Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Braking resistors for blocksize format

  • Заказные данные
    (19)
  • Информационные материалы

    Информационные материалы

    Braking resistor for PM240‑2 Power Modules, frame size FSD

    Excess energy in the DC link is dissipated in the braking resistor. The braking resistors are intended for use with PM240‑2 Power Modules which feature an integrated braking chopper, but cannot regenerate energy to the supply system. For regenerative operation, e.g. the braking of a rotating mass with high moment of inertia, a braking resistor must be connected to convert the resulting energy into heat.

    The braking resistors can be installed laterally next to the PM240‑2 Power Modules. The braking resistors for the Power Modules, frame sizes FSD to FSF, should be placed outside the control cabinet or outside the switchgear room so that the heat is dissipated away from the Power Modules. The level of air conditioning required is therefore reduced.

    Every braking resistor has a temperature switch (UL-listed). The temperature switch should be evaluated to prevent consequential damage if the braking resistor overheats.

    Характеристика

    Load diagram for the braking resistors

    ta = 12 s (see section Technical specifications)

    t = 240 s (see Section Technical specifications)

    Интеграция

    Braking resistors that are optionally available depending on the Power Module used

     

    Frame size

     

    FSA

    FSB

    FSC

    FSD

    FSE

    FSF

    PM240-2 Power Module with integrated braking chopper

    Available frame sizes

     

     

     

     

     

     

    • 200 V versions

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    • 400 V versions

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    • 690 V versions

    ✓ 

    ✓ 

    ✓ 

    DC link components

    Braking resistor

    S

    S

    S

    S

    S

    S



    S = Lateral mounting

    – = Not possible

    Технические данные

    Line voltage 200 V … 240 V 1 AC/3 AC

    Braking resistor

     

    JJY:023146720008

    JJY:023151720007

    JJY:023163720018

    Resistance

    Ω 

    200

    68

    37

    Rated power PDB

    (continuous braking power)

    kW

    0.0375

    0.11

    0.2

    Peak power Pmax

    (load duration ta = 12 s with period t = 240 s)

    kW

    0.75

    2.2

    4

    Power connections

     

    Cable

    Cable

    Cable

    Thermostatic switch

     

    Integrated

    Integrated

    Integrated

    Degree of protection

     

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

    • Width

    mm (in)

    167 (6.57)

    217 (8.54)

    337 (13.27)

    • Height

    mm (in)

    60 (2.36)

    60 (2.36)

    60 (2.36)

    • Depth

    mm (in)

    30 (1.18)

    30 (1.18)

    30 (1.18)

    Weight, approx.

    kg (lb)

    0.5 (1.10)

    0.7 (1.54)

    1.1 (2.43)

    Suitable for
    PM240‑2 Power Module standard variant

    Type

    6SL3210-1PB13-0 . L0
    6SL3210-1PB13-8 . L0

    6SL3210-1PB15-5 . L0
    6SL3210-1PB17-4 . L0
    6SL3210-1PB21-0 . L0

    6SL3210-1PB21-4 . L0
    6SL3210-1PB21-8 . L0

    Suitable for
    PM240‑2 Power Module push‑through variant

    Type

    6SL3211-1PB13-8 . L0

    6SL3211-1PB21-0 . L0

    6SL3211-1PB21-8 . L0

    • Frame size

     

    FSA

    FSB

    FSC



     

    Line voltage 200 V … 240 V 3 AC

    Braking resistor

     

    JJY:023433720001

    JJY:023422620002

    JJY:023423320001

    JJY:023434020003

    Resistance

    Ω 

    20

    7.5

    4.5

    2.5

    Rated power PDB

    (continuous braking power)

    kW

    0.375

    0.93

    1.5

    2.75

    Peak power Pmax

    (load duration ta = 12 s with period t = 240 s)

    kW

    7.5

    18.5

    30

    55

    Power connections

     

    Cable

    Cable

    Cable

    Cable

    Thermostatic switch

     

