loss, max. 3)

     

     

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    1.5

    2.1

    3

    5.4

    5.8

    7.3

    • At 60 Hz 575 V

    kW

    1.5

    2.1

    3

    5.4

    5.8

    7.3

    Cooling air requirement

    m3/s

    0.17

    0.17

    0.17

    0.36

    0.36

    0.36

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    66/68

    66/68

    66/68

    71/73

    71/73

    71/73

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    240

    Cable length, max. 4)

     

     

     

     

     

     

     

    • Shielded

    m

    1500

    1500

    1500

    2250

    2250

    2750

    • Unshielded

    m

    2250

    2250

    2250

    3375

    3375

    4125

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm

    400

    400

    400

    400/600/600

    400/600/600

    400/600/600

    • Height 5)

    mm

    2200

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    166

    166

    166

    320/440/480

    320/440/480

    320/440/480

    Frame size

     

    FB

    FB

    FB

    GB

    GB

    GD

    Short-circuit current rating according to IEC

    kA

    65

    65

    84

    100

    100

    100

    Minimum short-circuit current 6)

    A

    3000

    4400

    8000

    2000

    2500

    3200

    • For connection in parallel

    A

    4000

    5000

    6400



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The current demand for the 500 V/690 V AC auxiliary power supply is drawn from the line input voltage.

    3) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request.

    5) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 or IP54.

    6) Current required to ensure reliable tripping of installed protective devices.