PS 405/407 power supply

  • Заказные данные
    (8)
  • Аксессуары
    (3)
  • Информационные материалы

    Информационные материалы

    • Power supplies for SIMATIC S7-400
    • For conversion of AC or DC line voltages to the 5 V DC and 24 V DC operating voltages required
    • 4 A, 10 A and 20 A output currents
    • In addition:
      • SIPLUS power supply 6AG1 405-0KA02-2AA0 for temperature range of -25 to +60 °C and use under medium load (e.g. chlorine/sulfur atmosphere). Technical specifications similar to 6ES7 405-0KA02-0AA0
      • SIPLUS power supply 6AG1 407-0KA02-4AA0 for use under medium load (e.g. chlorine/sulfur atmosphere). Technical specifications similar to 6ES7 407-0KA02-0AA0
      • SIPLUS power supply 6AG1 407-0KR02-4AA0 for use under medium load (e.g. chlorine/sulfur atmosphere). Technical specifications similar to 6ES7 407-0KR02-0AA0

    Область применения

    The power supplies supply the S7-400 modules with their 5 V DC and 24 V DC operating voltages via the backplane bus.

    Power supplies are available for AC line voltages of 85 to 264 V and for DC voltages of 19.2 to 300 V.

    One power supply module is required per rack.
    Exception:
    With interfaces with current transfer, the power supply module in the central controller also supplies all modules in the expansion units.

    The load voltage for supplying sensors and actuators must be made available separately.

    There are also power supplies to make both the standard system and the H system fail-safe (redundant power supplies).

    Дизайн

    The power supply modules are inserted at the far left in the rack (starting from slot 1). Depending on the version, they occupy slots 1 to 3. The modules are enclosed and are cooled via natural convection.

    The front of the module contains:

    • LED displays:
      LEDS indicate internal faults, correct output voltages 5 V DC, 24 V DC, and correct back-up battery voltage.
    • Pushbutton for fault acknowledgment.
    • On/off switch for output voltages.
    • Battery compartment for back-up battery (batteries).
    • Switch for battery monitoring.
    • Supply voltage selector switch (not for wide-range power supplies).
    • Power supply connection.

    The back-up battery is optional and must be ordered in addition. For power supplies at and above 10 A, two back-up batteries are recommended.

    Технические данные

    Order number

    6ES7405-0DA02-0AA0

    6ES7405-0KA02-0AA0

    6ES7405-0KR02-0AA0

    6ES7405-0RA02-0AA0

    PS405 POWER SUPPLY, DC24/48/60V, DC5V/4A

    SIMATIC S7-400, PS 405 POWER

    POWERSUPP.PS405,DC24/48/60V,DC5V/10A,RED

    PS405 POWER SUPPLY,DC24/48/60V,DC5V/20A

    General information

     

     

     

     

    Product type designation

    PS405, 24 VDC, 5 VDC/4 A

    PS405, 24/48/60 VDC, 5 VDC/10 A

    PS405,24/48/60 VDC,5 VDC/10 A,RED

    PS405, 24/48/60 VDC, 5 VDC/20 A

    Supply voltage

     

     

     

     

    Rated value (DC)

    • 24 V DC

    Yes

    Yes

    Yes

    Yes

    • 48 V DC

    Yes

    Yes

    Yes

    Yes

    • 60 V DC

    Yes

    Yes

    Yes

    Yes

    permissible range, lower limit (DC)

    19.2 V; Dynamic 18.5 V

    19.2 V; Dynamic 18.5 V

    19.2 V; Dynamic 18.5 V

    19.2 V; Dynamic 18.5 V

    permissible range, upper limit (DC)

    72 V; dynamic 75.5 V

    72 V; dynamic 75.5 V

    72 V; dynamic 75.5 V

    72 V; dynamic 75.5 V

    Mains buffering

     

     

     

     

    • Mains/voltage failure stored energy time

    20 ms

    20 ms

    20 ms

    20 ms

    • Mains buffering according to NAMUR recommendation

    Yes

    Yes

    Yes

    Yes

    Input current

     

     

     

     

    Rated value at 24 V DC

    2 A

    4 A

    4 A

    7 A

    Rated value at 48 V DC

    1 000 mA

    2 A

    2 A

    3.2 A

    Rated value at 60 V DC

    800 mA

    1.6 A

    1.6 A

    2.5 A

    Inrush current, max.

