Товаров
  
корзина пуста
  • Каталог оборудования Siemens

CP 440

  • Заказные данные
    (1)
  • Аксессуары
    (3)
  • Информационные материалы

    Информационные материалы

    • For high-performance transmission of messages via point-to-point connections (high message rate)
    • Physical interface: RS 422/RS 485 (X.27)
    • Up to 32 nodes
    • Protocol implemented: ASCII, 3964 (R)
    • Simple parameterization via a parameterization tool integrated into STEP 7

    Область применения

    The CP 440 communications processor is used for high-performance transmission of short message frames via RS 422/RS 485 (X27). This is the preferred method for implementing point-to-point connections.

    Point-to-point connection is possible, for instance, for:

    • SIMATIC S7, SIMATIC S5 programmable logic controllers and third-party controllers
    • Programming devices and PCs
    • Robot controls
    • Scanners, barcode readers
    • Measuring systems
    • Scales

    The RS 485 interface supports links to up to 32 partners.

    Дизайн

    The communications processors have the following mechanical features:

    • Rugged plastic housing
    • LEDs:
      For "Send", "Receive” and ”Error”.

    The CP 440 can also be used in expansion racks. However, transmission of the C bus signals must be ensured. A table with possible applications can be found under "Technical specifications".

    Функции

    A number of standard protocols are implemented and allow data exchange with a wide variety of nodes:

    • ASCII:
      For connection to third-party systems with simple communication protocols, such as protocols with start and end characters or protocols with block-check characters. The interface's handshake signals can be scanned and controlled via the user program.
    • 3964 (R):
      For connection to Siemens devices or third-party devices by means of the standardized and published Siemens 3964 (R) protocol. Also implemented are a 3964(R) driver with default values and a programmable 3964(R) driver.
    Parameterization

    Parameterization of the CP 440 communications processor is particularly convenient and simple:

    • The user specifies module characteristics via a parameter assignment tool integrated in STEP 7, such as:
      • Which implemented protocol driver is to be used, or
      • Which driver-specific features are to be utilized
    • Parameterization via CPU:
      Simply connect the programming device to the CPU. The configuration data is filed in a system data block that is saved in the CPU. When a module is replaced, the new module is thus immediately ready for operation.
    • Configuring package (on CD-ROM):
      With electronic manual, parameterization screen forms and standard function block for communication with the CP

    Технические данные

    Order number

    6ES7440-1CS00-0YE0

    CP 440-1, PTP-CONNECTIONS, 1 CHANNEL

    Supply voltage

     

    Rated value (DC)

    • 5 V DC

    Yes

    • 24 V DC

    Yes

    Input current

     

    from backplane bus 5 V DC, max.

    360 mA

    Power loss

     

    Power loss, typ.

    1.7 W

    Memory

     

    Memory requirements per interface in memory card of S7-CPU

    1 to 5 Kbytes for parameters

    Interfaces

     

    Number of interfaces

    1

    Interface (physical) RS 422/485 (X.27)

    Yes

    RS 422/RS 485, cable length shielded, max.

    1 200 m

    Point-to-point

     

    Integrated protocol driver

     

    • 3964 (R)

    Yes

    • ASCII

    Yes

    Transmission rate, RS 422/485

     

    • with 3964 (R) protocol, max.

    115.2 kbit/s

    • with ASCII protocol, max.

    115.2 kbit/s

    Configuration

     

    Configuration software

     

    • STEP 7

    Yes; own parameter assignment forms

    Dimensions

     

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Weights

     

    Weight, approx.

    600 g