    Maintenance-free SITOP UPS1100 battery modules with 1.2 Ah up to 12 Ah and various types of energy storage (lead, pure lead, lithium iron phosphate = LiFePo) for SITOP UPS1600 DC UPS modules. The intelligent UPS1600 battery management charges the UPS1100 with the optimal, temperature-controlled charging characteristics and monitors the status (operating data and diagnostics information) via the energy storage link of the connected battery modules. For longer buffer times, up to six battery modules can be connected in parallel. Mounting onto standard mounting rail or directly to the wall.

    Технические данные

    Order number

    6EP4131-0GB00-0AY0

    6EP4132-0GB00-0AY0

    6EP4133-0GB00-0AY0

    6EP4133-0JB00-0AY0

    6EP4134-0GB00-0AY0

    6EP4135-0GB00-0AY0

    Product

    SITOP UPS1100

    SITOP UPS1100

    SITOP UPS1100

    SITOP UPS1100

    SITOP UPS1100

    SITOP UPS1100

    Product type

    Battery module 1.2 Ah

    Battery module 2.5 Ah

    Battery module 3.2 Ah

    Battery module 5 Ah

    Battery module 7 Ah

    Battery module 12 Ah

    Charging current charging voltage

     

     

     

     

     

     

    End-of-charge voltage at DC

     

     

     

     

     

     

    • at -10 °C recommended

    28.02 V

    28.02 V

    28.02 V

    28.8 V

    28.02 V

    28.02 V

    • at 0 °C recommended

    28.02 V

    28.02 V

    28.02 V

    28.8 V

    28.02 V

    28.02 V

    • at 10 °C recommended

    27.8 V

    27.8 V

    27.8 V

    28.8 V

    27.8 V

    27.8 V

    • at 20 °C recommended

    27.3 V

    27.3 V

    27.3 V

    28.8 V

    27.3 V

    27.3 V

    • at 30 °C recommended

    26.8 V

    26.8 V

    26.8 V

    28.8 V

    26.8 V

    26.8 V

    • at 40 °C recommended

    26.6 V

    26.6 V

    26.6 V

    28.8 V

    26.6 V

    26.6 V

    • at 50 °C recommended

    26.3 V

    26.3 V

    26.3 V

    28.8 V

    26.3 V

    26.3 V

    • at 60 °C recommended

    26 V

    Permissible charging current, max.

    0.3 A

    5 A

    0.8 A

    2.1 A

    1.75 A

    3 A

    Rated voltage Vout DC

    24 V

    24 V

    24 V

    24 V

    24 V

    24 V

    Rated current value Iout rated

    10 A

    20 A

    20 A

    20 A

    40 A

    40 A

    Safety

     

     

     

     

     

     

    Short-circuit protection

    Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support)

    Battery fuse 25 A/32 V (solid-state circuitry blade-type fuse + support)

    Battery fuse 25 A/32 V (solid-state circuitry blade-type fuse + support)

    Battery fuse 25 A/32 V (FKS blade-type fuse + holder); overcurrent switch-off at 60 A > 30 ms/min and 24 A > 5 s/min

    Battery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support)

    Battery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support)

    Design of the overload protection

    Valve control

    Valve control

    Valve control

    Valve control

    Valve control

    Valve control

    Status display

    LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

    LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

    LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

    LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

    LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

    LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

    Safety

     

     

     

     

     

     

    Protection class

    Class III

    Class III

    Class III

    Class III

    Class III

    Class III

    CE mark

    Yes

    Yes

    Yes

    Yes

    Yes

    Yes

    UL/cUL (CSA) approval

    cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

    cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

    cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

    cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

    cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

    cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627

    Explosion protection

    IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4

    IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4

    IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4

    No

    IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4

    IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4

    Marine approval

    GL, ABS

    GL, ABS

    GL, ABS

    GL, ABS

    GL, ABS

    GL, ABS

    Degree of protection (EN 60529)

    IP20

    IP20

    IP20

    IP20

    IP20

    IP20

    Operating data note

     

     

     

     

     

     

    Operating data note

    For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.

    For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.

    For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.

    For storage, mounting and operation of batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed.

    For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.

    For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.