    Integrated

    Integrated

    Integrated

    Integrated

    Degree of protection

     

    IP20

    IP21

    IP21

    IP21

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    337 (13.27)

    470 (18.5)

    560 (22.5)

    630 (24.8)

    • Height

    mm (in)

    120 (4.72)

    220 (8.66)

    220 (8.66)

    350 (13.78)

    • Depth

    mm (in)

    30 (1.18)

    180 (7.09)

    180 (7.09)

    180 (7.09)

    Weight, approx.

    kg (lb)

    2 (4.41)

    7 (15.4)

    8.5 (18.7)

    13.5 (29.8)

    Suitable for
    Power Module PM240‑2

    Type

    6SL3210-1PC22-2 . L0
    6SL3210-1PC22-8 . L0

    6SL3210-1PC24-2UL0
    6SL3210-1PC25-4UL0
    6SL3210-1PC26-8UL0

    6SL3210-1PC28-0UL0
    6SL3210-1PC31-1UL0

    6SL3210-1PC31-3UL0
    6SL3210-1PC31-6UL0
    6SL3210-1PC31-8UL0

    • Frame size

     

    FSC

    FSD

    FSE

    FSF



     

    Line voltage 380 ... 480 V 3 AC

    Braking resistor

     

    6SL3201-0BE14-3AA0

    6SL3201-0BE21-0AA0

    6SL3201-0BE21-8AA0

    6SL3201-0BE23-8AA0

    Resistance

    Ω 

    370

    140

    75

    30

    Rated power PDB

    (continuous braking power)

    kW

    0.075

    0.2

    0.375

    0.925

    Peak power Pmax

    (load duration ta = 12 s with period t = 240 s)

    kW

    1.5

    4

    7.5

    18.5

    Power connection

     

    Terminal block

    Terminal block

    Terminal block

    Terminal block

    • Conductor cross-section

    mm2

    2.5

    2.5

    4

    6

    Thermostatic switch

     

    NC contact

    NC contact

    NC contact

    NC contact

    • Contact load, max.

     

    250 V AC/2.5 A

    250 V AC/2.5 A

    250 V AC/2.5 A

    250 V AC/2.5 A

    • Conductor cross-section

    mm2

    2.5

    2.5

    2.5

    2.5

    PE connection

     

     

     

     

     

    • Via terminal block

     

    Yes

    Yes

    Yes

    Yes

    • PE connection on housing

     

    M4 screw

    M4 screw

    M4 screw

    M4 screw

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    105 (4.13)

    105 (4.13)

    175 (6.89)

    250 (9.84)

    • Height

    mm (in)

    295 (11.61)

    345 (13.58)

    345 (13.58)

    490 (19.29)

    • Depth

    mm (in)

    100 (3.94)

    100 (3.94)

    100 (3.94)

    140 (5.51)

    Weight, approx.

    kg (lb)

    1.5 (3.31)

    1.8 (3.97)

    2.7 (5.95)

    6.2 (13.7)

    Suitable for
    PM240‑2 Power Module
    standard variant
    380 ... 480 V 3 AC

    Type

    6SL3210-1PE11-8 . L1
    6SL3210-1PE12-3 . L1
    6SL3210-1PE13-2 . L1
    6SL3210-1PE14-3 . L1

    6SL3210-1PE16-1 . L1
    6SL3210-1PE18-0 . L1

    6SL3210-1PE21-1 . L0
    6SL3210-1PE21-4 . L0
    6SL3210-1PE21-8 . L0

    6SL3210-1PE22-7 . L0
    6SL3210-1PE23-3 . L0

    Suitable for
    PM240‑2 Power Module
    push-through variant
    380 ... 480 V 3 AC

    Type

    6SL3211-1PE18-0 . L1

    6SL3211-1PE21-8 . L0

    6SL3211-1PE23-3 . L0

    • Frame size

     

    FSA

    FSA

    FSB

    FSC



     

    Line voltage 380 ... 480 V 3 AC

    Braking resistor

     

