    The self-commutated infeed/regenerative feedback units (with IGBTs in infeed and regenerative feedback directions) generate a regulated DC link voltage. This means that the connected Motor Modules are decoupled from the line voltage. Line voltage fluctuations within the permissible supply tolerances have no effect on the motor voltage.

    If required, the Active Line Modules can also provide reactive power compensation.

    Active Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.

    Liquid-cooled Active Line Modules are especially suitable for applications where installation space is restricted and environmental conditions are harsh. Liquid cooling ensures efficient heat dissipation.

    Active Line Modules are always operated together with the associated Active Interface Modules. These include the necessary pre-charging circuit as well as a Clean Power Filter.

    Дизайн

    The liquid-cooled Active Line Modules have the following interfaces as standard:

    • 1 line supply connection
    • 1 connection for the 24 V DC electronics power supply
    • 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
    • 3 DRIVE‑CLiQ sockets
    • 1 temperature sensor input for KTY84‑130, Pt1000, PTC or Pt100 (Pt1000 can be used from firmware V4.7 HF17)
    • 1 PE connection
    • 2 coolant connections

    The status of the Active Line Modules is indicated via three LEDs.

    The following are included in the scope of supply of the Active Line Modules:

    • 1 DRIVE‑CLiQ cable for connection to the Control Unit
    • 2 seals for coolant connections
    • 1 set of warning labels in 30 languages
      (BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

    Интеграция

    Active Line Modules are always operated together with the associated Active Interface Modules. Active Interface Modules contain a Clean Power Filter with basic RI suppression, the pre-charging circuit for the Active Line Module, line supply voltage sensing circuit and monitoring sensors.

    The liquid-cooled Active Line Modules communicate with the higher-level control module via DRIVE‑CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate the Active Line Modules.

    Connection example of an Active Line Module

    Технические данные

    General technical specifications

    Electrical specifications

    Line power factor

     

    • Basic fundamental (cos φ1)

    1 (factory setting), can be altered by inputting a reactive current setpoint

    • Total (λ)

    1 (factory setting)

    Efficiency

    >98.5 % (Active Line Modules)

    >99 % (Active Interface Module)

    DC link voltage, approx.

    The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
    Factory setting of the DC link voltage: 1.5 × line voltage



    Line voltage 380 V ... 480 V 3 AC

    Active Line Modules

     

     

    6SL3335-7TE35-0AA3

    6SL3335-7TE36-1AA3

    6SL3335-7TE38-4AA3

    6SL3335-7TE41-0AA3

    6SL3335-7TE41-4AA3

    Rated power

     

     

     

     

     

     

    • At Irated DC (50 Hz 400 V)

    kW

    300

    380

    500

    630

    900

    • At IH DC (50 Hz 400 V)

    kW

    270

    335

    465

    545

    780

    • At Irated DC (60 Hz 460 V)

    hp

    500

    600

    700

    900

    1250

    • At IH DC (60 Hz 460 V)

    hp

    400

    500

    700

    800

    1000

    DC link current

     

     

     

     

     

     

    • Rated current Irated DC

    A

    549

    677

    941

    1100

    1573

    • Base-load current IH DC 1)

    A

    489

    603

    837

    982

    1401

    • Maximum current Imax DC

    A

    823

    1017

    1410

    1654

    2361

    Infeed/regenerative feedback current

     

     

     

     

     

     

    • Rated current Irated I

    A

    490

    605

    840

    985

    1405

    • Maximum current Imax I

    A

    735

    907

    1260

    1477

    2055

    Current demand

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.5

    1.6

    1.6

    1.6

    1.6

    DC link capacitance

     

     

     

     

     

     

    • Active Line Module

    μF

    9600

    12600

    17400

    18900

    28800

    Pulse frequency

    kHz

    4

    2.5

    2.5

    2.5

    2.5

    Power loss, at 50 Hz 400 V 2)

     

     

     

     

     

     

    • Dissipated to coolant

    kW

    3.42

    4.65

    5.52

    7.46

    9.58

    • Dissipated to ambient air

    kW

    0.14

    0.17

    0.23

    0.44

    0.62

    • Total

    kW

    3.56

    4.82

    5.75

    7.9

    10.2

    Coolant volume flow 3)

    l/min

    12

    16

    16

    27

    27

    Liquid volume

    of the integrated heat exchanger

    dm3

    0.91

    0.74

    0.74

    1.56

    1.56

    Pressure drop, typ. 4)

    for volume flow

    Pa

    70000

    70000

    70000

    70000

    70000

    Heat exchanger material

     

    Stainless steel

    Aluminum

    Aluminum

    Aluminum

    Aluminum

    Sound pressure level LpA 5)

    (1 m) at 50/60 Hz

    dB

    69/73

    70/73

    70/73

    71/73

    71/73

    Line connection

    U1, V1, W1

     

    Hole for M12

    2 x hole for M12

    2 x hole for M12

    2 x hole for M12

    2 x hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    4 × 185

    4 × 185

    Busbar

    Busbar

    DC link connection

    DCP, DCN

     

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    PE/GND connection

     

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    4 × 185

    4 × 185

    4 × 240

    4 × 240

    Cable length, max. 6)

     

     

     

     

     

     

    • Shielded

    m (ft)

    2700 (8859)

    3900 (12796)

    3900 (12796)

    3900 (12796)

    3900 (12796)

    • Unshielded

    m (ft)

    4050 (13288)

    5850 (19194)

    5850 (19194)

    5850 (19194)

    5850 (19194)

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    150 (5.91)

    265 (10.4)

    265 (10.4)

    295 (11.6)

    295 (11.6)

    • Height

    mm (in)

    1172 (46.1)

    1002 (39.4)

    1002 (39.4)

    1516 (59.7)

    1516 (59.7)

    • Depth

    mm (in)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    Weight, approx.

    kg (lb)

    80 (176)

    110 (243)

    110 (243)

    220 (486)

    220 (486)

    Frame size

     

    GXL

    HXL

    HXL

    JXL

    JXL

    Minimum short-circuit current 7)

    A

    8000

    9200

    10400

    16000

    21000



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

    3) The value applies to coolants comprising water and a mixture of water and anti-freeze agent.

