Smart Line Modules

  • Заказные данные
    (21)
  • Информационные материалы

    Информационные материалы

    Smart Line Modules are non-regulated rectifier/regenerative units. The infeed occurs over a diode jumper, while stable, line-commutated regenerative feedback takes place via IGBTs with 100 % continuous energy regeneration. An autotransformer is not required for regenerative feedback.

    The regenerative capability can be deactivated.

    Smart Line Modules are suitable for connection to grounded TN/TT and non-grounded IT systems. The following voltages and power ratings are available:

    Line voltage

    Rated power

    380 ... 480 V 3 AC

    250 ... 800 kW

    500 ... 690 V 3 AC

    450 ... 1400 kW



    The power ratings can be increased by connecting up to four identical Smart Line Modules in parallel.
    For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    Дизайн

    IGBTs (fundamental frequency-switched) serve as Smart Line Module power semiconductors. Because this reduces switching losses, a high percentage of the power unit current can be utilized.

    The current flows in the direction of the infeed via the freewheeling diodes of the IGBTs. This means that the Smart Line Module behaves in a similar way to the Basic Line Module. If the DC link voltage increases due to regenerative operation of the drives, the IGBTs conduct the current, thus feeding the energy back into the supply system.

    In contrast to Active Line Modules, Smart Line Modules do not require a line-side filter; all they require is a line reactor (4 % uk). The unit has a built-in pre-charging circuit for the DC link capacitors. For this reason, a main contactor or a motor-driven circuit breaker is absolutely essential. By specifying the option with order code L44 for the Line Connection Modules, these components are appropriately accommodated in the Line Connection Module.

    Parallel connection of Smart Line Modules to increase power rating

    Up to four Smart Line Modules with the same power rating can be connected in parallel in order to increase power. Current derating of 7.5% with respect to the rated current of each Smart Line Module must be taken into account when the system is dimensioned.

    A connection of the Smart Line Modules connected in parallel using DRIVE‑CLiQ must be taken into consideration during the engineering phase.

    For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    A 4% reactor is always required upstream of each Smart Line Module for the purpose of current symmetrization. This is integrated as standard. Just as with the Basic Line Modules, "mirror-image" power connections are available for Smart Line Modules, which enable parallel circuits to be realized in a compact design. Units that are arranged to the left of the Line Connection Module have the letter "C" at the penultimate position of the article number.
    Example: 6SL3730‑6TE41‑1BC3 (see also the corresponding diagram for the Basic Line Modules).

    Интеграция

    Connection example of a Smart Line Module

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    Smart Line Modules

     

    6SL3730-6TE35-5AA3

    6SL3730-6TE37-3AA3

    6SL3730-6TE41-1AA3

    6SL3730-6TE41-3AA3

    6SL3730-6TE41-7AA3

    For a parallel circuit configuration,
    mounted to the right of the Line Connection Module

     

     

    6SL3730-6TE41-1BA3

    6SL3730-6TE41-3BA3

    6SL3730-6TE41-7BA3

    For a parallel circuit configuration,
    mounted to the left of the Line Connection Module

     

     

    6SL3730-6TE41-1BC3

    6SL3730-6TE41-3BC3

    6SL3730-6TE41-7BC3

    Rated power

     

     

     

     

     

     

    • At Irated DC (50 Hz 400 V)

    kW

    250

    355

    500

    630

    800

    • At IH DC (50 Hz 400 V)

    kW

    235

    315

    450

    555

    730

    • At Irated DC (60 Hz 460 V)

    hp

    395

    545

    770

    970

    1230

    • At IH DC (60 Hz 460 V)

    hp

    360

    485

    695

    855

    1125

    DC link current

     

     

     

     

     

     

    • Rated current Irated DC

    A

    550

    730

    1050

    1300

    1700

    • Base-load current IH DC1)

    A

    490

    650

    934

    1157

    1513

    • Maximum current Imax DC

    A

    825

    1095

    1575

    1950

    2550

    Infeed/regenerative feedback current

     

     

     

     

     

     

    • Rated current Irated I

    A

    463

    614

    883

    1093

    1430

    • Maximum current Imax I

    A

    694

    921

    1324

    1639

    2145

    Current demand

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.35

    1.35

    1.4

    1.5

    1.7

    • 400 V AC 2)

    A

    1.8

    1.8

    3.6

    5.4

    5.4

    DC link capacitance

     

     

     

     

     

     

    • Smart Line Module

    μF

    8400

    12000

    16800

    18900

    28800

    • Drive line-up, max.

