SIPLUS S7-400 CP 443-5 Extended

  • Заказные данные
    (1)
  • Аксессуары
    (5)
  • Информационные материалы

    Информационные материалы

    • DP-V1 master connection of the S7-400 to PROFIBUS
    • For setting up additional PROFIBUS DP lines
    • Communications services:
      • PROFIBUS DP
      • PG/OP communication
      • S7 communication
      • S5-compatible communication (SEND/RECEIVE)
    • Clock synchronization
    • Easy programming and configuration over PROFIBUS
    • Cross-network programming device communication through S7 routing
    • Can be easily integrated into the SIMATIC S7-400 system
    • Module replacement without PG
    • SIMATIC H system operation for redundant S7 communication or DP master communication
    • Data record routing (PROFIBUS DP)
    • Adding or modifying distributed I/O during operation
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

    SIPLUS CP 443-5-Extended

     

    Article No.

    6AG1 443-5DX05-4XE0

    Order No. based on

    6GK7 443-5DX05-0XE0

    Ambient temperature range

    0 ... +60 °C

    Conformal coating

    Coating of the printed circuit boards and the electronic components

    Technical specifications

    The technical specifications of the standard product apply, except for the ambient conditions

    Ambient conditions

    Relative humidity

    100%, condensation/frost permitted. No commissioning in bedewed state.

    Biologically active substances, compliance with EN 60721-3-3

    Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    Chemically active substances, compliance with EN 60721-3-3

    Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!

    Mechanically active substances, compliance with EN 60721-3-3

    Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Air pressure (depending on the highest positive temperature range specified)

    1080 ... 795 hPa (-1000 ... +2000 m)
    see ambient temperature range

    795 ... 658 hPa (+2000 ... +3500 m)
    derating 10 K

    658 ... 540 hPa (+3500 ... +5000 m)
    derating 20 K



    Technical documentation on SIPLUS can be found here:
    http://www.siemens.de/siplus-extreme

    Область применения

    The CP 443-5 Extended is the communications processor of the SIMATIC S7-400 for the PROFIBUS bus system.

    It relieves the CPU of communication tasks and supports additional connections.

    Communication possibilities of the S7-400 using communication modules:

    • As master for PROFIBUS DP according to IEC 61158/EN 50170
    • Communication with programming devices and HMI devices
    • Communication with other SIMATIC S7 systems
    • Communication with SIMATIC S5 programmable controllers

    The number of CPs that can be used is dependent on the performance range of the CPU and on the communications services used.

    Функции

    The CP 443-5 Extended provides access to different communication services of the PROFIBUS bus system:

    • PROFIBUS DP (according to IEC 61158/61784)
    • PG/OP communication
    • S7 communication (S7 controllers)
    • Open communication (SEND/RECEIVE)
    • Time synchronization

    Master for PROFIBUS DP

    The CP 443-5 Extended operates as DP-V1 master. It processes data transfer autonomously and allows slaves to be connected, such as CP 342-5 as DP slave, DP slaves of the ET 200 distributed I/O system, etc. This means that the CP 443-5 Extended is able to connect the S7-400 station to PROFIBUS DP and is the ideal expansion to the integral DP master interfaces of the S7-400 CPUs for establishing additional PROFIBUS DP lines.

    The CP 443-5 Extended can also be used in the SIMATIC S7 H system as a redundant DP master.

    The CP 443-5 Extended is a DP-V1 master, i.e. it also supports the acyclic standard services incl. interrupt handling.

    The CP 443-5 Extended also supports the SYNC and FREEZE functions, constant bus cycle time, direct slave-to-slave traffic, data set routing and changes to the configuration of the assigned distributed I/O during normal operation.

    During normal operation, it is also possible to activate or deactivate DP slaves. This supports the step-by-step start-up of subprocesses, for example.

    A diagnostic repeater allows the line to be diagnosed during operation, enabling line faults to be detected at an early stage. The CP 443-5 Extended supports operation with diagnostic repeater (including activation of topology identification in the diagnostic repeater).

    The distributed I/Os are handled like central I/Os from the user's point of view. This means that there are no differences between the CP 443-5 Extended and the integral DP master interface of the S7-400 CPU with regard to configuration and parameterization. Depending on the scale of the system, the CP 443-5 Extended has extremely short response times.

    PG/OP communication

    PG/OP communication allows all S7 stations connected to the network to be remotely programmed.

    • S7 routing
      With the aid of routing it is possible to use programming device communication across networks.

    S7 communication

    S7 communication is used for the coupling

    • between SIMATIC S7 programmable controllers
    • to programming devices (PG/OP communication)
    • to PCs,
      e.g. CP 5711 with SOFTNET-PB S7, CP 5623 etc.
    • to HMI devices (OPs).

    For redundant S7 communication, the CP 443-5 Extended can also be used in SIMATIC H systems.

    Open communication (SEND/RECEIVE)

    SIMATIC S7-400 is integrated into existing systems by means of open communication.

    Based on Layer 2 (FDL) of PROFIBUS, the CP 443-5 Extended offers a simple, optimized interface for process or field communication. This interface offers uniform, high-performance communication between SIMATIC S5, SIMATIC S7 and the PC. It provides the services SDA (PLC/PLC connections) and SDN (Broadcast, Multicast).

