    SITRANS P pressure transmitters, DS III HART series for gage pressure, dimensions in mm (inch)

    SITRANS P pressure transmitters, DS III PA and FF series for gage pressure, dimensions in mm (inch)

    Технические данные

    SITRANS P, DS III series for gauge pressure

     

    HART

    PROFIBUS PA or Foundation Fieldbus

    Input

     

    Measured variable

    Gauge pressure

    Spans (infinitely adjustable) or
    nominal measuring range and
    max. permissible test pressure

    Span

    Max. perm. test pressure

    Rated measuring range

    Max. perm. test pressure

     

    0,01 ... 1 bar g
    (0.15 ... 14.5 psi g)

    6 bar g
    (87 psi g)

    1 bar g
    (14.5 psi g)

    6 bar g
    (87 psi g)

     

    0.04 ... 4 bar g
    (0.58 ... 58 psi g)

    10 bar g
    (145 psi g)

    4 bar g
    (58 psi g)

    10 bar g
    (145 psi g)

     

    0.16 ... 16 bar g
    (2.32 ... 232 psi g)

    32 bar g
    (464 psi g)

    16 bar g
    (232 psi g)

    32 bar g
    (464 psi g)

     

    0.6 ... 63 bar g
    (9.14 ... 914 psi g)

    100 bar g
    (1450 psi g)

    63 bar g
    (914 psi g)

    100 bar g
    (1450 psi g)

     

    1.6 ... 160 bar g
    (23.2 ... 2320 psi g)

    250 bar g
    (3626 psi g)

    160 bar g
    (2320 psi g)

    250 bar g
    (3626 psi g)

     

    4.0 ... 400 bar g
    (58 ... 5802 psi g)

    600 bar g
    (8700 psi g)

    400 bar g
    (5802 psi g)

    600 bar g
    (8700 psi g)

     

    7.0 ... 700 bar g
    (102 ... 10153 psi g)

    800 bar g
    (11603 psi g)

    700 bar g
    (10153 psi g)

    800 bar g
    (11603 psi g)

    Lower measuring limit

      
    • Measuring cell with silicone oil filling

    30 mbar a (0.435 psi a)

    • Measuring cell with inert filling liquid

    30 mbar a (0.435 psi a)

    Upper measuring limit

    100 % of max. span (for oxygen version and inert filling liquid; max. 160 bar g (2320 psi g))

    Output

      

    Output signal

    4 ... 20 mA

    Digital PROFIBUS PA or Foundation Fieldbus signal

    • Lower limit (infinitely adjustable)

    3.55 mA, factory preset to 3.84 mA

    -

    • Upper limit (infinitely adjustable)

    23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA

    -

    Load

     
    • Without HART communication

    RB ≤ (UH - 10.5 V)/0.023 A in Ω,
    UH : Power supply in V

    -

    • With HART communication

    RB = 230 ... 500 Ω (SIMATIC PDM) or
    RB = 230 ... 1100 Ω (HART Communicator)

    -

    Physical bus

    -

    IEC 61158-2

    Protection against polarity reversal

    Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage.

    Measuring accuracy

    Acc. to EN 60770-1

    Reference conditions
    (All error data refer always refer to the set span)

    Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F)) r: Span ratio
    (r = max. span / set span)

    Error in measurement and fixed-point setting (including hysteresis and repeatability)

     
    • Linear characteristic
     

    ≤ 0,075 %

    • r ≤ 10

    ≤ (0.0029 · r + 0.071)%

     
    • 10 < r ≤ 30

    ≤ (0.0045 · r + 0.071)%

     
    • 30 < r ≤ 100

    ≤ (0.005 · r + 0.05)%

     

    Long-term drift (temperature change ±30 °C (±54 °F))

    ≤ (0.25 · r)% every 5 years

    ≤ 0.25 % every 5 years

    Influence of ambient temperature

     
    • at -10 ... +60 °C (14 ... 140 °F)

    ≤ (0.08 · r + 0.1)%
    (at 700 bar: ≤ (0.1 · r + 0.2)%

    ≤ 0,3 %

    • at -40 ... -10 °C and +60 ... +85 °C
      (-40 ... +14 °F and 140 ... 185 °F)

