Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Recommended line-side power components

  • Заказные данные
    (4)
  • Информационные материалы

    Информационные материалы

    The following table lists recommendations for additional line-side components, such as fuses and circuit breakers.

    Note for use in compliance with IEC standards:

    3NA3 type fuses and 3RV type circuit breakers are recommended for European countries. The values in the table take into account the overload capability of the inverter.

    Note for use in compliance with UL regulations:

    Fuses for use in North America must be UL-certified, Class J or Class CC fuses with a rated voltage of 600 V AC.

    Short Circuit Current Rating (SCCR)
    according to UL

    Applies to industrial control panel installations according to NEC Article 409 or UL 508A.

    • PM240M: 40 kA

    Additional information about the listed fuses and circuit breakers can be found in Catalogs LV 10, IC 10 and IC 10 AO.

    Individual protection

    Rated power

    SINAMICS G110M
    PM240M Power Modules

    IEC-compliant

    UL/cUL-compliant

     

     

    Fuse

    Circuit breaker

    Fuse type
    Rated voltage 600 V AC

     

     

     

     

    Current

     

     

     

    Current

    kW

    hp

    Type

    Frame size

    A

    Article No.

    Article No.

    Class

    A

    380 ... 480 V 3 AC

    0.37

    0.5

    6SL3517-1BE11-3AM0

    FSA

    10

    3NA3803

    3RV2011-1JA10

    J, CC

    10

    0.75

    1

    6SL3517-1BE12-3AM0

    FSA

    10

    3NA3803

    3RV2011-1JA10

    J, CC

    10

    1.1

    1.5

    6SL3517-1BE13-3AM0

    FSA

    10

    3NA3803

    3RV2011-1JA10

    J, CC

    10

    1.5

    2

    6SL3517-1BE14-3AM0

    FSA

    10

    3NA3803

    3RV2011-1JA10

    J, CC

    10

    2.2

    3

    6SL3517-1BE16-3AM0

    FSB

    20

    3NA3807

    3RV2021-4BA10

    J, CC

    20

    3

    4

    6SL3517-1BE17-7AM0

    FSB

    20

    3NA3807

    3RV2021-4BA10

    J, CC

    20

    4

    5

    6SL3517-1BE21-0AM0

    FSB

    20

    3NA3807

    3RV2021-4BA10

    J, CC

    20



    The SINAMICS G110M system supports an inverter loop-through of line current to several inverters connected in series.

    Further information can be found in the operating instructions on the Internet at
    http://www.siemens.com/sinamics-g110m/documentation

    Group protection (installation on power bus)

    For installations with several inverters, the inverters are normally supplied from a 400 V power bus.

    Further information can be found in the operating instructions on the Internet at
    http://www.siemens.com/sinamics-g110m/documentation