    dv/dt filters compact plus VPL (Voltage Peak Limiter) limit the voltage rate-of-rise dv/dt to values < 1600 V/μs and the typical voltage peaks to the following values according to limit value curve A to IEC 60034‑25: 2007:

    • < 1150 V at Uline < 575 V
    • < 1400 V at 660 V < Uline < 690 V

    Standard motors with standard insulation and without insulated bearings can be used for inverter operation if a dv/dt filter compact plus VPL is used.

    dv/dt filters compact plus VPL are designed for the following maximum motor cable lengths:

    • Shielded cables: 100 m (328 ft) (e.g. Protodur NYCWY)
    • Unshielded cables: 150 m (492 ft) (e.g. Protodur NYY)

    For longer cable lengths (> 100 m (328 ft) shielded, > 150 m (492 ft) unshielded) refer to dv/dt filter plus VPL.

    Note:

    • The max. permissible cable length between the dv/dt filter and Power Module is 5 m.
    • Operation with output frequencies <10 Hz is permissible for max. 5 min.

    Дизайн

    The dv/dt filter compact plus VPL consists of two components, which are supplied together as a compact mechanical unit:

    • dv/dt reactor
    • Voltage limiting network, which cuts off the voltage peaks and feeds the energy back into the DC link.

    Технические данные

    Line voltage 380 ... 480 V 3 AC

    dv/dt filter compact plus VPL

     

    6SL3000-2DE35-0EA0

    6SL3000-2DE38-4EA0

    6SL3000-2DE41-4EA0

    Ith max

    A

    490

    840

    1405

    Power loss, max.

     

     

     

     

    • At 50 Hz

    kW

    0.29

    0.518

    1.154

    • At 60 Hz

    kW

    0.296

    0.529

    1.197

    Connections

     

     

     

     

    • To Power Module

     

    1 × hole for M10,
    provided for busbar connection

    1 × hole for M12,
    provided for busbar connection

    2 × hole for M12,
    provided for busbar connection

    • To load

     

    1 × hole for M10,
    provided for busbar connection

    1 × hole for M12,
    provided for busbar connection

    2 × hole for M12,
    provided for busbar connection

    • PE

     

    Threaded socket M6

    Threaded socket M6

    Threaded socket M6
    (reactor and VPL)

    DC link connection,

    DCPS, DCNS

     

    Threaded socket M8

    Hole for M8

    Hole for M8

    • Conductor cross section, max. (IEC)

    mm2

    25

    50

    95

    Cable length, max.

    between dv/dt filter and motor

     

     

     

     

    • Shielded

    m (ft)

    100 (328)

    100 (328)

    100 (328)

    • Unshielded

    m (ft)

    150 (492)

    150 (492)

    150 (492)

    Degree of protection

     

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

    • Width

    mm (in)

    350 (13.8)

    440 (17.3)

    Reactor: 430 (16.9) / VPL: 277 (10.9)

    • Height

    mm (in)

    317 (12.5)

    369 (14.5)

    Reactor: 385 (15.2) / VPL: 360 (14.17)

    • Depth

    mm (in)

    260 (10.2)

    311 (12.2)

    Reactor: 323 (12.7) / VPL: 291 (11.5)

    Weight, approx.

    kg (lb)

    61 (134)

    103 (227)

    Reactor: 168.8 (372) / VPL: 19.2 (42.3)

    Suitable for
    PM330 Power Module

     

    6SL3310-1PE33-0AA0
    6SL3310-1PE33-7AA0
    6SL3310-1PE34-6AA0

    6SL3310-1PE35-8AA0
    6SL3310-1PE36-6AA0
    6SL3310-1PE37-7AA0

    6SL3310-1PE38-4AA0
    6SL3310-1PE38-8AA0
    6SL3310-1PE41-0AA0

    • Frame size

     

    GX

    HX

    JX



     

    Line voltage 500 ... 690 V 3 AC

    dv/dt filter compact plus VPL

     

    6SL3000-2DG38-1EA0

    Ith max

    A

    810

    Power loss, max.

     

     

    • At 50 Hz

    kW

    0.964

    • At 60 Hz

    kW

    0.998

    Connections

     

     

    • To Power Module

     

    2 × hole for M12,
    provided for busbar connection

    • To load

     

    2 × hole for M12,
    provided for busbar connection

    • PE

     

    Threaded socket M6

    DC link connection,

    DCPS, DCNS

     

    Hole for M8

    • Conductor cross section, max. (IEC)

    mm2

    95

    Cable length, max.

    between dv/dt filter and motor

     

     

    • Shielded

    m (ft)

    100

    • Unshielded

    m (ft)

    150 (492)

    Degree of protection

     

    IP00

    Dimensions

     

     

    • Width

    mm (in)

    Reactor: 430 (16.9) / VPL: 277 (10.9)

    • Height

    mm (in)

    Reactor: 385 (15.2) / VPL: 360 (14.2)

    • Depth

    mm (in)

    Reactor: 323 (12.7) / VPL: 291 (11.5)

    Weight, approx.

    kg (lb)

    Reactor: 171.2 (377) / VPL: 18.8 (41.4)

    Suitable for
    PM330 Power Module

     

    6SL3310-1PG35-8AA0
    6SL3310-1PG36-5AA0
    6SL3310-1PG37-2AA0

    • Frame size

     

    JX