    18 A; Full width at half maximum 20 ms

    18 A; Full width at half maximum 20 ms

    18 A; Full width at half maximum 20 ms

    56 A; Full width at half maximum 1.5 ms

    Output voltage

     

     

     

     

    Type of output voltage

    DC

    DC

    DC

    DC

    Rated value (DC)

    • 5 V DC

    Yes

    Yes

    Yes

    Yes

    • 24 V DC

    Yes

    Yes

    Yes

    Yes

    Output current

     

     

     

     

    for backplane bus (5 V DC), max.

    4 A; no base load required

    10 A; no base load required

    10 A; no base load required

    20 A; no base load required

    for backplane bus (24 V DC), max.

    0.5 A; idling-proof

    1 A; idling-proof

    1 A; idling-proof

    1 A; idling-proof

    Short-circuit protection

    Yes

    Yes

    Yes

    Yes

    Power

     

     

     

     

    Active power input, typ.

    48 W

    95 W

    95 W

    168 W

    Power loss

     

     

     

     

    Power loss, typ.

    16 W

    20 W

    20 W

    44 W

    Battery

     

     

     

     

    Backup battery

     

     

     

     

    • Backup battery (optional)

    Yes; 1x lithium AA; 3.6 V / 2.3 Ah

    Yes; 2x lithium AA; 3.6 V / 2.3 Ah

    Yes; 2x lithium AA; 3.6 V / 2.3 Ah

    Yes; 2x lithium AA; 3.6 V / 2.3 Ah

    Hardware configuration

     

     

     

     

    Slots

     

     

     

     

    • required slots

    1

    2

    2

    2

    Potential separation

     

     

     

     

    primary/secondary

    Yes

    Yes

    Yes

    Yes

    Degree and class of protection

     

     

     

     

    Protection class

    1; with protective conductor

    1; with protective conductor

    1; with protective conductor

    1; with protective conductor

    Standards, approvals, certificates

     

     

     

     

    FM approval

    Yes; Ta: 0 °C to 60 °C T4

    Yes; Ta: 0 °C to 60 °C T4

    Yes; Ta: 0 °C to 60 °C T4

    Yes; Ta: 0 °C to 60 °C T4

    Connection method

     

     

     

     

    Connecting cables/cross-sections

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    Dimensions

     

     

     

     

    Width

    25 mm

    50 mm

    50 mm

    50 mm

    Height

    290 mm

    290 mm

    290 mm

    290 mm

    Depth

    217 mm

    217 mm

    217 mm

    217 mm

    Weights

     

     

     

     

    Weight, approx.

    760 g

    1 200 g

    1 200 g

    1 300 g


    Order number

    6ES7407-0DA02-0AA0

    6ES7407-0KA02-0AA0

    6ES7407-0KR02-0AA0

    6ES7407-0RA02-0AA0

    POWER SUPPLY PS407, 120/230V UC,5V DC/4A

    PS407 POWER SUPPLY,120/230V UC,5V DC/10A

    POWERSUPP.PS407,UC120/230V,DC5V/10A,RED.

    PS407 POWER SUPPLY,120/230V UC,5V DC/20A

    General information

     

     

     

     

    Product type designation

    PS407,UC 120/230 V,5 VDC/10 A,RED.

    PS407, 120/230 V AC/DC, 5 V DC/20 A

    Supply voltage

     

     

     

     

    Rated value (DC)

    • 120 V DC

    Yes

    Yes

    Yes

    Yes

    • 230 V DC

    Yes

    Yes

    Yes

    Yes

    permissible range, lower limit (DC)

    88 V

    88 V

    88 V

    88 V

    permissible range, upper limit (DC)

    300 V

    300 V

    300 V

    300 V

    Rated value (AC)

    • 120 V AC

    Yes

    Yes

    Yes

    Yes

    • 230 V AC

    Yes

    Yes

    Yes

    Yes

    permissible range, lower limit (AC)

    85 V

    85 V

    85 V

    85 V

    permissible range, upper limit (AC)

