Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS S7-400 CPU 414H

  • Заказные данные
    (1)
  • Аксессуары
    (20)
  • Информационные материалы

    Информационные материалы

    • CPU for SIPLUS S7-400H
    • Usable in high-availability systems such as the S7-400H
    • With integral PROFIBUS DP master interface
    • Features 2 slots for sync modules
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Область применения

    The CPU 414-5H can be used for the SIMATIC S7-400H. It enables configuration of an S7-400H high-availability system

    The integrated PROFIBUS DP interfaces facilitate direct connection as master to the PROFIBUS DP fieldbus.

    The integrated PROFINET interface with switch functionality forms the basis for providing 2 externally accessible PROFINET ports. In this way, linear or ring structures can be implemented.

    Дизайн

    The CPU 414-5H features:

    • A powerful processor:
      The CPU achieves command execution times as low as 18.75 ns per binary command.
    • 4 MB main memory (2 MB for programs, 2 MB for data);
      load memory for user programs and configuration data for the S7-400 H automation system; fast main memory for runtime-relevant subroutines of the user program.
    • A memory card:
      For expanding the integrated load memory. In addition to the program itself, the information contained in the load memory also includes configuration data for the S7-400H, which is why it takes up around twice as much space in the memory. The result is:
      • The integrated load memory is not sufficient for large programs, which is why a memory card is often required.
        RAM and FEPROM cards are available (FEPROM for saving data even when power supply is disconnected).
    • Flexible expansion options
      Up to 131 072 digital and 81 932 analog inputs/outputs
    • MPI multi-point interface:
      The MPI enables the creation of a simple network with up to 32 nodes and a data transfer rate of 187.5 kbit/s. The CPU can establish up to 64 connections to nodes on the communication bus (C bus) and the MPI.
      Note:
      If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:
      • With socket: 6ES7 972-0BB42-0XA0
      • Without socket: 6ES7 972-0BA42-0XA0
    • PROFIBUS DP interface:
      The PROFIBUS DP interface allows a redundant, distributed automation configuration offering high speed and ease of use. From the user's point of view, the distributed I/O is handled like the centralized I/O (same configuring, addressing and programming).
    • PROFINET interface with 2 ports (switch):
      Supports system redundancy and MRP (Media Redundancy Protocol)
    • Mode selector:
      Toggle switch design.
    • Diagnostics buffer:
      The last 120 alarm and interrupt events are stored in a ring buffer for diagnostic purposes.
    • Real-time clock:
      Diagnostics reports from the CPU are provided with the date and time.
    • PROFIBUS DP interface:
      The CPU 414-5H with PROFIBUS DP master interface enables distributed automation to be established at high speed and with easy operation. From the user's point of view, the distributed I/O is handled like the centralized I/O (same configuring, addressing and programming).
      Note:
      If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:
      • With socket: 6ES7 972-0BB42-0XA0
      • Without socket: 6ES7 972-0BA42-0XA0

    Функции

    • Block protection:
      In addition to the keyswitch, a password concept protects the user program from unauthorized access. User blocks can also be protected by an encryption mechanism.
    • Integrated HMI services:
      In the case of HMI devices, the user only has to specify the source and destination of the data. These are automatically transferred cyclically by the system.
    • Integrated communication functions:
      • PG/OP communication
      • Extended communication (simple and high-availability)
    • Master-spare switchover programmed by user.
    Parameterizable properties

    With the STEP 7 tool "Hardware Configuration" and the installed option package S7-400H, the properties and behavior of the S7-400H including the CPUs can be parameterized, e.g.:

    • MPI multi-point interface:
      • Determining node addresses.
      • Startup/cyclic behavior.
      • Definition of maximum cycle time and communication load.
    • Address assignment:
      Addressing of I/O modules
    • Retentive areas:
      Definition of the number of retentive bit memories, counters, timers, data blocks and clock memories.
    • Protection level:
      Definition of access authorization to program and data.
    • System diagnostics:
      Determination of handling and scope of diagnostics messages.
    • Watchdog interrupts:
      Setting the periodicity.
    • Configuring of H stations.
    Display and information functions
    • Status and fault indicators:
      LEDs indicate, for example, internal and external faults and operating statuses such as RUN, STOP, startup, "Master" operating mode, redundancy errors, and test function.
    • Test functions:
      The programming device can be used to display signal states in the program execution sequence, modify process variables independently of the user program, output contents of stack memories, run through program steps individually, and disable program sections.
    • Information functions:
      The user can obtain information about the memory capacity and operating mode of the CPU, and the current utilization of the RAM and load memory.

