SIPLUS S7-400 SM 422

  • Заказные данные
    (1)
  • Аксессуары
    (9)
  • Информационные материалы

    Информационные материалы

    • Digital outputs for SIMATIC S7-400
    • For connecting solenoid valves, contactors, small-power motors, lamps and motor starters
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Technical documentation on SIPLUS can be found here:
    http://www.siemens.de/siplus-extreme

    Область применения

    Digital output modules can be used to output digital signals from the control to the process. They are suitable, for example, for connecting solenoid valves, contactors, low-power motors, lamps and motor starters.

    Дизайн

    Digital output modules are characterized by the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains:
      • Green LEDs for indicating the signal statuses at the outputs
      • One red LED each to indicate internal and external faults or errors, and to display blown fuses and the absence of the load voltage
      • Labeling strips
    • Simple assembly
    • User-friendly wiring:
      The modules are wired by means of a plug-in front connector.

    Функции

    Digital output modules convert the internal signal levels of the S7-400 in the external signal levels required for the process.

    Технические данные

    Order number

    6AG1422-1BL00-2AA0

    SIPLUS_SM422_32DA

    Supply voltage

     

    Load voltage L+

     

    • Rated value (DC)

    24 V

    • permissible range, lower limit (DC)

    20.4 V

    • permissible range, upper limit (DC)

    28.8 V

    Input current

     

    from load voltage L+ (without load), max.

    30 mA

    from backplane bus 5 V DC, max.

    200 mA

    Power loss

     

    Power loss, typ.

    4 W

    Digital outputs

     

    Number of digital outputs

    32

    Limitation of inductive shutdown voltage to

    -27 V

    Switching capacity of the outputs

     

    • on lamp load, max.

    5 W

    Output voltage

     

    • for signal "1", min.

    L+ (-0.3 V)

    Output current

     

    • for signal "1" rated value

    0.5 A

    • for signal "1" permissible range, min.

    5 mA

    • for signal "1" permissible range, max.

    0.6 A

    • for signal "0" residual current, max.

    0.3 mA

    Switching frequency

     

    • with resistive load, max.

    100 Hz

    • with inductive load, max.

    0.5 Hz

    Total current of the outputs (per group)

     

    all mounting positions

     

    • up to 60 °C, max.

    2 A; 8 adjacent outputs each

    Cable length

     

    • shielded, max.

    1 000 m

    • unshielded, max.

    600 m

    Potential separation

     

    Potential separation digital outputs

     

    • between the channels, in groups of

    32

    • between the channels and backplane bus

    Yes

    Isolation

     

    Isolation tested with

    500 V DC

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    -25 °C; = Tmin

    • max.

    60 °C; = Tmax

    Ambient temperature during storage/transportation

     

    • min.

    -40 °C

    • max.

    70 °C

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Dimensions

     

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Weights

     

    Weight, approx.

    600 g


    Дальнейшая информация

    For further technical documentation on SIPLUS, see:
    http://www.siemens.com/siplus-techdoku