For gauge and absolute pressure, with flush-mounted diaphragm

  • Заказные данные
    (3)
  • Аксессуары
    (53)
  • Информационные материалы

    Чертеж

    SITRANS P pressure transmitters, DS III series for gage pressure, with flush-mounted diaphragm, dimensions in mm (inch)

    The diagram shows a SITRANS P DS III with an example of a flange. In this drawing the height is subdivided into H1 and H2.

    H1 = Height of the SITRANS P300 up to a defined cross-section

    H2 = Height of the flange up to this defined cross-section

    Only the height H2 is indicated in the dimensions of the flanges.

    Flanges as per EN and ASME

    Flange to EN

    EN 1092-1

     

    DN

    PN

    ∅D

    H2

    25

    40

    115 mm (4.5")

    Approx. 52 mm (2")

    25

    100

    140 mm (5.5")

    40

    40

    150 mm (5.9")

    40

    100

    170 mm (6.7")

    50

    16

    165 mm (6.5")

    50

    40

    165 mm (6.5")

    80

    16

    200 mm (7.9")

    80

    40

    200 mm (7.9")



    Flanges to ASME

    ASME B16.5

     

    DN

    class

    ∅D

    H2

    1“

    150

    110 mm (4.3")

    Approx. 52 mm (2")

    1“

    300

    125 mm (4.9")

    1½“

    150

    130 mm (5.1")

    1½“

    300

    155 mm (6.1")

    2“

    150

    150 mm (5.9")

    2“

    300

    165 mm (6.5")

    3“

    150

    190 mm (7.5")

    3“

    300

    210 mm (8.1")

    4“

    150

    230 mm (9.1")

    4“

    300

    255 mm (10.0")



    NuG and pharmaceutical connections

    Connections to DIN

    DIN 11851 (milk pipe union)

     

    DN

    PN

    ∅D

    H2

    50

    25

    92 mm (3.6")

    Approx. 52 mm (2")

    80

    25

    127 mm (5.0")



    TriClamp to DIN 32676

     

    DN

    PN

    ∅D

    H2

    50

    16

    64 mm (2.5")

    Approx. 52 mm (2")

    65

    16

    91 mm (3.6")



    Other connections

    Varivent connection

     

    DN

    PN

    ∅D

    H2

    40 ... 125

    40

    84 mm (3.3")

    Approx. 52 mm (2")



    Biocontrol connection

     

    DN

    PN

    ∅D

    H2

    50

    16

    90 mm (3.5")

    Approx. 52 mm (2")

    65

    16

    120 mm (4.7")



    Sanitary process connection to DRD

     

    DN

    PN

    ∅D

    H2

    65

    40

    105 mm (4.1")

    Approx. 52 mm (2")

       


    Sanitary process screw connection to NEUMO Bio-Connect

     

    DN

    PN

    ∅D

    H2

    50

    16

    82 mm (3.2")

    Approx. 52 mm (2")

    65

    16

    105 mm (4.1")

    80

    16

    115 mm (4.5")

    100

    16

    145 mm (5.7")

    2”

    16

    82 mm (3.2")

    2½”

    16

    105 mm (4.1")

    3”

    16

    105 mm (4.1")

    4”

    16

    145 mm (5.7")



    Sanitary process connection to NEUMO Bio-Connect flange connection

     

    DN

    PN

    ∅D

    H2

    50

    16

    110 mm (4.3")

    Approx. 52 mm (2")

    65

    16

    140 mm (5.5")

    80

    16

    150 mm (5.9")

    100

    16

    175 mm (6.9")

    2”

    16

    100 mm (3.9")

    2½”

    16

    110 mm (4.3")

    3”

    16

    140 mm (5.5")

    4”

    16

    175 mm (6.9")



    Sanitary process connection to NEUMO Bio-Connect clamp connection

     

    DN

    PN

    ∅D

    H2

    50

    16

    77.4 mm (3.0")

    Approx. 52 mm (2")

    65

    10

    90.9 mm (3.6")

    80

    10

    106 mm (4.2")

    100

    10

    119 mm (4.7")

    2”

    16

    64 mm (2.5")

    2½”

    16

    77.4 mm (3.0")

    3”

    10

    90.9 mm (3.6")

    4”

    10

    779 mm (4.7")



    Sanitary process connection to NEUMO Bio-Connect S flange connection

     

