    Communications processor for connecting a SIMATIC S7-400 to Industrial Ethernet networks, also as PROFINET IO controller or in SIMATIC H systems.

    The CP supports:

    • PG/OP communication
    • S7 communication
    • Open communication (SEND/RECEIVE)
    • PROFINET communication
    • IT communication

    The communications processor can also be used for redundant S7 communication in SIMATIC H systems and for fail-safe applications (PROFIsafe) in connection with an S7-400 F-CPU.

    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    SIPLUS CP 443-1

     

    Article No.

    6AG1 443-1EX30-4XE0

    Order number based on

    6GK7 443-1EX30-0XE0

    Ambient temperature range

    0 ... +60 °C

    Conformal coating

    Coating of the printed circuit boards and the electronic components

    Technical data

    The technical data of the standard product applies, except for the ambient conditions

    Ambient conditions

     

    Relative humidity

    100%, condensation/frost permissible. No commissioning if condensation present.

    Biologically active substances, compliance with EN 60721-3-3

    Class 3B2 mold spores, fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    Chemically active substances, compliance with EN 60721-3-3

    Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!

    Mechanically active substances, compliance with EN 60721-3-3

    Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Air pressure (depending on the highest positive temperature range specified)

    1080 ... 795 hPa (-1000 ... +2000 m)
    see ambient temperature range

    795 ... 658 hPa (+2000 ... +3500 m)
    derating 10 K

    658 ... 540 hPa (+3500 ... +5000 m)
    derating 20 K



    Technical documentation on SIPLUS can be found here:
    http://www.siemens.com/siplus-extreme

    Область применения

    • The CP 443-1 is used to connect the SIMATIC S7-400 to Industrial Ethernet networks. With its own processor, it relieves the CPU of communications tasks and facilitates additional connections.

    The CP 443-1 offers communication options with

    • PGs/PCs
    • Host computers
    • HMI systems
    • SIMATIC S5/S7/C7 systems
    • PROFINET IO devices

    Дизайн

    The CP 443-1 features all the advantages of the SIMATIC S7-400 design:

    • Compact design:
      • Two RJ45 sockets for connecting to Industrial Ethernet; automatic data rate detection by means of the autosensing/autocrossover function; the connection is made via the IE FC RJ45 Plug 180 with 180° cable outlet or via a standard patch cable
      • Diagnostics LEDs for indicating the operational and communication status
    • Easy installation:
      The CP 443-1 is mounted on the S7-400 rack and connected to the other modules via the backplane bus. No slot rules apply.
    • The CP 443-1 can be operated without a fan
    • The CP 443-1 can also be operated in the expansion rack (ER) in conjunction with the IM 460/461
    • The module can be replaced without the need for a programming device

    Функции

    • Two RJ45 ports with 10/100 Mbps full/half duplex with autosensing and autocrossover functionality via integrated 2-port switch
    • Communication services of the interface:
      • Open communication (TCP/IP and UDP): Multicast with UDP, including routing between both interfaces
      • PG/OP communication: Inter-network with S7 routing
      • S7 communication (client, server, multiplexing) including routing between both interfaces
      • S7 H communication for S7-400 H systems, now also across network boundaries (ISO-on-TCP)
      • Certified PROFINET IO controller with real-time properties (RT and IRT)
      • IP address assignment via DHCP, simple PC tool or via program block (e.g. for HMI)
    • Media redundancy (MRP):
      • Within an Ethernet network with ring topology, the CP supports the media redundancy procedure MRPMRP as an MRP Manager and as an MRP Client
    • Diagnostics and network management:
      • Comprehensive diagnostics functions for all modules in the rack (including graphical diagnostics, e.g. topology)
      • Integration in network management systems due to support of SNMP V1/V3
    • Security mechanisms:
      • Access protection by means of configurable IP access list
      • Secure firmware update
      • Plagiarism detection
      • Certification as per the Achilles Level II Standard
        http://www.wurldtech.com/product_services/certifications/certified_products/
    • Configuration of all functions with STEP 7 V5.5 SP2;
      configuration with STEP 7 Professional V11 only with a limited range of functions of the predecessor CP 443-1 (6GK7 443-1EX20-0XE0) possible
    • When using the blocks AG_SSEND (FC53), AG_SRECV (FC63), TSEND (FB63), TRCV (FB64), TCON (FB65) and TDISCON (FB66), please note the following information: http://support.automation.siemens.com/WW/view/en/60037071
    • Module replacement without programming device: All information can be stored on the CPU

    Интеграция

    Interfacing to higher-level network with CP 443-1 as PROFINET IO controller

    Line structure as PROFINET IO controller with integrated real-time switch

    Line structure at the superordinated control level through integrated 2-port switch

