VSM10 Voltage Sensing Module

  • Заказные данные
    (1)
  • Аксессуары
    (1)
  • Информационные материалы

    Информационные материалы

    VSM10 Voltage Sensing Module

    The VSM10 Voltage Sensing Module is capable of measuring the line voltage waveform precisely and helps Line Modules to continue functioning properly under difficult supply conditions, for example, in the case of extreme voltage fluctuations or brief supply interruptions.

    The VSM10 Voltage Sensing Module is integrated in Active Interface Modules in chassis format and Smart Line Modules in chassis format. It can be optionally deployed for all Active Line Modules in bookside format and for 16 kW and 36 kW Smart Line Modules.

    Дизайн

    The VSM10 Voltage Sensing Module has the following connections and interfaces:

    • 1 connection for direct line voltage sensing up to 690 V
    • 1 connection for line voltage sensing via voltage transformers; maximum voltage 100 V
    • 2 analog inputs (reserved for monitoring of resonance in the Active Interface Module in chassis format)
    • 1 temperature sensor input for KTY84‑130, Pt1000 or PTC (Pt1000 can be used from firmware V4.7 HF17)
    • 1 DRIVE‑CLiQ socket
    • 1 connection for the electronics power supply via the 24 V DC power supply connector
    • 1 PE (protective earth) connection

    The status of the VSM10 Voltage Sensing Modules is indicated via a multi-color LED.

    The VSM10 Voltage Sensing Module can be snapped onto a TH 35 standard mounting rail in accordance with EN 60715 (IEC 60715).

    Интеграция

    The VSM10 Voltage Sensing Module can communicate with the following Control Units via DRIVE‑CLiQ:

    • CU320‑2 Control Unit
    • SINUMERIK Control Unit
    • SIMOTION D Control Unit or Controller Extension

    Connection example of VSM10 Voltage Sensing Module

    Технические данные

     

    VSM10 Voltage Sensing Module

    6SL3053-0AA00-3AA1

    Current requirement, max.

    at 24 V DC

    0.2 A

    • Conductor cross-section, max.

    2.5 mm2

    Power loss, max.

    10 W

    Line voltage detection

     

    • Insulation resistance
      neutral point – ground when jumper is not inserted

    >10 MΩ

    • Input resistance

     

    • Terminal X521

    >362 kΩ/phase

    • Terminal X522

    >2.5 MΩ/phase

    Analog inputs

    (reserved for monitoring an Active Interface Module in chassis format)

     

    • Internal resistance, approx.
      (between differential inputs)

    100 kΩ

    • Resolution

    12 bits + sign

    PE connection

    M4 screw

    Dimensions

     

    • Width

    50 mm (1.97 in)

    • Height

    151 mm (5.94 in)

    • Depth

    110 mm (4.33 in)

    Weight, approx.

    1 kg (2.21 lb)

    Certificate of suitability