    264 V

    264 V

    264 V

    264 V

    Line frequency

     

     

     

     

    • Rated value 50 Hz

    Yes

    Yes

    Yes

    Yes

    • Rated value 60 Hz

    Yes

    Yes

    Yes

    Yes

    • permissible range, lower limit

    47 Hz

    47 Hz

    47 Hz

    47 Hz

    • permissible range, upper limit

    63 Hz

    63 Hz

    63 Hz

    63 Hz

    Mains buffering

     

     

     

     

    • Mains/voltage failure stored energy time

    20 ms

    20 ms

    20 ms

    20 ms

    • Mains buffering according to NAMUR recommendation

    Yes

    Yes

    Yes

    Yes

    Input current

     

     

     

     

    Rated value at 110 V DC

    350 mA; at 120 V DC

    1 A; at 120 V DC

    1 A; at 120 V DC

    1.4 A; at 120 V DC

    Rated value at 230 V DC

    190 mA

    0.5 A

    0.5 A

    0.7 A

    Rated value at 120 V AC

    0.42 A

    0.9 A

    0.9 A

    1.4 A

    Rated value at 230 V AC

    0.22 A

    0.5 A

    0.5 A

    0.7 A

    Inrush current, max.

    8.25 A; Full width at half maximum 5 ms

    63 A; Full width at half maximum 1 ms

    63 A; Full width at half maximum 1 ms

    88 A; Full width at half maximum 1.1 ms

    Output voltage

     

     

     

     

    Type of output voltage

    DC

    DC

    DC

    DC

    Rated value (DC)

    • 5 V DC

    Yes

    Yes

    Yes

    Yes

    • 24 V DC

    Yes

    Yes

    Yes

    Yes

    Output current

     

     

     

     

    for backplane bus (5 V DC), max.

    4 A; no base load required

    10 A; no base load required

    10 A; no base load required

    20 A; no base load required

    for backplane bus (24 V DC), max.

    0.5 A; idling-proof

    1 A; idling-proof

    1 A; idling-proof

    1 A; idling-proof

    Short-circuit protection

    Yes

    Yes

    Yes

    Yes

    Power

     

     

     

     

    Active power input, typ.

    52 W

    95 W

    95 W

    158 W

    Power loss

     

     

     

     

    Power loss, typ.

    20 W

    20 W

    20 W

    35 W

    Battery

     

     

     

     

    Backup battery

     

     

     

     

    • Backup battery (optional)

    Yes; 1x lithium AA; 3.6 V / 2.3 Ah

    Yes; 2x lithium AA; 3.6 V / 2.3 Ah

    Yes; 2x lithium AA; 3.6 V / 2.3 Ah

    Yes; 2x lithium AA; 3.6 V / 2.3 Ah

    Hardware configuration

     

     

     

     

    Slots

     

     

     

     

    • required slots

    1

    2

    2

    2

    Potential separation

     

     

     

     

    primary/secondary

    Yes

    Yes

    Yes

    Yes

    EMC

     

     

     

     

    Compliance with line harmonic distortion limits

     

     

     

     

    • Compliance with line harmonic distortion acc. to IEC 61000-3-2, IEC 61000-3-3

    Yes

    Yes

    Yes

    Yes

    Degree and class of protection

     

     

     

     

    Protection class

    1; with protective conductor

    1; with protective conductor

    1; with protective conductor

    1; with protective conductor

    Standards, approvals, certificates

     

     

     

     

    FM approval

    Yes; Ta: 0 °C to 60 °C T4

    Yes; Ta: 0 °C to 60 °C T4

    Yes; Ta: 0 °C to 60 °C T4

    Yes; Ta: 0 °C to 60 °C T4

    Connection method

     

     

     

     

    Connecting cables/cross-sections

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm

    Dimensions

     

     

     

     

    Width

    25 mm

    50 mm

    50 mm

    50 mm

    Height

    290 mm

    290 mm

    290 mm

    290 mm

    Depth

    217 mm

    217 mm

    217 mm

    217 mm

    Weights

     

     

     

     

    Weight, approx.

    760 g

    1 200 g

    1 200 g

    1 300 g