    DN

    PN

    ∅D

    H2

    50

    16

    125 mm (4.9")

    Approx. 52 mm (2")

    65

    10

    145 mm (5.7")

    80

    10

    155 mm (6.1")

    100

    10

    180 mm (7.1")

    2”

    16

    125 mm (4.9")

    2½”

    10

    135 mm (5.3")

    3”

    10

    145 mm (5.7")

    4”

    10

    180 mm (7.1")



    Threaded connection G¾", G1" and G2" acc. to DIN 3852

     

    DN

    PN

    ∅D

    H2

    ¾“

    63

    37 mm (1.5")

    Approx. 45 mm (1.8")

    1“

    63

    48 mm (1.9")

    Approx. 47 mm (1.9")

    2“

    63

    78 mm (3.1")

    Approx. 52 mm (2")



    Tank connection TG 52/50 and TG52/150

     

    DN

    PN

    ∅D

    H2

    25

    40

    63 mm (2.5")

    Approx. 63 mm (2.5")

    25

    40

    63 mm (2.5")

    Approx. 170 mm (6.7")



    SMS socket with union nut

     

    DN

    PN

    ∅D

    H2

    2“

    25

    84 mm (3.3")

    Approx. 52 mm (2.1")

    2½“

    25

    100 mm (3.9")

    3“

    25

    114 mm (4.5")



    SMS threaded socket

     

    DN

    PN

    ∅D

    H2

    2“

    25

    70 x 1/6 mm

    Approx. 52 mm (2.1")

    2½“

    25

    85 x 1/6 mm

    3“

    25

    98 x 1/6 mm



    IDF socket with union nut

     

    DN

    PN

    ∅D

    H2

    2“

    25

    77 mm (3")

    Approx. 52 mm (2.1")

    2½“

    25

    91 mm (3.6")

    3“

    25

    106 mm (4.2")



    IDF threaded socket

     

    DN

    PN

    ∅D

    H2

    2“

    25

    64 mm (2.5")

    Approx. 52 mm (2.1")

    2½“

    25

    77,5 mm (3.1")

    3“

    25

    91 mm (3.6")



    Aseptic threaded socket to DIN 11864-1 Form A

     

    DN

    PN

    ∅D

    H2

    50

    25

     

    Approx. 52 mm (2.1")

    65

    25

     

    80

    25

     

    100

    25

     


    Aseptic flange with notch to DIN 11864-2 Form A

     

    DN

    PN

    ∅D

    H2

    50

    16

     

    Approx. 52 mm (2.1")

    65

    16

     

    80

    16

     

    100

    16

     


    Aseptic flange with groove to DIN 11864-2 Form A

     

    DN

    PN

    ∅D

    H2

    50

    16

     

    Approx. 52 mm (2.1")

    65

    16

     

    80

    16

     

    100

      


    Aseptic clamp with groove to DIN 11864-3 Form A

     

    DN

    PN

    ∅D

    H2

    50

    25

     

    Approx. 52 mm (2.1")

    65

    25

     

    80

    16

     

    100

    16

     


    Технические данные

    SITRANS P, DS III series for gauge and absolute pressure, with flush-mounted diaphragm

     

    HART

    PROFIBUS PA or Foundation Fieldbus

    Input of gauge pressure, with flush-mounted diaphragm

     

    Measured variable

    Gauge pressure, flush-mounted

    Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure

    Span

    Max. perm. test pressure

    Nominal measuring range

    Max. perm. test pressure

     

    0.01 ... 1 bar g
    (0.15 ... 14.5 psi g)

    6 bar g
    (87 psi g)

    1 bar g
    (14.5 psi g)

    6 bar g
    (87 psi g)

     

    0.04 ... 4 bar g
    (0.58 ... 58 psi g)

    10 bar g
    (145 psi g)

    4 bar g
    (58 psi g)

    10 bar g
    (145 psi g)

     

    0.16 ... 16 bar g
    (2.32 ... 232 psi g)

    32 bar g
    (464 psi g)

    16 bar g
    (232 psi g)

    32 bar g
    (464 psi g)

     

    0.6 ... 63 bar g
    (9.14 ... 914 psi g)

    100 bar g
    (1450 psi g)

    63 bar g
    (914 psi g)

    100 bar g
    (1450 psi g)

    Lower measuring limit

    -100 mbar g (-1.45 psi g)