    ≤ (0.1·r + 0.15) %/10 K

    ≤ 0.25 %/10 K

    Measured Value Resolution

    -

    3 · 10-5 of nominal measuring range

    Rated conditions

     

    Degree of protection (to EN 60529)

    IP65

    Temperature of medium

     
    • Measuring cell with silicone oil filling

    -40 ... +100 °C (-40 ... +212 °F)

    • Measuring cell with inert filling liquid

    -20 ... +100 °C (-4 ... +212 °F)

    • In conjunction with dust explosion protection

    -20 ... +60 °C (-4 ... +140 °F)

    Ambient conditions

     
    • Ambient temperature
     
    • Digital indicator

    -30 ... +85 °C (-22 ... +185 °F)

    • Storage temperature

    -50 ... +85 °C (-58 ... +185 °F)

    • Climatic class
     
    • Condensation

    Permissible

    • Electromagnetic Compatibility
     
    • Emitted interference

    Acc. to EN 50081-1

    • Interference immunity

    Acc. to EN 61326 and NAMUR NE 21

    Design

     

    Weight (without options)

    ≈ 1.5 kg (≈ 3.3 lb)

    Enclosure material

    Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. No. 1.4408

    Wetted parts materials

     
    • Connection shank

    Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610

    • Oval flange

    Stainless steel, mat. No. 1.4404/316L

    • Seal diaphragm

    Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819

    Measuring cell filling

    Silicone oil or inert filling liquid (max. 160 bar (2320 psi g) with oxygen measurement)

    Process connection

    Connection shank G½B to DIN EN 837-1, female thread ½ -14 NPT or oval flange (PN 160 (MWP 2320 psi g)) to DIN 19213 with mounting thread M10 or 7/16-20 UNF to EN 61518

    Material of mounting bracket

     

    Steel

    Sheet-steel, Mat. No. 1.0330, chrome-plated

    Stainless steel

    Stainless steel, mat. No. 1.4301 (SS 304)

    Power supply UH

     

    Supplied through bus

    Terminal voltage on transmitter

    10.5 ... 45 V DC
    10.5 ... 30 V DC in intrinsically-safe mode

    -

    Separate 24 V power supply necessary

    -

    No

    Bus voltage

     
    • Not Ex

    -

    9 ...32 V

    • With intrinsically-safe operation

    -

    9 ...24 V

    Current consumption

     
    • Basic current (max.)

    -

    12.5 mA

    • Startup current ≤ basic current

    -

    Yes

    • Max. current in event of fault

    -

    15.5 mA

    Fault disconnection electronics (FDE) available

    -

    Yes

    Certificates and approvals

      

    Classification according to PED 97/23/EC

    For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice)

    Explosion protection

     
    • Intrinsic safety "i"

    PTB 99 ATEX 2122

    • Marking

    Ex II 1/2 G EEx ia/ib IIB/IIC T6

    • Permissible ambient temperature

    -40 ... +85 °C (-40 ... +185 °F) temperature class T4;
    -40 ... +70 °C (-40 ... +158 °F) temperature class T5;
    -40 ... +60 °C (-40 ... +140 °F) temperature class T6

    • Interface

    To certified intrinsically-safe circuits with peak values:
    Ui = 30 V, Ii = 100 mA,
    Pi = 750 mW; Ri = 300 Ω

    FISCO supply unit:
    Uo = 17.5 V, Io = 380 mA, Po = 5.32 W

    Linear barrier:
    Uo = 24 V, Io = 250 mA, Po = 1.2 W

    • Effective internal inductance/capacitance

    Li = 0.4 mH, Ci = 6 nF

    Li = 7 μH, Ci = 1.1 nF

    • Explosion-proof "d"

    PTB 99 ATEX 1160

    • Marking

    Ex II 1/2 G EEx d IIC T4/T6

    • Permissible ambient temperature

    -40 ... +85 °C (-40 ... +185 °F) temperature class T4;
    -40 ... +60 °C (-40 ... +140 °F) temperature class T6

