    The Central Interface Module (CIM) is the intelligent processor module of the SIPLUS HCS4300 heating control system.

    Дизайн

    • Module (encapsulated) in metal enclosure
    • 3 LEDs for normal operation (green), heating on (yellow) and fault (red)
    • PROFINET interface (up to 100 MBaud) with double switch
    • Differential serial bus interface for the power output modules (POM)
    • Connection of up to 6 POMs possible per CIM

    Функции

    Communication

    PROFINET

    • Import of parameter settings from the higher-level control system
    • Transfer of diagnostic information to the higher-level control system

    Serial bus (internal)

    • Control and monitoring of up to 54 power channels
    Performance features
    • Calculation of manipulated variables of power channels
    • Setpoints can be adjusted from 0% to 100% in increments of 1%
    • Even load distribution over all power channels and over all SIPLUS HCS4300 heating control systems operated as an integrated group
    • Simple adaptation to any production process through the selection of operating modes
    • Diagnostics functions
    • Evaluation of diagnostics information from connected power output modules
    • Phase-sequence detection indicating whether phases L1, L2, and L3 are correctly connected
    • Automatic detection of the line frequency

    Технические данные

    Order number

    6BK1943-1AA00-0AA0

    6BK1943-1BA00-0AA0

    6BK1943-1CA00-0AA0

    HCS CIM4310 PROFINET

    HCS CIM4310 PROFIBUS

    HCS CIM4310 EtherNet/IP

    General information

     

     

     

    Product brand name

    SIPLUS

    Product designation

    CIM4310 PROFINET

    CIM4310 PROFIBUS

    Installation type/mounting

     

     

     

    Mounting type

    Screw mounting to POM

    Mounting position

    vertical

    Type of ventilation

    Forced ventilation

    Supply voltage

     

     

     

    Type of supply voltage

    DC

    Rated value (DC)

    24 V

    Relative negative tolerance

    20 %

    Relative positive tolerance

    20 %

    Resistance thermometer (RTD)

     

     

     

    • Design of electrical connection for supply voltage

    Connector 2x 2-pin with tension spring connection

    • Connectable conductor cross-sections, solid

    1x (0.2 ... 2.5 mm²)

    • Connectable conductor cross-sections, finely stranded with wire end processing

    1x (0.2 ... 2.5 mm²)

    • Connectable conductor cross-sections for AWG cables

    1x (26 ... 12)

    Power

     

     

     

    Active power input

    3 W

    Hardware configuration

     

     

     

    Type of power output connectable

    POM4320

    Slots

     

     

     

    • Number of slots

    1

    Interfaces

     

     

     

    Interfaces/bus type

    PROFINET IO

    PROFIBUS DP

    EtherNet/IP

    PROFINET IO

     

     

     

    • Transmission rate, max.

    100 Mbit/s

    • Design of electrical connection of PROFINET interface

    2 x RJ45

    PROFIBUS DP

     

     

     

    • Transmission rate, max.

    12 Mbit/s

    • Design of electrical connection of PROFIBUS interface

    9-pin sub D socket

    EtherNet/IP

     

     

     

    • Transmission rate, max.

    100 Mbit/s

    • Design of EtherNet/IP interface electrical connection

    2 x RJ45

    Protocols

     

     

     

    Supports protocol for PROFINET IO

    Yes

    No

    PROFIBUS DP

    No

    Yes

    No

    Further protocols

     

     

     

    • EtherNet/IP

    Yes

    Interrupts/diagnostics/status information

     

     

     

    Number of status displays

    3

    LED status display

    LED green = ready, LED yellow = heating on/off, LED red = error display

    Isolation

     

     

     

    Overvoltage category

    III

    EMC

     

     

     

    EMC interference emission

    Limit value in accordance with IEC 61000-6-4:2007 + A1:2011

    Electrostatic discharge acc. to IEC 61000-4-2

    4 kV contact discharge / 8 kV air discharge

    Field-related interference acc. to IEC 61000-4-3

    10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz)

    Conducted interference due to burst acc. to IEC 61000-4-4

    2 kV power supply lines, 2 kV PROFINET cables

    2 kV power supply lines / 2 kV PROFIBUS cables

    2 kV power supply lines, 2 kV PROFINET cables

    Conducted interference due to surge acc. to IEC 61000-4-5

    DC supply lines: 0.5 kV symmetric and unsymmetric PROFINET cables: 1 kV unsymmetric

    DC supply lines: 0.5 kV symmetrical and asymmetrical, PROFIBUS lines: 1 kV asymmetrical

    DC supply lines: 0.5 kV symmetric and unsymmetric PROFINET cables: 1 kV unsymmetric

    Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6

    10 V (0.15 ... 80 MHz)

    Degree and class of protection

     

     

     

    IP degree of protection

    IP20

    Standards, approvals, certificates

     

     

     

    Degree of pollution

    2

    Device tag according to DIN EN 81346-2

    K

    Ambient conditions

     

     

     

    Ambient temperature during operation

     

     

     

    • min.

    0 °C

    • max.

    55 °C

    Ambient temperature during storage/transportation

     

     

     

    • Storage, min.

    -25 °C

    • Storage, max.

    70 °C

    • Transportation, min.

    -25 °C

    • Transportation, max.

    70 °C

    Air pressure acc. to IEC 60068-2-13

     

     

     

    • Operation, min.

    860 hPa

    • Operation, max.

    1 080 hPa

    • Storage, min.

    660 hPa

    • Storage, max.

    1 080 hPa

    • Installation altitude above sea level, max.

    2 000 m

    Relative humidity

     

     

     

    • Operation at 25 ℃, max.

    95 %

    • Operation at 50 ℃, max.

    50 %; 95 % at 25 °C, decreasing linearly to 50 % at 50 °C

    Vibrations

     

     

     

    • Vibration resistance during operation acc. to IEC 60068-2-6

    10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g

    • Vibration resistance during storage acc. to IEC 60068-2-6

    5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g

    Shock testing

     

     

     

    • Shock resistance during operation acc. to IEC 60068-2-27

    15 g / 11 ms / 3 shocks/axis

    • Shock resistance during storage acc. to IEC 60068-2-29

    25 g / 6 ms / 1 000 shocks/axis

    Dimensions

     

     

     

    Width

    56 mm

    Height

    285 mm

    Depth

    136 mm