SM 422 digital output module

  • Заказные данные
    (5)
  • Аксессуары
    (35)
  • Информационные материалы

    Информационные материалы

    • Digital outputs for the SIMATIC S7-400
    • For connecting solenoid valves, contactors, low-power motors, lamps and motor starters

    Область применения

    Digital output modules can be used to output digital signals from the control to the process. They are suitable, for example, for connecting solenoid valves, contactors, low-power motors, lamps and motor starters.

    Дизайн

    Digital output modules are characterized by the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains:
      • Green LEDs for indicating the signal statuses at the outputs
      • One red LED each to indicate internal and external faults or errors, and to display blown fuses and the absence of the load voltage
      • Labeling strips
    • Simple assembly
    • User-friendly wiring:
      The modules are wired by means of a plug-in front connector.

    Функции

    Digital output modules convert the internal signal levels of the S7-400 in the external signal levels required for the process.

    Технические данные

    Order number

    6ES7422-1FH00-0AA0

    6ES7422-1HH00-0AA0

    6ES7422-1BH11-0AA0

    6ES7422-1BL00-0AA0

    6ES7422-7BL00-0AB0

    SM422, 16DO, AC120/230V, 2A

    SM422, 16DO, AC5-230V, 5A RELAY

    SM422, 16DO, DC24V, 2A,

    SIMATIC S7-400, SM 422

    SIMATIC S7-400, DIG.OUTPUT MOD.

    Supply voltage

     

     

     

     

     

    Load voltage L+

     

     

     

     

     

    • Rated value (DC)

    60 V

    24 V

    24 V

    24 V

    • permissible range, lower limit (DC)

    1 V

    20.4 V

    20.4 V

    20.4 V

    • permissible range, upper limit (DC)

    60 V

    28.8 V

    28.8 V

    28.8 V

    Load voltage L1

     

     

     

     

     

    • Rated value (AC)

    230 V; 120/230V AC

    230 V

    • permissible range, lower limit (AC)

    79 V

    2 V

    • permissible range, upper limit (AC)

    264 V

    264 V

    Input current

     

     

     

     

     

    from load voltage L+ (without load), max.

    1.5 mA

    30 mA

    30 mA

    120 mA

    from backplane bus 5 V DC, max.

    400 mA

    1 A

    160 mA

    200 mA

    200 mA

    Power loss

     

     

     

     

     

    Power loss, typ.

    16 W

    4.5 W

    5 W

    4 W

    8 W

    Digital outputs

     

     

     

     

     

    Number of digital outputs

    16

    16; Relays

    16

    32

    32

    Limitation of inductive shutdown voltage to

    -30 V

    -27 V

    L+ (-45 V)

    Switching capacity of the outputs

     

     

     

     

     

    • on lamp load, max.

    50 W

    60 W

    10 W

    5 W

    5 W

    Output voltage

     

     

     

     

     

    • for signal "1", min.

    L1 (-18.1 V)

    L+ (-0.5 V)

    L+ (-0.3 V)

    L+ (-0.8 V)

    Output current

     

     

     

     

     

    • for signal "1" rated value

    2 A

    5 A

    2 A

    0.5 A

    0.5 A

    • for signal "1" permissible range, min.

    10 mA

    5 mA

    5 mA

    5 mA

    • for signal "1" permissible range, max.

    2 A

    2.4 A

    0.6 A

    600 A

    • for signal "0" residual current, max.

    2.6 mA

    0.5 mA

    0.3 mA

    0.5 mA

    Switching frequency

     

     

     

     

     

    • with resistive load, max.

    10 Hz

    10 Hz

    100 Hz

    100 Hz

    100 Hz

    • with inductive load, max.

    0.5 Hz

    0.1 Hz

    0.5 Hz

    2 Hz

    Total current of the outputs (per group)

     

     

     

     

     

    all mounting positions

     

     

     

     

     

    • up to 60 °C, max.

    2 A; 5 A with fan subassembly; per 4 adjacent outputs

    5 A; 10 A with fan subassembly

    2 A; 2 adjacent outputs each

    2 A; 8 adjacent outputs each

    2 A

    Relay outputs

     

     

     

     

     

    • Number of operating cycles, max.

    100 000; 100 000 (AC-15 / DC-13); 3 000 000 mechanical

    Switching capacity of contacts

     

     

     

     

     

    • with inductive load, max.

    5 A; 5 A (30 V DC), 5 A (230 V AC)

    • with resistive load, max.

    5 A; 5 A (30 V DC), 5 A (230 V AC), 1.2 A (60 V DC), 0.2 A (125 V DC)

    Cable length

     

     

     

     

     

    • shielded, max.

    1 000 m

    1 000 m

    1 000 m

    1 000 m

    1 000 m

    • unshielded, max.

    600 m

    600 m

    600 m

    600 m

    600 m

    Interrupts/diagnostics/status information

     

     

     

     

     

    Diagnostics

    Yes; internal/ external fault

    Alarms

     

     

     

     

     

    • Diagnostic alarm

    Yes; Parameterizable

    • Hardware interrupt

    Yes; Parameterizable

    Potential separation

     

     

     

     

     

    Potential separation digital outputs

     

     

     

     

     

    • between the channels, in groups of

    4

    2

    8

    32

    8

    • between the channels and backplane bus

    Yes

    Yes

    Yes

    Yes

    Yes

    Isolation

     

     

     

     

     

    Isolation tested with

    1500 V AC

    1500 V AC

    500 V DC

    500 V DC

    500 V DC

    Dimensions

     

     

     

     

     

    Width

    25 mm

    25 mm

    25 mm

    25 mm

    25 mm

    Height

    290 mm

    290 mm

    290 mm

    290 mm

    290 mm

    Depth

    210 mm

    210 mm

    210 mm

    210 mm

    210 mm

    Weights

     

     

     

     

     

    Weight, approx.

    800 g

    700 g

    600 g

    600 g

    600 g