PM230 Power Modules

  • Заказные данные
    (84)
  • Информационные материалы

    Информационные материалы

    PM230 Power Modules, degree of protection IP20, frame sizes FSA to FSF (with Control Unit and operator panel)

     

    PM230 Power Modules, degree of protection IP20, Push Through variant, frame sizes FSA to FSC (with Control Unit and operator panel)

     

    PM230 Power Modules, degree of protection IP54, frame sizes FSA to FSF (with operator panel)

    PM230 Power Modules are designed for applications involving pumps, fans and compressors with a quadratic characteristic. They do not have an integrated braking chopper (single-quadrant applications).

    The PM230 Power Module only generates low line harmonics and apparent power losses. In addition to the energy-related advantages, environmental stressing is also reduced.

    • Line harmonics are reduced significantly.
      • The limit values of EN 61000‑3‑2, EN 61000‑3‑12 or IEC 61000‑3‑4 are maintained for RSCE > 250.
        RSCE is the short-circuit power ratio Ssc line/Sinverter acc. to EN 61000‑3‑2, EN 61000‑3‑12 or EN 61000‑3‑4 and is identical to RSC acc. to IEC 60146‑1‑1 in the case of three-phase devices.
      • Additional components such as line reactors are not required and it is not permissible to use them. As a consequence, low envelope dimensions are obtained for space-saving designs.
    • The active power component is very high, i.e. the devices consume less current from the supply for the same drive power. As a consequence, smaller supply cables can be used.

    Frame sizes FSA to FSF of the PM230 Power Module in degree of protection IP55/UL Type 12 are available with integrated line filter class A for Category C2 installations in accordance with EN 61800‑3. The PM230 Power Modules with integrated filter class B that are available as an alternative also comply with the conducted interference requirements for Category C1 in accordance with EN 61800‑3.

    Frame sizes FSA to FSF of the PM230 Power Module in degree of protection IP20 are available with integrated line filter class A for Category C2 installations in accordance with EN 61800‑3, or without an integrated line filter.

    Frame sizes FSA to FSC of the PM230 Power Module in degree of protection IP20 Push Through variant are available with integrated line filter class A for Category C2 installations in accordance with EN 61800‑3, or without an integrated line filter.

    In order to maintain EMC categories C2 (line filter A) or C1 table 14 (line filter B, conducted), the permissible shielded cable length between the inverter and motor is limited to max. 25 m (82 ft).

    The permissible cable lengths between inverter and motor are limited. Longer cables can be used if output reactors are connected for PM230 (see load-side power components).

    The line system configurations that are supported are symmetrical systems with grounded neutral point.

    PM230 Power Modules do not support Control Units with Safety Integrated. Safety functions can be implemented by means of external switching devices.

    Note:

    Shield plates and shield connection kits are available. These can be used in the wiring installation for the Control Units and Power Modules to ensure that it complies with EMC guidelines.
    For further information, see Shield connection kits and Shield plates for Control Units and Power Modules in section Supplementary system components.

    Характеристика

    Derating data for PM230 Power Modules

    Pulse frequency

    Rated power 1)

    Rated output current in A

    for a pulse frequency of

    400 V

    460 V

    kW

    hp

    4 kHz

    6 kHz

    8 kHz

    10 kHz

    12 kHz

    14 kHz

    16 kHz

    0.37

    0.5

    1.3

    1.11

    0.91

    0.78

    0.65

    0.59

    0.52

    0.55

    0.5

    1.7

    1.45

    1.19

    1.02

    0.85

    0.77

    0.68

    0.75

    0.75

    2.2

    1.87

    1.54

    1.32

    1.1

    0.99

    0.88

    1.1

    1

    3.1

    2.64

    2.17

    1.86

    1.55

    1.4

    1.24

    1.5

    2

    4.1

    3.49

    2.87

    2.46

    2.05

    1.85

    1.64

    2.2

    3

    5.9

    5.02

    4.13

    3.54

    2.95

    2.66

    2.36

    3

    3

    7.7

    6.55

    5.39

    4.62

    3.85

    3.47

    3.08

    4

    5

    10.2

    8.67

    7.14

    6.12

    5.1

    4.59

    4.08

    5.5

    7.5

    13.2

    11.22

    9.24

    7.92

    6.6

    5.94

    5.28

    7.5

    10

    18

    15.3

    12.6

    10.8

    9

    8.1

    7.2

    11

    15

    26

    22.1

    18.2

    15.6

    13

    11.7

    10.4

    15

    15

    32

    27.2

    22.4

    19.2

    16

    14.4

    12.8

    18.5

    20

    38

    32.3

    26.6

    22.8

    19

    17.1

    15.2

    22

    25

    45

    38.25

    31.5

    27

    22.5

    20.25

    18

    30

    30

    60

    51

    42

    36

    30

    27

    24

    37

    40

    75

    63.75

    52.5

    45

    37.5

    33.75

    30

    45

    50

    90

    76.5

    63

    54

    45

    40.5

    36

    55

    60

    110

    93.5

    77

    66 2)