    JJY:023422620001

    JJY:023424020001

    JJY:023434020001

    JJY:023454020001 1)

    JJY:023464020001 2)

    Resistance

    Ω 

    25

    15

    10

    7.1

    5

    Rated power PDB

    (continuous braking power)

    kW

    1.1

    1.85

    2.75

    3.85

    5.5

    Peak power Pmax

    (load duration ta = 12 s with period t = 240 s)

    kW

    22

    37

    55

    77

    110

    Power connection

     

    Cable

    Cable

    Cable

    Cable

    Cable

    Thermostatic switch

     

    Integrated

    Integrated

    Integrated

    Integrated

    Integrated

    Degree of protection

     

    IP21

    IP21

    IP21

    IP21

    IP21

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    470 (18.5)

    610 (24.0)

    630 (24.8)

    1)

    2)

    • Height

    mm (in)

    220 (8.66)

    220 (8.66)

    350 (13.78)

    1)

    2)

    • Depth

    mm (in)

    180 (7.09)

    180 (7.09)

    180 (7.09)

    1)

    2)

    Weight, approx.

    kg (lb)

    7 (15.4)

    9.5 (20.9)

    13.5 (29.8)

    20.5 (45.2)

    27 (59.5)

    Suitable for
    PM240‑2 Power Module

    Type

    6SL3210-1PE23-8 . L0
    6SL3210-1PE24-5 . L0

    6SL3210-1PE26-0 . L0
    6SL3210-1PE27-5 . L0

    6SL3210-1PE28-8 . L0
    6SL3210-1PE31-1 . L0

    6SL3210-1PE31-5 . L0
    6SL3210-1PE31-8 . L0

    6SL3210-1PE32-1 . L0
    6SL3210-1PE32-5 . L0

    • Frame size

     

    FSD

    FSD

    FSE

    FSF

    FSF



    1) This braking resistor consists of the two braking resistors, JJY:023422620001 and JJY:023434020001, which must be connected in parallel on the plant/system side.

    2) This braking resistor consists of two JJY:023434020001 braking resistors, which must be connected in parallel on the plant/system side.

     

    Line voltage 500 ... 690 V 3 AC

    Braking resistor

     

    JJY:023424020002

    JJY:023434020002

    JJY:023464020002 1)

    Resistance

    Ω 

    31

    21

    10.5

    Rated power PDB

    (continuous braking power)

    kW

    1.85

    2.75

    5.5

    Peak power Pmax

    (load duration ta = 12 s with period t = 240 s)

    kW

    37

    55

    110

    Power connection

     

    Cable

    Cable

    Cable

    Thermostatic switch

     

    Integrated

    Integrated

    Integrated

    Degree of protection

     

    IP21

    IP21

    IP21

    Dimensions

     

     

     

     

    • Width

    mm (in)

    610 (24.0)

    630 (24.8)

    1)

    • Height

    mm (in)

    220 (8.66)

    350 (13.78)

    1)

    • Depth

    mm (in)

    180 (7.09)

    180 (7.09)

    1)

    Weight, approx.

    kg (lb)

    9.5 (20.95)

    13.5 (29.7)

    27 (59.5)

    Suitable for
    PM240‑2 Power Module

    Type

    6SL3210-1PH21-4 . L0
    6SL3210-1PH22-0 . L0
    6SL3210-1PH22-3 . L0
    6SL3210-1PH22-7 . L0
    6SL3210-1PH23-5 . L0
    6SL3210-1PH24-2 . L0

    6SL3210-1PH25-2 . L0
    6SL3210-1PH26-2 . L0

    6SL3210-1PH28-0 . L0
    6SL3210-1PH31-0 . L0
    6SL3210-1PH31-2 . L0
    6SL3210-1PH31-4 . L0

    • Frame size

     

    FSD

    FSE

    FSF



    1) This braking resistor consists of two JJY:023434020002 braking resistors, which must be connected in parallel on the plant/system side.