    4) The value is valid for water as coolant. Additional information and notes on other coolants is provided in the SINAMICS Low Voltage Engineering Manual.

    5) Total sound pressure level of Active Interface Module and Active Line Module.

    6) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    7) Current required for reliably triggering protective devices.

    Line voltage 500 ... 690 V 3 AC

    Active Line Modules

     

     

    6SL3335-7TG35-8AA3

    6SL3335-7TG37-4AA3

    6SL3335-7TG38-1AA3

    6SL3335-7TG41-0AA3

    6SL3335-7TG41-3AA3

    6SL3335-7TG41-6AA3

    Rated power

     

     

     

     

     

     

     

    • At Irated DC (50 Hz 690 V)

    kW

    630

    800

    900

    1100

    1400

    1700

    • At IH DC (50 Hz 690 V)

    kW

    620

    705

    670

    1000

    1215

    1490

    • At Irated DC (50 Hz 500 V)

    kW

    447

    560

    620

    780

    965

    1180

    • At IH DC (50 Hz 500 V)

    kW

    450

    510

    485

    710

    880

    1080

    • At Irated DC (60 Hz 575 V)

    hp

    675

    900

    975

    1250

    1500

    1880

    • At IH DC (60 Hz 575 V)

    hp

    506

    600

    765

    1000

    1250

    1530

    DC link current

     

     

     

     

     

     

     

    • Rated current Irated DC

    A

    644

    823

    907

    1147

    1422

    1740

    • Base-load current IH DC 1)

    A

    573

    732

    808

    1022

    1266

    1550

    • Maximum current Imax DC

    A

    966

    1235

    1360

    1722

    2133

    2620

    Infeed/regenerative feedback current

     

     

     

     

     

     

     

    • Rated current Irated I

    A

    575

    735

    810

    1025

    1270

    1560

    • Maximum current Imax I

    A

    862

    1100

    1214

    1537

    1905

    2055

    Current demand

     

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.6

    1.6

    1.6

    1.6

    1.46

    1.5

    DC link capacitance

     

     

     

     

     

     

     

    • Active Line Module

    μF

    9670

    10500

    10500

    19330

    19330

    21000

    Pulse frequency

    kHz

    2.5

    2.5

    2.5

    2.5

    2.5

    2.5

    Power loss, at 50 Hz 690 V 2)

     

     

     

     

     

     

     

    • Dissipated to coolant

    kW

    5.45

    7.45

    8.28

    10.37

    12.98

    17.17

    • Dissipated to ambient air

    kW

    0.16

    0.2

    0.22

    0.53

    0.57

    0.79

    • Total

    kW

    5.61

    7.65

    8.5

    10.9

    13.55

    17.96

    Coolant volume flow 3)

    l/min

    16

    16

    16

    27

    27

    27

    Liquid volume

    of the integrated heat exchanger

    dm3

    0.74

    0.74

    0.74

    1.56

    1.56

    1.56

    Pressure drop, typ. 4)

    for volume flow

    Pa

    70000

    70000

    70000

    70000

    70000

    70000

    Heat exchanger material

     

    Aluminum

    Aluminum

    Aluminum

    Aluminum

    Aluminum

    Aluminum

    Sound pressure level LpA 5)

    (1 m) at 50/60 Hz

    dB

    70/73

    71/73

    71/73

    71/73

    71/73

    71/73

    Line connection

    U1, V1, W1

     

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    4 × 185

    4 × 185

    4 × 185

    Busbar

    Busbar

    Busbar

    DC link connection

    DCP, DCN

     

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    2 × hole for M12

    Busbar

    PE/GND connection

     

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    2 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    4 × 185

    4 × 185

    4 × 185

    Busbar

    Busbar

    Busbar

    Cable length, max. 6)

     

     

     

     

     

     

     

    • Shielded

    m (ft)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    • Unshielded

    m (ft)

    3375 (11073)

    3375 (11073)

    3375 (11073)

    3375 (11073)

    3375 (11073)

    3375 (11073)

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    265 (10.4)

    265 (10.4)

    265 (10.4)

    295 (11.6)

    295 (11.6)

    295 (11.6)

    • Height

    mm (in)

    1002 (39.4)

    1002 (39.4)

    1002 (39.4)

    1516 (59.7)

    1516 (59.7)

    1516 (59.7)

    • Depth

    mm (in)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    545 (21.5)

    Weight, approx.

    kg (lb)

    110 (243)

    110 (243)

    110 (243)

    220 (486)

    220 (486)

    230 (507)

    Frame size

     

    HXL

    HXL

    HXL

    JXL

    JXL

    JXL

    Minimum short-circuit current 7)

    A

    8400

    10500

    12600

    16000

    20000

    24000



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

    3) The value applies to coolants comprising water and a mixture of water and anti-freeze agent.

    4)The value is valid for water as coolant. Additional information and notes on other coolants is provided in the SINAMICS Low Voltage Engineering Manual.

    5) Total sound pressure level of Active Interface Module and Active Line Module.

    6) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    7) Current required for reliably triggering protective devices.