Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Loadable drivers for CP 441-2 and CP 341

  • Заказные данные
    (4)
  • Аксессуары
    (1)
  • Информационные материалы

    Информационные материалы

    • Drivers for Modbus protocol with RTU message format; communication as master or slave
    • Downloadable onto CP 341 and CP 441-2 (6ES7 441-2AA04-0AE0)

    Область применения

    Drivers are available for downloading for the CP 341 and CP 441-2:

    • Modbus:
      For communication according to the Modbus protocol with RTU format.
      Communication as master or slave

    The two serial interfaces of the CP 441-2 can be operated independently with different standard protocols or downloadable drivers together with the V.24/TTY/X.27 interface modules.

    Функции

    Modbus

    • Modbus master:
      Master/slave coupling with SIMATIC S7 as master.
    • Modbus slave:
      Master/slave coupling with SIMATIC S7 as slave, message frame traffic from slave to slave not possible.
    Configuration

    The configuration package for CP 441-2 and CP 341 (V4.0 and higher) and STEP 7 V4.0 are required for downloading and configuration of the drivers. The drivers are copy protected by a dongle.

    Технические данные

    Parameterization software

    Loadable drivers for CP 441-2 and CP 341

    Type of license

    Simple license, copy license

    Target system

    SIMATIC CP 341, SIMATIC CP 441-2



    Technical specifications

    Modbus Master

     
    • Modbus protocol with RTU format
     
    • Master/slave coupling: SIMATIC S7 is master
     
    • Function codes implemented: 01, 02, 03, 04, 05, 06, 07, 08, 11,12,15,16
     
    • No V.24 control and signal lines
     
    • CRC polynomial: x16 + x15 + x2 +1
     
    • Interfaces: TTY (20 mA); V.24 (RS 232 C); X.27 (RS 422/485) 2-wire or 4-wire
     
    • Receive mailbox specified on BRCV
     
    • Character delay time 3.5 characters or multiple thereof
     
    • Broadcast message possible

    Adjustable parameters

    • Transmission rate 300 bit/s up to 76800 bit/s (TTY up to 19200 bit/s)
     
    • Character frame
     
    • With/without RS 485 operation for 2-wire connections
     
    • With/without modem operation (ignore smudge characters)
     
    • Response monitoring time 100 ms to 25.5 s in steps of 100 ms
     
    • Factor for the character delay time 1-10
     
    • Default setting of receive line when using the X.27 interface module


     

    Modbus slave

     
    • Modbus protocol with RTU format
     
    • Master/slave coupling: SIMATIC S7 is slave
     
    • Function codes implemented: 01, 02, 03, 04, 05, 06, 08, 15, 16
     
    • No V.24 control and signal line
     
    • CRC polynomial: x16 + x15 + x2 +1
     
    • Interfaces: TTY (20 mA), V.24 (RS 232C), X.27 (RS 422/485) 2-wire or 4-wire
     
    • Communications FB 180, instance DB 180 (use of a multi-instance)
     
    • Conversion of the Modbus data address to S7 data areas. Data areas which can be processed: DB, bit memories, outputs, inputs, timers, counters
     
    • Character delay time 3.5 characters or multiple thereof

    Adjustable parameters

    • Transmission rate 300 bit/s up to 76800 bit/s (TTY up to 19200 bit/s)
     
    • Character frame
     
    • Slave address of CP (1 to 255)
     
    • With/without RS 485 operation for 2-wire connection
     
    • With/without modem operation (ignore smudge characters)
     
    • Factor for the character delay time 1-10
     
    • Number of work DB (for FB processing)
     
    • Enabling of memory areas for writing by the master
     
    • Default setting of receive line when using the X.27 interface module
     
    • Conversion of Modbus addresses to S7 data areas