    55 2)

    49.5 2)

    44 2)

    75

    75

    145

    123.3

    101.5

    90

    100

    178

    151.3

    124.6



    1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).

    2) Values apply only to IP20 variants.

     

    Ambient temperature

    Permissible output current as a function of ambient temperature for low overload (LO) for PM230 Power Modules, frame sizes FSA to FSC

     

    Permissible output current as a function of ambient temperature for low overload (LO) for PM230 Power Modules, frame sizes FSD to FSF

     

    Permissible output current as a function of ambient temperature for high overload (HO) PM230 Power Modules, frame sizes FSA to FSC

     

    Permissible output current as a function of ambient temperature for high overload (HO) PM230 Power Modules, frame sizes FSD to FSF

    Note:

    The operating temperature ranges of the Control Units should be taken into account. The temperature ranges are specified in the section Technical specifications under Control Units.

    Installation altitude

    Permissible line supplies depending on the installation altitude

    • Installation altitude up to 2 000 m (6562 ft) above sea level
      • Connection to every supply system permitted for the inverter
    • Installation altitudes between 2 000 m (6562 ft) and 4 000 (13124 ft) m above sea level
      • Connection to a TN system with grounded neutral point
      • TN systems with grounded line conductor are not permitted
      • The TN line system with grounded neutral point can also be supplied using an isolation transformer
      • The phase-to-phase voltage does not have to be reduced

    Note:

    The connected motors, power elements and components must be considered separately.

    Permissible output current as a function of the installation altitude for PM230 Power Modules, frame sizes FSA to FSF

     

    System operating voltage

    Permissible output current as a function of the line voltage for PM230 Power Modules, frame sizes FSA to FSF

     

    Permissible rated power as a function of the line voltage for PM230 Power Modules, frame sizes FSA to FSF

    Интеграция

    PM230 Power Modules have the following connections and interfaces:

    • PM‑IF interface for connection of the PM230 Power Module and Control Unit. The PM230 Power Module also supplies power to the Control Unit using an integrated power supply.
    • Motor connection using screw terminals or screw studs
    • 2 PE/protective conductor connections

    PM230 Power Modules communicate with the Control Unit via the PM-IF interface.

    Connection diagram for PM230 Power Module with or without integrated line filter class A or B

    Power components that are optionally available depending on the Power Module used

    The following line-side and load-side power components are optionally available in the appropriate frame sizes for the Power Modules:

     

    Frame size

     

    FSA

    FSB

    FSC

    FSD

    FSE

    FSF

    PM230 Power Module (IP54/IP55)

    Available frame sizes

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    Line-side power components

    Line filter class A

    I

    I

    I

    I

    I

    I

    Line filter class B

    I

    I

    I

    I

    I

    I

    Line reactor 1)

    1)

    1)

    1)

    1)

    1)

    1)

    Load-side power components

    Output reactor

    S

    S

    S

    S

    S

    S

    Sine-wave filter

    S

    S

    S

    PM230 Power Module (IP20)

    Available frame sizes

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    Line-side power components

    Line filter class A

    F

    F

    F

    F

    F

    F

    Line filter class B

    U 2)

    U 2)

    U 2)

    S

    S

    S

    Line reactor 1)

    1)

    1)

    1)

    1)

    1)

    1)

    Load-side power components

    Output reactor

    S

    S

    S

    S

    S

    S

    Sine-wave filter

    S

    S

    S



    U = Base component

    S = Lateral mounting

    I = Integrated

    F = Power Modules available with and without integrated filter class A

    – = Not possible

    1) A line reactor is not required and must not be used in conjunction with a PM230 Power Module.

    2) Lateral mounting is the only possible option for Push Through variants.

