Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Recommended line-side power components

  • Заказные данные
    (22)
  • Информационные материалы

    Информационные материалы

    Selection and ordering data

    The fuses specified below are the recommended types for protecting the unit on the low-voltage distribution panel. If option L26 (main switch) has been selected, the inverter has integrated semiconductor protection. In this case, a fuse of type 3NA can be used on the low-voltage distribution panel.

    Further information on the fuses is provided in Catalog LV 10.

    Rated power

    SINAMICS G120P Cabinet inverter

    Fuse
    for option L26

    Fuse
    (incl. semiconductor protection) without option L26

    At 400 V/690 V,
    50 Hz

    At 460 V/575 V,
    60 Hz

     

    Rated current

    Frame size acc. to IEC 60269‑2

     

    Rated current

    Frame size acc. to IEC 60269‑2

     

    kW

    hp

    6SL3710‑ ...

    A

     

    Article No.

    A

     

    Article No.

    380 ... 480 V 3 AC

    110

    150

    1PE32-1 . A0-Z

    250

    1

    3NA3144

    315

    1

    3NE1230-2

    132

    200

    1PE32-5 . A0-Z

    315

    2

    3NA3252

    350

    2

    3NE1331-2

    160

    250

    1PE33-0 . A0-Z

    400

    2

    3NA3260

    450

    2

    3NE1333-2

    200

    300

    1PE33‑7 . A0-Z

    500

    3

    3NA3365

    500

    2

    3NE1334-2

    250

    350

    1PE34-6 . A0-Z

    630

    3

    3NA3372

    560

    3

    3NE1435-2

    315

    400

    1PE35-8 . A0-Z

    630

    3

    3NA3372

    710

    3

    3NE1437-2

    355

    450

    1PE36-6 . A0-Z

    800

    4

    3NA3475

    800

    3

    3NE1438-2

    400

    500

    1PE37-4 . A0-Z

    800

    4

    3NA3475

    850

    3

    3NE1448-2

    450

    500

    1PE38-4AA0-Z

    1000

    4

    3NA3480

    2 × 500

    2

    3NE1334-3 *)

    500

    600

    1PE38-8AA0-Z

    1000

    4

    3NA3480

    2 × 560

    3

    3NE1435-3 *)

    560

    700

    1PE41-0AA0-Z

    1250

    4

    3NA3482

    2 × 630

    3

    3NE1436-3 *)

    500 ... 690 V 3 AC

    500

    500

    1PG35-8AA0-Z

    2 x 355

    3

    3NA3354-6 *)

    710

    3

    3NE1437-2

    560

    600

    1PG36-5AA0-Z

    2 x 400

    3

    3NA3360-6 *)

    800

    3

    3NE1438-2

    630

    700

    1PG37-2AA0-Z

    2 x 425

    3

    3NA3362-6 *)

    850

    3

    3NE1448-2



    *) 2 units.

    Note:

    The power data in hp units are based on the NEC/CEC standards for the North American market.