    Upper measuring limit

    100 % of max. span

    100 % of the max. nominal measuring range

    Input of absolute pressure, with flush-mounted diaphragm

     

    Measured variable

    Absolute pressure, flush-mounted

    Spans (infinitely adjustable) or
    nominal measuring range and
    max. permissible test pressure

    Span

    Max. perm. test pressure

    Nominal measuring range

    Max. perm. test pressure

     

    43 ... 1300 mbar a
    (0.62 ... 18.9 psi a)

    10 bar a
    (145 psi a)

    1300 mbar a
    (18.9 psi a)

    10 bar a
    (145 psi a)

     

    0,16 ... 5 bar a
    (2.32 ... 72.5 psi a)

    30 bar a
    (435 psi a)

    5 bar a
    (72.5 psi a)

    30 bar a
    (435 psi a)

     

    1 ... 30 bar a
    (14.5 ... 435 psi a)

    100 bar a
    (1450 psi a)

    30 bar a
    (435 psi a)

    100 bar a
    (1450 psi a)

    Lower measuring limit

    0 bar a (0 psi a)

    Upper measuring limit

    100% of max. span

    100% of the max. nominal measuring range

    Output

      

    Output signal

    4 ... 20 mA

    Digital PROFIBUS PA or Foundation Fieldbus signal

    • Lower limit (infinitely adjustable)

    3.55 mA, factory preset to 3.84 mA

    -

    • Upper limit (infinitely adjustable)

    23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA

    -

    Load

     
    • Without HART communication

    RB ≤ (UH - 10.5 V)/0.023 A in Ω,
    UH : Power supply in V

    -

    • With HART communication

    RB = 230 ... 500 Ω (SIMATIC PDM) or
    RB = 230 ... 1100 Ω (HART Communicator)

    -

    Physical bus

    -

    IEC 61158-2

    Protection against polarity reversal

    Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage.

    Measuring accuracy

    Acc. to EN 60770-1

    Reference conditions
    (All error data refer always refer to the set span)

    Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F)) r: Span ratio
    (r = max. span / set span)

    Error in measurement and fixed-point setting (including hysteresis and repeatability)

     
     

    Gauge pressure,
    flush-mounted

    Absolute pressure,
    flush-mounted

    Gauge pressure,
    flush-mounted

    Absolute pressure,
    flush-mounted

    • Linear characteristic
      

    ≤ 0,075 %

    ≤ 0.2 %

    • r ≤ 10

    ≤ (0.0029 · r + 0.071) %

    ≤ 0.2 %

      
    • 10 < r ≤ 30

    ≤ (0.0045 · r + 0.071)%

    ≤ 0.4 %

      
    • 30 < r ≤ 100

    ≤ (0.005 · r + 0.05)%

       

    Long-term drift (temperature change ±30 °C (±54 °F))

    ≤ (0.25 · r)% every 5 years

     

    ≤ 0.25 % every 5 years

     

    Influence of ambient temperature

        
    • at -10 ... +60 °C (14 ... 140 °F)

    ≤ (0.1 · r + 0.2)%

    ≤ (0.2 · r + 0.3)%

    ≤ 0.3 %

    ≤ 0.5 %

    • at -40 ... -10 °C and +60 ... +85 °C
      (-40 ... +14 °F and 140 ... 185 °F)

    ≤ (0.1·r + 0.15) %/10 K

    ≤ (0.2·r + 0.3) %/10 K

    ≤ 0.25 %/10 K

    ≤ 0.5 %/10 K

    Influence of mounting position

    0.1 mbar g (0.00145 psi g) per 10° inclination

    Measured Value Resolution

    -

    3 · 10-5 of nominal measuring range

    Influence of the medium temperature (only with flush-mounted diaphragm)

     
    • Temperature difference between medium temperature and ambient temperature

    3 mbar/10 K (0.04 psi/10 K)

    Rated conditions

     

    Installation conditions

     

    Ambient temperature

    Observe the temperature class in areas subject to explosion hazard.