    Maximum permissible cable lengths from the motor to the inverter when using output reactors or filters depending on the voltage range and the Power Module being used

    The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result in the following maximum cable lengths:

     

    Maximum permissible motor cable lengths (shielded/unshielded) in m (ft)

    Frame size

    FSA

    FSB

    FSC

    FSD

    FSE

    FSF

    PM230 Power Module degree of protection IP20

    Available frame sizes

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    ✓ 

    Without output reactor/sine-wave filter

    25/100 (82/328)

    25/100 (82/328)

    25/100 (82/328)

    25/100 (82/328)

    25/100 (82/328)

    25/100 (82/328)

    With optional output reactor

     

     

     

     

     

     

    • At 380 ... 415 V 3 AC

    150/225 (492/738)

    150/225 (492/738)

    150/225 (492/738)

    • At 440 ... 480 V 3 AC

    100/150 (328/492)

    100/150 (328/492)

    100/150 (328/492)

    • At 380 ... 480 V 3 AC

    200/300 (656/984)

    200/300 (656/984)

    200/300 (656/984)

    With optional sine-wave filter

     

     

     

     

     

     

    • At 380 ... 480 V 3 AC

    200/300 (656/984)

    200/300 (656/984)

    200/300 (656/984)

    With integrated line filter class A
    (EMC category C3)

     

     

     

     

     

     

    • At 380 ... 480 V 3 AC

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    With optional external line filter class B (EMC category C1 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800‑3)

     

     

     

     

     

     

    • At 380 ... 480 V 3 AC

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    50/- (164/-)

    With optional external line filter class B and output reactor (EMC category C1 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800‑3)

     

     

     

     

     

     

    • At 380 ... 415 V 3 AC

    150/- (492/-)

    150/- (492/-)

    150/- (492/-)

    • At 440 ... 480 V 3 AC

    100/- (328/-)

    100/- (328/-)

    100/- (328/-)



    1) Further information is available on the Internet at http://www.siemens.com/sinamics-g120/documentation

    Чертеж

    PM230 Power Modules, degree of protection IP55/UL Type 12

    Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP55/UL Type 12 with integrated line filter class A/B

    Frame size

    Dimensions

    in mm (inches)

    Drilling dimensions

    in mm (inches)

    Cooling clearance

    in mm (inches)

    Mounting

     

    a
    (width)

    b
    (height)

    c
    (depth) 1)

    d

    e

    f

    top

    bottom

    side

    With bolts, nuts and washers

    PM230 Power Modules, degree of protection IP55/UL Type 12 with integrated line filter class A/B

    FSA

    154
    (6.06)

    460
    (18.11)

    249
    (9.8)

    132
    (5.19)

    445
    (17.51)

    11
    (0.43)

    100
    (3.94)

    0
    (0)

    0
    (0)

    4 × M4

    FSB

    180
    (7.08)

    540
    (21.25)

    249
    (9.8)

    158
    (5.9)

    524
    (20.62)

    11
    (0.43)

    100
    (3.94)

    0
    (0)

    0
    (0)

    4 × M4

    FSC

    230
    (9.05)

    620
    (24.4)

    249
    (9.8)

    208
    (8.18)

    604
    (23.77)

    11
    (0.43)

    125
    (4.92)

    0
    (0)

    0
    (0)

    4 × M5

    FSD

    320
    (12.59)

    640
    (25.19)

    329
    (12.95)

    285
    (11.22)

    600
    (23.62)

    17.5
    (0.69)

    300
    (11.81)

    0
    (0)

    50
    (1.97) 2)

    4 × M8

    FSE

    320
    (12.59)

    751
    (29.56)

    329
    (12.95)

    285
    (11.22)

    710
    (27.95)

    17.5
    (0.69)

    300
    (11.81)

    0
    (0)

    50
    (1.97) 2)

    4 × M8

    FSF

    410
    (16.14)

    915
    (36.02)

    416
    (16.38)

    370
    (14.56)

    870
    (34.25)

    20
    (0.79)

    350
    (13.78)

    0
    (0)

    50
    (1.97) 2)

    4 × M8



    1) Increased depth:

    • When the IOP is plugged on, the depth increases by 17 mm (0.67 in)

    • When the BOP‑2/blanking cover is plugged on, the depth increases by 7 mm (0.28 in)

    2) Up to 40 °C (104 °F) without any lateral clearance.