    Особенности

    • High plant availability through the support of media redundancy (MRP) and use in the SIMATIC S7-400 H system
    • Optimum support of maintenance through
      • Web-based diagnostics
      • Remote programming via WAN or a telephone network (ISDN)
      • Monitoring by means of IT network management tools (SNMP)
      • Module exchange without programming device using the C-PLUG swap medium
    • Securing the system against unauthorized access by means of
      • Central access protection for any devices within an automation cell, e.g. by means of authentication of the network stations
    • The capability of later connecting existing SIMATIC S7 systems to Industrial Ethernet using the CP 443-1 ensures investment protection

    Технические данные

    Order number

    6GK7443-1EX30-0XE0

    Product type designation

    CP 443-1

    Transmission rate

     

    Transfer rate

     

    • at the 1st interface

    10 ... 100 Mbit/s

    Interfaces

     

    Number of interfaces acc. to Industrial Ethernet

    2

    Number of electrical connections

     

    • at the 1st interface acc. to Industrial Ethernet

    2

    Type of electrical connection

     

    • at the 1st interface acc. to Industrial Ethernet

    RJ45 port

    design of the removable storage C-PLUG

    No

    Supply voltage, current consumption, power loss

     

    Type of voltage of the supply voltage

    DC

    Supply voltage 1 from backplane bus

    5 V

    Relative symmetrical tolerance at DC

     

    • at 5 V

    5 %

    Consumed current

     

    • from backplane bus at DC at 5 V typical

    1.4 A

    Power loss [W]

    7.25 W

    Permitted ambient conditions

     

    Ambient temperature

     

    • during operation

    0 ... 60 °C

    • during storage

    -40 ... +70 °C

    • during transport

    -40 ... +70 °C

    Relative humidity at 25 °C without condensation during operation maximum

    95 %

    Protection class IP

    IP20

    Design, dimensions and weight

     

    Module format

    Compact module S7-400 single width

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Net weight

    0.7 kg

    Product properties, functions, components general

     

    Number of units

     

    • per CPU maximum

    14

    • Note

    max. 4 as PN IO ctrl.

    Performance data open communication

     

    Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum

    64

    Amount of data

     

    • as user data per ISO connection for open communication by means of SEND/RECEIVE blocks maximum

    8 Kibyte

    • as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum

    8 Kibyte

    • as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum

    8 Kibyte

    • as user data per UDP connection for open IE communication by means of SEND/RECEIVE blocks maximum

    2 Kibyte

    Number of possible connections for open communication

     

    • by means of T blocks maximum

    64

    Amount of data

     

    • as user data per ISO on TCP connection for open communication by means of T blocks maximum

    1 452 byte

    Performance data S7 communication

     

    Number of possible connections for S7 communication

     

    • maximum

    128

    • with PG connections maximum

    2

    • Note

    when using several CPUs

    Performance data multi-protocol mode

     

    Number of active connections with multi-protocol mode

    128

    Performance data PROFINET communication as PN IO-Controller

     

    Product function PROFINET IO controller

    Yes

    Number of PN IO devices on PROFINET IO controller usable total

    128

    Number of PN IO IRT devices on PROFINET IO controller usable

    64

    Number of external PN IO lines with PROFINET per rack

    4

    Amount of data

     

    • as user data for input variables as PROFINET IO controller maximum

    4 Kibyte

    • as user data for input variables as PROFINET IO controller maximum

    4 Kibyte

    • as user data for input variables per PN IO device as PROFINET IO controller maximum

    1 433 byte

    • as user data for output variables per PN IO device as PROFINET IO controller maximum

    1 433 byte

    • as user data for input variables per PN IO device for each sub-module as PROFINET IO controller maximum

    240 byte

    • as user data for output variables per PN IO device for each sub-module as PROFINET IO controller maximum

    240 byte

    Product function MIB support

    Yes

    Protocol is supported

     

    • SNMP v1

    Yes

    • DCP

    Yes

    • LLDP

    Yes

    Configuration software

     

    • required

    STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher

    Product functions Diagnosis

     

    Product function Web-based diagnostics

    Yes

    Product functions switch

     

    Product feature Switch

    Yes

    Product function

     

    • switch-managed

    No

    • with IRT PROFINET IO switch

    Yes

    • Configuration with STEP 7

    Yes

    Product functions Redundancy

     

    Product function

     

    • Ring redundancy

    Yes

    • Redundancy manager

    Yes

    • Parallel Redundancy Protocol (PRP)/operation in the PRP-network

    Yes

    Protocol is supported Media Redundancy Protocol (MRP)

    Yes

    Product functions Security

     

    Product function

     

    • password protection for Web applications

    No

    • ACL - IP-based

    Yes

    • ACL - IP-based for PLC/routing

    No

    • switch-off of non-required services

    Yes

    • Blocking of communication via physical ports

    Yes

    • log file for unauthorized access

    No

    Product functions Time

     

    Product function SICLOCK support

    Yes

    Product function pass on time synchronization

    Yes

    Protocol is supported

     

    • NTP

    Yes