    Технические данные

    Order number

    6AG1412-5HK06-7AB0

    SIPLUS S7-400 CPU 412-5H

    General information

     

    Product type designation

    CPU 412-5H PN/DP

    Engineering with

     

    • Programming package

    As of STEP 7 V5.5 SP2 with HF1

    Supply voltage

     

    Rated value (DC)

    • 24 V DC

    No; Power supply via system power supply

    Power loss

     

    Power loss, typ.

    7.5 W

    Memory

     

    Work memory

     

    • integrated

    1 Mbyte

    • integrated (for program)

    512 kbyte

    • integrated (for data)

    512 kbyte

    Load memory

     

    • expandable FEPROM, max.

    64 Mbyte

    • integrated RAM, max.

    512 kbyte

    • expandable RAM, max.

    64 Mbyte

    CPU processing times

     

    for bit operations, typ.

    31.25 ns

    for word operations, typ.

    31.25 ns

    for fixed point arithmetic, typ.

    31.25 ns

    for floating point arithmetic, typ.

    62.5 ns

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    2 048

    IEC counter

     

    • present

    Yes

    S7 times

     

    • Number

    2 048

    IEC timer

     

    • present

    Yes

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    8 192 byte

    Address area

     

    I/O address area

     

    • Inputs

    8 kbyte

    • Outputs

    8 kbyte

    Process image

     

    • Inputs, adjustable

    8 kbyte

    • Outputs, adjustable

    8 kbyte

    Time of day

     

    Clock

     

    • Hardware clock (real-time)

    Yes

    Operating hours counter

     

    • Number

    16

    Interfaces

     

    Number of RS 485 interfaces

    2

    Number of other interfaces

    2; Fiber-optic interface

    1. Interface

     

    Interface type

    Integrated

    Physics

    RS 485 / PROFIBUS + MPI

    Functionality

     

    • MPI

    Yes

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    No

    DP master

     

    • Number of DP slaves, max.

    32

    2. Interface

     

    Interface type

    PROFINET

    Physics

    Ethernet RJ45

    Interface types

     

    • Number of ports

    2

    Functionality

     

    • PROFINET IO Controller

    Yes

    • PROFINET IO Device

    No

    • PROFINET CBA

    No

    • PROFIBUS DP master

    No

    • PROFIBUS DP slave

    No

    3. Interface

     

    Interface type

    Integrated

    Physics

    RS 485 / PROFIBUS

    Functionality

     

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    No

    DP master

     

    • Number of DP slaves, max.

    64

    4. Interface

     

    Interface type

    Pluggable synchronization submodule (FO)

    Plug-in interface modules

    Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

    5. Interface

     

    Interface type

    Pluggable synchronization submodule (FO)

    Plug-in interface modules

    Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    No

    Communication functions

     

    PG/OP communication

    Yes

    Data record routing

    Yes

    S7 routing

    Yes

    Global data communication

     

    • supported

    No

    S7 basic communication

     

    • supported

    No

    S7 communication

     

    • supported

    Yes

    S5 compatible communication

     

    • supported

    Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

    Standard communication (FMS)

     

    • supported

    Yes; Via CP and loadable FB

    Open IE communication

     

    • TCP/IP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    46

    • ISO-on-TCP (RFC1006)

    Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

    • Number of connections, max.

    46

    • UDP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    46

    Web server

     

    • supported

    No

    Number of connections

     

    • overall

    48

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    -25 °C; = Tmin

    • max.

    70 °C; = Tmax; @ 60°C for UL/ATEX/FM and safety-related application

    Ambient temperature during storage/transportation

     

    • min.

    -40 °C

    • max.

    70 °C

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m). For "F-Systems" applications max. +2 000 m above sea level permissible

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Configuration

     

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Block encryption

    Yes; With S7 block Privacy

    Dimensions

     

    Width

    50 mm

    Height

    290 mm

    Depth

    219 mm

    Weights

     

    Weight, approx.

    995 g