    • Interface

    To circuits with values: UH = 10.5 ... 45 V DC

    To circuits with values: UH = 9 ... 32 V DC

    • Dust explosion protection for zone 20

    PTB 01 ATEX 2055

    • Marking

    Ex II 1 D IP65 T 120 °C
    Ex II 1/2 D IP65 T 120 °C

    • Permissible ambient temperature

    -40 ... +85 °C (-40 ... +185 °F)

    • Max. surface temperature

    120 °C (248 °F)

    • Interface

    To certified intrinsically-safe circuits with peak values:
    Ui = 30 V, Ii = 100 mA,
    Pi = 750 mW, Ri = 300 Ω

    FISCO supply unit:
    Uo = 17.5 V, Io = 380 mA, Po = 5.32 W

    Linear barrier:
    Uo = 24 V, Io = 250 mA, Po = 1.2 W

    • Effective internal inductance/capacitance

    Li = 0.4 mH, Ci = 6 nF

    Li = 7 μH, Ci = 1.1 nF

    • Dust explosion protection for zone 21/22

    PTB 01 ATEX 2055

    • Marking

    Ex II 2 D IP65 T 120 °C

    • Interface

    To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W

    To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W

    • Type of protection "n" (zone 2)

    TÜV 01 ATEX 1696 X

    Planned

    • Marking

    Ex II 3 G EEx nA L IIC T4/T5/T6

    -

    • Explosion protection acc. to FM

    Certificate of Compliance 3008490

    • Identification (XP/DIP) or (IS); (NI)

    CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

    • Explosion protection to CSA

    Certificate of Compliance 1153651

    • Identification (XP/DIP) or (IS)

    CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III



    HART communication

     

    HART communication

    230 ... 1100 Ω

    Protocol

    HART Version 5.x

    Software for computer

    SIMATIC PDM



    PROFIBUS PA communication

     

    Simultaneous communication with master class 2 (max.)

    4

    The address can be set using

    Configuration tool or local operation (standard setting address 126)

    Cyclic data usage

     
    • Output byte

    5 (one measured value) or
    10 (two measured values)

    • Input byte

    0, 1, or 2 (register operating mode and reset function for metering)

    Internal preprocessing

     

    Device profile

    PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B

    Function blocks

    2

    • Analog input
     
    • Adaptation to customer-specific process variables

    Yes, linearly rising or falling characteristic

    • Electrical damping T63 , adjustable

    0 to 100 s

    • Simulation function

    Input /Output

    • Failure mode

    parameterizable (last good value, substitute value, incorrect value)

    • Limit monitoring

    Yes, one upper and lower warning limit and one alarm limit respectively

    • Register (totalizer)

    Can be reset, preset, optional direction of counting, simulation function of register output

    • Failure mode

    parameterizable (summation with last good value, continuous summation, summation with incorrect value)

    • Limit monitoring

    One upper and lower warning limit and one alarm limit respectively

    • Physical block

    1

    Transducer blocks

    2

    • Pressure transducer block
     
    • Can be calibrated by applying two pressures

    Yes

    • Monitoring of sensor limits

    Yes

    • Specification of a container characteristic with

    Max. 30 nodes

    • Square-rooted characteristic for flow measurement

    Yes

    • Gradual volume suppression and implementation point of square-root extraction

    Parameterizable

    • Simulation function for measured pressure value and sensor temperature

    Constant value or over parameterizable ramp function



    Communication Foundation Fieldbus

     

    Function blocks

    3 function blocks analog input, 1 function block PID

    • Analog input
     
    • Adaptation to customer-specific process variables

    Yes, linearly rising or falling characteristic

    • Electrical damping T63 , adjustable

    0 to 100 s

    • Simulation function

    Output/input (can be locked within the device with a bridge)

    • Failure mode

    parameterizable (last good value, substitute value, incorrect value)

    • Limit monitoring

    Yes, one upper and lower warning limit and one alarm limit respectively

    • Square-rooted characteristic for flow measurement

    Yes

    • PID

    Standard FF function block

    • Physical block

    1 resource block

    Transducer blocks

    1 transducer block Pressure with calibration, 1 transducer block LCD

    • Pressure transducer block
     
    • Can be calibrated by applying two pressures

    Yes

    • Monitoring of sensor limits

    Yes

    • Simulation function: Measured pressure value, sensor temperature and electronics temperature

    Constant value or over parameterizable ramp function