    • Measuring cell with silicone oil

    -40 ... +85 °C (-40 ... +185 °F)

    • Measuring cell with Neobee oil (with flush-mounted diaphragm)

    -10 ... +85 °C (14 ... 185 °F)

    • Measuring cell with inert liquid (not with flush-mounted diaphragm)

    -20 ... +85 °C (-4 ... +185 °F)

    • Digital display

    -30 ... +85 °C (-22 ... +185 °F)

    • Storage temperature

    -50 ... +85 °C (-58 ... +185 °F)
    (for Neobee: -20 ... +85 °C (-4 ... +185 °F))

    • Climatic class
     
    • Condensation

    Permissible

    Degree of protection (to EN 60529)

    IP65, IP68, NEMA 4X, enclosure cleaning, resistant to lyes, steam to 150° C (302 °F)

    • Electromagnetic Compatibility
     
    • Emitted interference and interference immunity

    Acc. to EN 61326 and NAMUR NE 21

    Medium conditions

     

    Temperature of medium

     
    • Measuring cell with silicone oil

    -40 ... +100 °C (-40 ... +212 °F)

    • Measuring cell with silicone oil (with flush-mounted diaphragm)

    -40 ... +150 °C (-40 ... +302 °F)

    • Measuring cell with Neobee oil (with flush-mounted diaphragm)

    -10 ... +150 °C (14 ... 302 °F)

    • Measuring cell with silicone oil, with temperature decoupler (only with flush-mounted diaphragm)

    -40 ... +200 °C (-40 ... +392 °F)

    • Measuring cell with inert liquid

    -20 ... +100 °C (-4 ... +212 °F)

    • Measuring cell with high-temperature oil

    -10 ... +250 °C (14 ... 482 °F)

    Process connection

    • Flanges as per EN and ASME
    • F&B and pharmaceutical flanges

    Surface quality touched-by-media

    Ra values ≤ 0.8 µm (3.15.10-8 inch)/welded seams Ra ≤ 1.6 µm (6.4.10-8 inch)

    (process connections according to 3A; Ra values ≤ 0.8 µm (3.15.10-8 inch)/welded seams Ra ≤ 0.8 µm (3.15.10-8 inch)

    Design

     

    Weight (without options)

    ≈ 1.5 kg (≈ 3.3 lb)

    Enclosure material

    Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. No. 1.4408

    Wetted parts materials

    Stainless steel, mat. No. 1.4404/316L

    Measuring cell filling

    Silicone oil or inert filling liquid

    Power supply UH

     

    Supplied through bus

    Terminal voltage on transmitter

    10.5 ... 45 V DC
    10.5 ... 30 V DC in intrinsically-safe mode

    -

    Separate 24 V power supply necessary

    -

    No

    Bus voltage

     
    • Not Ex

    -

    9 ...32 V

    • With intrinsically-safe operation

    -

    9 ...24 V

    Current consumption

     
    • Basic current (max.)

    -

    12.5 mA

    • Startup current ≤ basic current

    -

    Yes

    • Max. current in event of fault

    -

    15.5 mA

    Fault disconnection electronics (FDE) available

    -

    Yes

    Certificates and approvals

      

    Classification according to PED 97/23/EC

    For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice)

    Explosion protection

     
    • Intrinsic safety "i"

    PTB 99 ATEX 2122

    • Marking

    Ex II 1/2 G EEx ia/ib IIB/IIC T6

    • Permissible ambient temperature

    -40 ... +85 °C (-40 ... +185 °F) temperature class T4;
    -40 ... +70 °C (-40 ... +158 °F) temperature class T5;
    -40 ... +60 °C (-40 ... +140 °F) temperature class T6

    • Connection

    To certified intrinsically-safe circuits with peak values:
    Ui = 30 V, Ii = 100 mA,
    Pi = 750 mW; Ri = 300 Ω

    FISCO supply unit:
    Uo = 17.5 V, Io = 380 mA, Po = 5.32 W

    Linear barrier:
    Uo = 24 V, Io = 250 mA, Po = 1.2 W

    • Effective internal inductance/capacitance

    Li = 0.4 mH, Ci = 6 nF

    Li = 7 μH, Ci = 1.1 nF

    • Explosion-proof "d"

    PTB 99 ATEX 1160

    • Marking

    Ex II 1/2 G EEx d IIC T4/T6

    • Permissible ambient temperature

    -40 ... +85 °C (-40 ... +185 °F) temperature class T4;
    -40 ... +60 °C (-40 ... +140 °F) temperature class T6

