Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Fan modules

  • Заказные данные
    (1)
  • Информационные материалы

    Информационные материалы

    Fan module for installation underneath two power output modules

    The fan module is available for reliable heat dissipation of the LA724I and LA724I HP power output modules. The fan module is a standard fan in an IP00 enclosure.

    The fan module can be connected to

    • 2 LA724I or LA724I HP power output modules

    or

    • 1 central interface module and 1 LA724I or LA724I HP power output module

    Технические данные

    Order number

    6ES7171-3AA00-0AA0

    HCS Fan module LM724

    General information

     

    Product designation

    Fan module LM724

    Installation type/mounting

     

    Mounting type

    Mounting clips

    Type of ventilation

    Self ventilation or forced ventilation

    Supply voltage

     

    Type of supply voltage

    AC

    Rated value (AC)

    230 V

    Relative negative tolerance

    18 %

    Relative positive tolerance

    15 %

    Line frequency

     

    • Rated value 1

    50 Hz

    • Rated value 2

    60 Hz

    • Relative symmetrical tolerance

    5 %

    Resistance thermometer (RTD)

     

    • Design of electrical connection for supply voltage

    Connector, 2-pole

    • Connectable conductor cross-sections, solid

    1x (0.2 ... 2.5 mm²)

    • Connectable conductor cross-sections, finely stranded with wire end processing

    1x (0.25 ... 2.5 mm²)

    • Connectable conductor cross-sections for AWG cables

    24 ... 12

    Power

     

    Active power input

    6 W

    Integrated Functions

     

    Measuring functions

     

    • Voltage measurement

    No

    • Current measurement

    No

    Isolation

     

    Overvoltage category

    III

    EMC

     

    EMC interference emission

    Limit value class A to EN 55011 group 1

    Electrostatic discharge acc. to IEC 61000-4-2

    4 kV contact discharge / 8 kV air discharge

    Field-related interference acc. to IEC 61000-4-3

    10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz)

    Conducted interference due to burst acc. to IEC 61000-4-4

    2 kV voltage supply cables / 2 kV signal cables

    Conducted interference due to surge acc. to IEC 61000-4-5

    on power supply and signal cables: 1 kV symmetrical, 2 kV unsymmetrical

    Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6

    10 V (0.15 ... 80 MHz)

    Degree and class of protection

     

    IP degree of protection

    IP20

    Standards, approvals, certificates

     

    Certificate of suitability

    CE, KCC

    Degree of pollution

    2

    Device tag according to DIN EN 81346-2

    G

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    0 °C

    • max.

    55 °C

    Ambient temperature during storage/transportation

     

    • Storage, min.

    -40 °C

    • Storage, max.

    70 °C

    • Transportation, min.

    -40 °C

    • Transportation, max.

    70 °C

    Air pressure acc. to IEC 60068-2-13

     

    • Operation, min.

    860 hPa

    • Operation, max.

    1 080 hPa

    • Storage, min.

    660 hPa

    • Storage, max.

    1 080 hPa

    • Installation altitude above sea level, max.

    2 000 m

    Relative humidity

     

    • at 25 °C, max.

    95 %

    Vibrations

     

    • Vibration resistance during operation acc. to IEC 60068-2-6

    10 ... 58 Hz / 0.15 mm, 58 ... 150 Hz / 1 g

    • Vibration resistance during storage acc. to IEC 60068-2-6

    5 ... 9 Hz / 3.5 mm, 9 ... 500 Hz / 1 g

    Shock testing

     

    • Shock resistance acc. to IEC 60068-2-27

    15 g / 11 ms / 3 shocks/axis

    • Shock resistance acc. to IEC 60068-2-29

    25 g / 6 ms / 1 000 shocks/axis

    Dimensions

     

    Width

    100 mm

    Height

    50 mm

    Depth

    162 mm