    μF

    42000

    60000

    67200

    75600

    115200

    Power loss, max. 3)

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    3.7

    4.7

    7.1

    11.0

    11.5

    • At 60 Hz 460 V

    kW

    3.7

    4.7

    7.1

    11.0

    11.5

    Cooling air requirement

    m3/s

    0.36

    0.36

    0.78

    1.08

    1.08

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    69/73

    69/73

    70/73

    70/73

    70/73

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    Cable length, max. 4)

     

     

     

     

     

     

    • Shielded

    m

    4000

    4000

    4800

    4800

    4800

    • Unshielded

    m

    6000

    6000

    7200

    7200

    7200

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

    • Width

    mm

    400

    400

    600

    800

    800

    • Height 5)

    mm

    2200

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    600

    Weight, approx.

    kg

    270

    270

    490

    775

    775

    Frame size

     

    GX

    GX

    HX

    JX

    JX

    Short-circuit current rating according to IEC

    kA

    65

    65

    84

    84

    100

    Minimum short-circuit current 6)

    A

    6200

    9200

    2000

    2500

    3200



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The current demand for the 400 V AC auxiliary power supply is drawn from the line input voltage.

    3) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request.

    5) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 or IP54.

    6) Current required to ensure reliable tripping of installed protective devices.

     

    Line voltage 500 ... 690 V 3 AC

    Smart Line Modules

     

    6SL3730-6TG35-5AA3

    6SL3730-6TG38-8AA3

    6SL3730-6TG41-2AA3

    6SL3730-6TG41-7AA3

    For a parallel circuit configuration,
    mounted to the right of the Line Connection Module

     

    6SL3730-6TG38-8BA3

    6SL3730-6TG41-2BA3

    6SL3730-6TG41-7BA3

    For a parallel circuit configuration,
    mounted to the left of the Line Connection Module

     

    6SL3730-6TG38-8BC3

    6SL3730-6TG41-2BC3

    6SL3730-6TG41-7BC3

    Rated power

     

     

     

     

     

    • At Irated DC (50 Hz 690 V)

    kW

    450

    710

    1000

    1400

    • At IH DC (50 Hz 690 V)

    kW

    405

    665

    885

    1255

    • At Irated DC (50 Hz 500 V)

    kW

    320

    525

    705

    995

    • At IH DC (50 Hz 500 V)

    kW

    295

    480

    640

    910

    • At Irated DC (60 Hz 575 V)

    hp

    500

    790

    1115

    1465

    • At IH DC (60 Hz 575 V)

    hp

    450

    740

    990

    1400

    DC link current

     

     

     

     

     

    • Rated current Irated DC

    A

    550

    900

    1200

    1700

    • Base-load current IH DC1)

    A

    490

    800

    1068

    1513

    • Maximum current Imax DC

    A

    825

    1350

    1800

    2550

    Infeed/regenerative feedback current

     

     

     

     

     

    • Rated current Irated I

    A

    463

    757

    1009

    1430

    • Maximum current Imax I

    A

    694

    1135

    1513

    2145

    Current demand

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.35

    1.4

    1.5

    1.7

    • 500 V AC 2)

    A

    1.3

    2.9

    4.3

    4.3

    • 690 V AC

    A

    1

    2.1

    3.1

    3.1

    DC link capacitance

     

     

     

     

     

    • Smart Line Module

    μF

    5600

    7400

    11100

    14400

    • Drive line-up, max.

    μF

    28000

    29600

    44400

    57600

    Power loss, max. 3)

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    4.3

    6.5

    12.0

    13.8

    • At 60 Hz 575 V

    kW

    4.3

    6.5

    12.0

    13.8

    Cooling air requirement

    m3/s

    0.36

    0.78

    1.08

    1.08

    Sound pressure level LpA

    (1 m) at 50/60 Hz

    dB

    69/73

    70/73

    70/73

    70/73

    PE/GND connection

     

    PE bar

    PE bar

    PE bar

    PE bar

    • Busbar cross-section

    mm2

    600

    600

    600

    600

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    Cable length, max. 4)

     

     

     

     

     

    • Shielded

    m

    2250

    2750

    2750

    2750

    • Unshielded

    m

    3375

    4125

    4125

    4125

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

    • Width

    mm

    400

    600

    800

    800

    • Height 5)

    mm

    2200

    2200

    2200

    2200

    • Depth

    mm

    600

    600

    600

    600

    Weight, approx.

    kg

    270

    550

    795

    795

    Frame size

     

    GX

    HX

    JX

    JX

    Short-circuit current rating according to IEC

    kA

    65

    100

    100

    100

    Minimum short-circuit current 6)

    A

    6200

    10500

    2500

    3200



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The current demand for the 500 V / 690 V AC auxiliary power supply is drawn from the line input voltage.

    3) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request.

    5) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 or IP54.

    6) Current required to ensure reliable tripping of installed protective devices.