SM 421 digital input module

  • Заказные данные
    (5)
  • Аксессуары
    (35)
  • Информационные материалы

    Информационные материалы

    • Digital inputs for the SIMATIC S7-400
    • For connecting standard switches and two-wire proximity switches (BERO)

    Область применения

    Digital input modules can be used to connect the control to digital process signals. They are suitable for connecting standard switches and two-wire proximity switches (BERO).

    Дизайн

    The digital input modules have the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains:
      • Green LEDs to indicate signal states at the inputs
      • One red LED each to indicate internal and external faults or errors in modules with diagnostic and process interrupts
      • Labeling strips
    • Simple assembly
    • User-friendly wiring:
      The modules are wired by means of a plug-in front connector.

    Функции

    Digital input modules convert the levels of the external digital signals from the process into the internal signal level of the S7-400.

    Технические данные

    Order number

    6ES7421-7BH01-0AB0

    6ES7421-1BL01-0AA0

    6ES7421-1EL00-0AA0

    6ES7421-1FH20-0AA0

    6ES7421-7DH00-0AB0

    SM421, 16DI, DC24V, 0.05MS INPUT DELAY

    SM421, 32DI, DC24V

    SM421, 32DI, DC/AC 120V

    SIMATIC S7-400, DIG.INPUT MOD.

    SIMATIC S7-400, SM 421

    Supply voltage

     

     

     

     

     

    Load voltage L+

     

     

     

     

     

    • Rated value (DC)

    24 V

    • permissible range, lower limit (DC)

    20.4 V

    • permissible range, upper limit (DC)

    28.8 V

    Input current

     

     

     

     

     

    from supply voltage L+, max.

    120 mA

    from backplane bus 5 V DC, max.

    130 mA

    20 mA

    200 mA

    80 mA

    150 mA

    Power loss

     

     

     

     

     

    Power loss, typ.

    5 W

    6 W

    6.5 W

    12 W

    8 W; 3.5 W (24 V DC); 6.5 W (48 V DC); 8.0 W (60 V DC)

    Digital inputs

     

     

     

     

     

    Number of digital inputs

    16

    32

    32

    16

    16

    Number of simultaneously controllable inputs

     

     

     

     

     

    • Number of simultaneously controllable inputs

    16

    32

    32

    16

    16

    Input voltage

     

     

     

     

     

    • Type of input voltage

    DC

    DC

    AC/DC

    AC/DC

    AC/DC

    • Rated value (DC)

    24 V

    24 V

    • Rated value (UC)

    120 V

    230 V; 120/230 V UC

    24 V; 24 to 60 V UC

    • for signal "0"

    -30 V DC to +5 V DC

    -30 V DC to +5 V DC

    0 to 20 V UC

    0 to 40 V AC/ -40 to +40 V DC

    -6 to +6 V DC/ 0 to 5 V AC

    • for signal "1"

    11 V DC to 30 V DC

    13 V DC to 30 V DC

    79 to 132 V AC; 80 to 132 V DC

    74 to 264 V AC; 80 to 264 V DC, -80 to -264 V

    15 to 72 V DC; -15 to -72 V DC; 15 to 60 V AC

    • Frequency range

    47 ... 63 Hz

    47 ... 63 Hz

    47 to 63 Hz AC / DC

    Input current

     

     

     

     

     

    • for signal "0", max. (permissible quiescent current)

    1.3 mA

    1 mA

    6 mA; AC: 6 mA; DC: 2 mA

    • for signal "1", typ.

    6 mA; 6 to 8 mA

    7 mA

    2 mA; 2 to 5 mA

    10 mA; at 120 V: 10 mA AC, 1.8 mA DC; at 230 V: 14 mA AC, 2 mA DC

    4 mA; 4 to 10 mA

    Input delay (for rated value of input voltage)

     

     

     

     

     

    for standard inputs

     

     

     

     

     

    • parameterizable

    Yes

    Yes

    • Rated value

    0.5 ms; 0.5 / 3 / 10 / 20 ms

    Cable length

     

     

     

     

     

    • shielded, max.

    1 000 m; 1000 m: 3 ms, 70 m: 0.5 ms, 30 m: 0.1 ms, 30 m: 0.05 ms

    1 000 m

    1 000 m

    1 000 m

    1 000 m

    • unshielded, max.

    600 m; 600 m: 3 ms; 50 m: 0,5 ms; 20 m: 0,1 ms; 20 m: 0,05 ms

    600 m

    600 m

    600 m

    600 m; 600 m: 3, 10, 20 ms; 100 m: 0,5 ms

    Encoder

     

     

     

     

     

    Connectable encoders

     

     

     

     

     

    • 2-wire sensor

    Yes

    Yes

    Yes

    Yes

    Yes

    • permissible quiescent current (2-wire sensor), max.

    3 mA

    1.5 mA

    1 mA

    5 mA; AC: 5 mA

    0.5 mA; 0.5 to 2 mA

    Interrupts/diagnostics/status information

     

     

     

     

     

    Diagnostics

    Yes; internal/ external fault

    Yes; internal/ external fault

    Alarms

     

     

     

     

     

    • Diagnostic alarm

    Yes; Parameterizable

    Yes; Parameterizable

    • Hardware interrupt

    Yes; Parameterizable

    Yes; Parameterizable

    Potential separation

     

     

     

     

     

    Potential separation digital inputs

     

     

     

     

     

    • between the channels, in groups of

    8

    32

    8

    4

    1

    • between the channels and backplane bus

    Yes

    Yes

    Yes

    Yes

    Yes

    Isolation

     

     

     

     

     

    Isolation tested with

    500 V DC

    500 V DC

    1500 V AC

    1500 V AC

    1500 V AC

    Dimensions

     

     

     

     

     

    Width

    25 mm

    25 mm

    25 mm

    25 mm

    25 mm

    Height

    290 mm

    290 mm

    290 mm

    290 mm

    290 mm

    Depth

    210 mm

    210 mm

    210 mm

    210 mm

    210 mm

    Weights

     

     

     

     

     

    Weight, approx.

    600 g

    500 g

    600 g

    650 g

    600 g


    Дальнейшая информация

    Brochures

    Information material for downloading can be found in the Internet:

    http://www.automation.siemens.com/infocenter