    The communication partners are the programmable controllers

    • SIMATIC S7
      with CP 342-5, CP 343-5, CP 443-5 Extended and Basic
    • SIMATIC S5
      with S5-95U with PROFIBUS interface, S5-115U/H, S5-135U, S5-155U/H with CP 5431 FMS/DP
    • SIMATIC 505
      with CP 5434-FMS
    • PCs
      with CP 5512, CP 5611 A2, CP 5621, CP 5613 A3, CP 5613 FO, CP 5614 A3, CP 5623, CP 5624
    • Non-Siemens systems that are equipped with an FDL interface.

    To use SEND/RECEIVE, function calls are required (PLC-SEND/PLC-RECEIVE), which must be linked into the STEP 7 user program.

    Time synchronization

    Time synchronization is used to set the time of day throughout the plant.

    The CP 443-5 Extended is capable of forwarding the time of day of the S7-400 CPU to PROFIBUS. Conversely, the CP of the S7-400 CPU can make an existing time of day available on PROFIBUS

    The CP 443-5 Extended supports

    • The time-stamping of distributed process signals in combination with IM 153
    • Time status value, daylight-saving time changeover, synchronization status

    Data set routing

    The CP 443-5 Extended supports the data set routing function. With this option, the CP can be used as a router for data sets that have to be sent to field devices (DP slaves). SIMATIC PDM (Process Device Manager) is a tool that creates data sets of this type for parameterizing and diagnosing field devices.

    Application:
    It is possible, for example, to use SIMATIC PDM (on the PC) to set parameters and perform diagnostics for a PA field device over Industrial Ethernet, S7-400 (CP 443-1, CP 443-5 Extended) and DP/PA Coupler/Link.

    Diagnostics data

    Extensive diagnostic options are available via STEP S7, including:

    • Status of the CP
    • General diagnostics and statistics functions
    • Connection diagnostics
    • Bus statistics
    • Message buffer
    • Support of operation with diagnostic repeater

    CiR – Configuration in RUN

    With CiR, it is possible to add or modify distributed I/O devices during normal operation.

    • Adding PROFIBUS DP/PA slaves
    • Adding/removing modules (e.g. I/O modules) in a modular DP slave (e.g. ET 200M and DP/PA Link)

    Configuration

    STEP 7 V5.1 SP2 or higher, or STEP 7 Professional V12 (TIA Portal) or higher, is required for configuring the full functional scope of the CP 443-5 Extended.

    DP configuration/programming is performed for the CP 443-5 Extended in the same manner as for DP configuration/programming of the integrated DP interfaces of the SIMATIC S7-400 CPUs with STEP 7.

    The configuring data of the CPs are always saved on the CPU and are retained even after a PLC failure. A module can therefore by replaced without having to reload the configuration data from a programming device. The CPU transfers the configuration data to the CP during start-up.

    Configuration and programming of all SIMATIC S7 controllers connected to the network is possible over the network.

    The function blocks for using the open communication (SEND/RECEIVE) can be found in the SIMATIC NET library following installation of STEP 7.

    Технические данные

    Order number

    6GK7443-5DX05-0XE0

    Product type designation

    CP 443-5 Extended

    Transmission rate

     

    Transfer rate

     

    • at the 1st interface acc. to PROFIBUS

    9.6 kbit/s ... 12 Mbit/s

    Interfaces

     

    Number of interfaces acc. to Industrial Ethernet

    0

    Number of electrical connections

     

    • at the 1st interface acc. to PROFIBUS

    1

    Type of electrical connection

     

    • at the 1st interface acc. to PROFIBUS

    9-pin Sub-D socket (RS485)

    Supply voltage, current consumption, power loss

     

    Type of voltage of the supply voltage

    DC

    Supply voltage 1 from backplane bus

    5 V

    Relative symmetrical tolerance at DC

     

    • at 5 V

    5 %

    Consumed current

     

    • from backplane bus at DC at 5 V typical

    0.6 A

    Power loss [W]

    3 W

    Permitted ambient conditions

     

    Ambient temperature

     

    • during operation

    0 ... 60 °C

    • during storage

    -40 ... +70 °C

    • during transport

    -40 ... +70 °C

    Relative humidity at 25 °C without condensation during operation maximum

    95 %

    Protection class IP

    IP20

    Design, dimensions and weight

     

    Module format

    Compact module S7-400 single width

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Net weight

    0.65 kg

    Product properties, functions, components general

     

    Number of units

     

    • per CPU maximum

    14

    • Note

    The number of CPs that can be operated as DP masters depends on the number of CP 443-1 Advanced processors operating in the S7-400 station as PROFINET IO controllers. Up to 10 CPs can be operated in total: up to 4 as PROFINET IO controllers (CP 443-1 Advanced); up to 10 as DP masters (CP 443-5 Extended)

    Performance data open communication

     

    Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum

    32

    Amount of data

     

    • as user data per connection for open communication by means of SEND/RECEIVE blocks maximum

    240 byte

    Performance data PROFIBUS DP

     

    Service as DP master

     

    • DPV1

    Yes

    Number of DP slaves on DP master usable

    125

    Amount of data

     

    • of the address area of the inputs as DP master total

    4 096 byte

    • of the address area of the outputs as DP master total

    4 096 byte

    • of the address area of the inputs per DP slave

    244 byte

    • of the address area of the outputs per DP slave

    244 byte

    Performance data S7 communication

     

    Number of possible connections for S7 communication

     

    • maximum

    48

    Performance data multi-protocol mode

     

    Number of active connections with multi-protocol mode

    • without DP maximum

    59

    • with DP maximum

    54

    Configuration software

     

    • required

    STEP 7 V5.4 SP4 or higher / STEP 7 Professional V12 (TIA Portal) or higher