    • Connection

    To circuits with values: UH = 10.5 ... 45 V DC

    To circuits with values: UH = 9 ... 32 V DC

    • Dust explosion protection for zone 20

    PTB 01 ATEX 2055

    • Marking

    Ex II 1 D IP65 T 120 °C
    Ex II 1/2 D IP65 T 120 °C

    • Permissible ambient temperature

    -40 ... +85 °C (-40 ... +185 °F)

    • Max. surface temperature

    120 °C (248 °F)

    • Connection

    To certified intrinsically-safe circuits with peak values:
    Ui = 30 V, Ii = 100 mA,
    Pi = 750 mW, Ri = 300 Ω

    FISCO supply unit:
    Uo = 17.5 V, Io = 380 mA, Po = 5.32 W

    Linear barrier:
    Uo = 24 V, Io = 250 mA, Po = 1.2 W

    • Effective internal inductance/capacitance

    Li = 0.4 mH, Ci = 6 nF

    Li = 7 μH, Ci = 1.1 nF

    • Dust explosion protection for zone 21/22

    PTB 01 ATEX 2055

    • Marking

    Ex II 2 D IP65 T 120 °C

    • Connection

    To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W

    To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W

    • Type of protection "n" (zone 2)

    TÜV 01 ATEX 1696 X

    Planned

    • Marking

    Ex II 3 G EEx nA L IIC T4/T5/T6

    -

    • Explosion protection acc. to FM

    Certificate of Compliance 3008490

    • Identification (XP/DIP) or (IS); (NI)

    CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

    • Explosion protection to CSA

    Certificate of Compliance 1153651

    • Identification (XP/DIP) or (IS)

    CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III



    Hygiene version

    In the case of SITRANS P DSIII with 7MF413x flush-mounted diaphragm, selected connections comply with the requirements of EHEDG.

    HART communication

     

    HART communication

    230 ... 1100 Ω

    Protocol

    HART Version 5.x

    Software for computer

    SIMATIC PDM



    PROFIBUS PA communication

     

    Simultaneous communication with master class 2 (max.)

    4

    The address can be set using

    Configuration tool or local operation (standard setting address 126)

    Cyclic data usage

     
    • Output byte

    5 (one measured value) or
    10 (two measured values)

    • Input byte

    0, 1, or 2 (register operating mode and reset function for metering)

    Internal preprocessing

     

    Device profile

    PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B

    Function blocks

    2

    • Analog input
     
    • Adaptation to customer-specific process variables

    Yes, linearly rising or falling characteristic

    • Electrical damping T63 , adjustable

    0 to 100 s

    • Simulation function

    Input /Output

    • Failure mode

    parameterizable (last good value, substitute value, incorrect value)

    • Limit monitoring

    Yes, one upper and lower warning limit and one alarm limit respectively

    • Register (totalizer)

    Can be reset, preset, optional direction of counting, simulation function of register output

    • Failure mode

    parameterizable (summation with last good value, continuous summation, summation with incorrect value)

    • Limit monitoring

    One upper and lower warning limit and one alarm limit respectively

    • Physical block

    1

    Transducer blocks

    2

    • Pressure transducer block
     
    • Can be calibrated by applying two pressures

    Yes

    • Monitoring of sensor limits

    Yes

    • Specification of a container characteristic with

    Max. 30 nodes

    • Square-rooted characteristic for flow measurement

    Yes

    • Gradual volume suppression and implementation point of square-root extraction

    Parameterizable

    • Simulation function for measured pressure value and sensor temperature

    Constant value or over parameterizable ramp function



    Communication Foundation Fieldbus

     

    Function blocks

    3 function blocks analog input, 1 function block PID

    • Analog input
     
    • Adaptation to customer-specific process variables

    Yes, linearly rising or falling characteristic

    • Electrical damping T63 , adjustable

    0 to 100 s

    • Simulation function

    Output/input (can be locked within the device with a bridge)

    • Failure mode

    parameterizable (last good value, substitute value, incorrect value)

    • Limit monitoring

    Yes, one upper and lower warning limit and one alarm limit respectively

    • Square-rooted characteristic for flow measurement

    Yes

    • PID

    Standard FF function block

    • Physical block

    1 resource block

    Transducer blocks

    1 transducer block Pressure with calibration, 1 transducer block LCD

    • Pressure transducer block
     
    • Can be calibrated by applying two pressures

    Yes

    • Monitoring of sensor limits

    Yes

    • Simulation function: Measured pressure value, sensor temperature and electronics temperature

    Constant value or over parameterizable ramp function