    Ambient temperature

     

     

     

     

     

     

    • during operation

    -15 ... +50 °C

    -40 ... +60 °C

    -15 ... +50 °C

    -20 ... +50 °C

    -15 ... +50 °C

    -15 ... +50 °C

    • during transport

    -20 ... +50 °C

    -40 ... +60 °C

    -20 ... +50 °C

    -40 ... +60 °C

    -20 ... +50 °C

    -20 ... +50 °C

    • during storage

    -20 ... +50 °C

    -40 ... +60 °C

    -20 ... +50 °C

    -40 ... +60 °C

    -20 ... +50 °C

    -20 ... +50 °C

    Relative temporary capacity loss at 20 °C in a month typical

    3 %

    3 %

    3 %

    3 %

    3 %

    3 %

    Service life

     

     

     

     

     

     

    Service life of energy storage

     

     

     

     

     

     

    • typical remark

    capacity falls to 50 % of original capacity

    capacity falls to 50 % of original capacity

    capacity falls to 50 % of original capacity

    capacity falls to 50 % of original capacity

    capacity falls to 50 % of original capacity

    capacity falls to 50 % of original capacity

    • at 20 °C typical

    4 y

    10 y

    4 y

    15 y

    4 y

    4 y

    • at 30 °C typical

    2 y

    7 y

    2 y

    10 y

    2 y

    2 y

    • at 40 °C typical

    1 y

    3 y

    1 y

    9 y

    1 y

    1 y

    • at 50 °C typical

    0.5 y

    1.5 y

    0.5 y

    2 y

    0.5 y

    0.5 y

    • at 60 °C typical

    1 y

    Ambient temperature during storage Note

    Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

    Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

    Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

    Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

    Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

    Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

    Mechanics

     

     

     

     

     

     

    Connection technology

    screw-type terminals

    screw-type terminals

    screw-type terminals

    screw-type terminals

    screw-type terminals

    screw-type terminals

    Connection for power supply unit

    1 screw terminal each for 0.2 ... 6 mm² for + BATT and - BATT

    1 screw terminal each for 0.2 ... 6 mm² for + BATT and - BATT

    1 screw terminal each for 0.2 ... 6 mm² for + BATT and - BATT

    1 screw terminal each for 0.5 ... 16 mm² for + BATT and - BATT

    1 screw terminal each for 0.5 ... 16 mm² for + BATT and - BATT

    1 screw terminal each for 0.5 ... 16 mm² for + BATT and - BATT

    Type of electrical connection for control circuit and status message

    1 screw terminal each for 0.14 ... 4 mm²

    1 screw terminal each for 0.14 ... 4 mm²

    1 screw terminal each for 0.14 ... 4 mm²

    1 screw terminal each for 0.14 ... 4 mm²

    1 screw terminal each for 0.14 ... 4 mm²

    1 screw terminal each for 0.14 ... 4 mm²

    Product component belonging to

    Accessories pack with solid-state circuitry fuse 15 A

    Accessories pack with solid-state circuitry fuse 25 A

    Accessories pack with solid-state circuitry fuse 25 A

    Accessories pack with solid-state circuitry fuse 15 A

    Accessories pack with solid-state circuitry fuse 25 A

    Accessories pack with solid-state circuitry fuse 25 A

    Width of the enclosure

    89 mm

    265 mm

    190 mm

    189 mm

    186 mm

    253 mm

    Height of the enclosure

    130.3 mm

    115 mm

    169.3 mm

    186 mm

    186 mm

    186 mm

    Depth of the enclosure

    106.7 mm

    76 mm

    78.7 mm

    112.7 mm

    110.3 mm

    110.3 mm

    Installation width

    89 mm

    265 mm

    190 mm

    189 mm

    186 mm

    253 mm

    Installation height

    145.3 mm

    130 mm

    184.3 mm

    201 mm

    201 mm

    201 mm

    Weight, approx.

    1.9 kg

    3.7 kg

    3.8 kg

    3.4 kg

    6.1 kg

    9.8 kg

    Installation

    snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws

    snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws

    snaps onto DIN rail EN 60715 35x15 or keyhole mounting for hooking in to M4 screws

    snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws

    can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)

    can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)

    Number of cells

    12

    12

    12

    16

    12

    12

    Equipment marking acc. to DIN EN 81346-2

    G

    G

    G

    G

    G

    G

    Other information

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)