    The VSM10 Voltage Sensing Module enables the line or motor voltage characteristic to be measured precisely. The phase differential voltage can be measured, either grounded (in the delivery state with jumper plugged in) or isolated.

    In addition, the VSM10 is used to connect to rotating synchronous motors – or for a "quick flying restart" of rotating induction motors.

    Дизайн

    The VSM10 Voltage Sensing Module has the following connections and interfaces:

    • 1 connection for direct voltage sensing up to 690 V
    • 1 connection for voltage sensing using voltage transformers, max. 100 V
    • 2 analog inputs (reserved for monitoring of resonance in the Active Interface Module in chassis format)
    • 1 temperature sensor input (KTY84‑130 or PTC)
    • 1 DRIVE‑CLiQ socket
    • 1 connection for the electronics power supply via the 24 V DC supply connector
    • 1 plug-in jumper for either grounded (delivery state) or isolated measurement
    • 1 PE/protective conductor connection

    The VSM10 Voltage Sensing Module can be snapped onto a TH 35 standard mounting rail in accordance with EN 60715 (IEC 60715).

    The status of the VSM10 Voltage Sensing Modules is indicated via a dual-color LED.

    Интеграция

    The VSM10 Voltage Sensing Module communicates with the CU310‑2 or CU320‑2 Control Unit via DRIVE‑CLiQ.

    On the SINAMICS S120 chassis format, the VSM10 Voltage Sensing Module is integrated in chassis format Active Interface Modules and Smart Line Modules.

    Connection example of a VSM10 Voltage Sensing Module

    Технические данные

     

    VSM10 Voltage Sensing Module

    6SL3053-0AA00-3AA1

    Power requirement, max.

    at 24 V DC

    0.2 A

    • Conductor cross-section, max.

    2.5 mm2

    Power loss, max.

    10 W

    Line voltage detection

     

    • Insulation resistance neutral point – ground when jumper is not inserted

    >10 MΩ

    • Input resistance

     

    • Terminal X521

    >362 kΩ/phase

    • Terminal X522

    >2.5 MΩ/phase

    Analog inputs

    (reserved for monitoring an Active Interface Module in chassis format)

     

    • Internal resistance, approx.
      (between differential inputs)

    100 kΩ

    • Resolution

    12 bits

    PE connection

    M4 screw

    Dimensions

     

    • Width

    50 mm

    • Height

    150 mm

    • Depth

    111 mm

    Weight, approx.

    0.9 kg