     

    PM230 Power Modules, degree of protection IP20, Standard variant

    Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, Standard variant, with/without integrated line filter class A

    Frame size

    Dimensions

    in mm (inches)

    Drilling dimensions

    in mm (inches)

    Cooling clearance

    in mm (inches)

    Mounting

     

    a
    (width)

    b
    (height)

    c
    (depth) 1)

    d

    e

    f

    top

    bottom

    side 2)

    With bolts

    PM230 Power Modules, degree of protection IP20, Standard variant, with/without integrated line filter class A

    FSA

    73
    (2.87)

    196
    (7.72)

    165
    (6.5)

    62.3
    (2.45)

    186
    (7.32)

    6
    (0.24)

    80
    (3.15)

    100
    (3.94)

    0
    (0)

    3 × M4

    FSB

    100
    (3.94)

    292
    (11.5)

    165
    (6.5)

    80
    (3.15)

    281
    (11.06)

    6
    (0.24)

    80
    (3.15)

    100
    (3.94)

    0
    (0)

    4 × M4

    FSC

    140
    (5.51)

    355
    (13.98)

    165
    (6.5)

    120
    (4.72)

    343
    (13.5)

    6
    (0.24)

    80
    (3.15)

    100
    (3.94)

    0
    (0)

    4 × M5

    FSD

    275
    (10.83)

    419/512
    (16.50/20.16)

    204
    (8.03)

    235
    (9.25)

    325/419
    (12.8/16.5)

    11
    (0.43)

    300
    (11.81)

    300
    (11.81)

    0
    (0)

    4 × M6

    FSE

    275
    (10.83)

    499/635
    (19.65/25)

    204
    (8.03)

    235
    (9.25)

    405/541
    (15.94/21.3)

    11
    (0.43)

    300
    (11.81)

    300
    (11.81)

    0
    (0)

    4 × M6

    FSF

    350
    (13.78)

    634/934
    (24.96/36.77)

    316
    (12.44)

    300
    (11.81)

    598/899
    (23.54/35.39)

    11
    (0.43)

    350
    (13.78)

    350
    (13.78)

    0
    (0)

    4 × M8



    1) Increased depth:

    • When the CU230P-2 Control Unit is plugged on, the depth increases by 58 mm (2.28 in) for FSA to FSC and by 49 mm (1.93 in) for FSD to FSF

    • When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)

    • When the BOP‑2 is plugged on, the depth increases by a further 12 mm (0.47 in)

    2)The Power Modules can be mounted side by side. A side clearance of 1 mm (0.04 in) is recommended for tolerance-related reasons.

     

    PM230 Power Modules, degree of protection IP20, Push Through variant

    Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, Push Through variant, with/without integrated line filter class A

    Frame size

    Dimensions

    in mm (inches)

    Drilling dimensions

    in mm (inches)

    Section of cabinet

    in mm (inches)

    Cooling clearance

    in mm (inches)

    Mounting

     

    a
    (width)

    b
    (height)

    c
    (depth) 1)

    d

    e

    f

    g
    (width)

    h
    (height)

    top

    bottom

    side 2)

    With bolts

    PM230 Power Modules, degree of protection IP20, Push Through variant, with/without integrated line filter class A

    FSA

    125.9
    (4.96)

    238
    (9.37)

    171
    (6.73)

    106
    (4.17)

    103
    (4.06)

    27
    (1.06)

    88
    (3.46)

    198
    (7.8)

    80
    (3.15)

    100
    (3.94)

    0
    (0)

    M5

    FSB

    153.9
    (6.06)

    345
    (13.58)

    171
    (6.73)

    134
    (5.28)

    147.5
    (5.81)

    34.5
    (1.36)

    116
    (4.57)

    304
    (11.97)

    80
    (3.15)

    100
    (3.94)

    0
    (0)

    M5

    FSC

    200
    (7.87)

    410.5
    (16.16)

    171
    (6.73)

    174
    (6.85)

    123
    (4.84)

    30.5
    (1.2)

    156
    (6.14)

    365
    (14.37)

    80
    (3.15)

    100
    (3.94)

    0
    (0)

    M5



    1) Overall depth, of which 117.7 mm (4.63 in) is inside and 53.1 mm (2.09 in) is outside the control cabinet.

    Increased depth:

    • When the CU230P‑2 Control Unit is plugged on, the depth increases by 58 mm (2.28 in)

    • When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)

    • When the BOP‑2 is plugged on, the depth increases by a further 12 mm (0.47 in)

    2)The Power Modules can be mounted side by side (mounting frame to mounting frame). A side clearance of 1 mm (0.04 in) is recommended for tolerance-related reasons.

    Технические данные

    General technical specifications

     

    PM230 Power Modules

    Degree of protection

    IP55/UL Type 12 (with BOP-2 or blanking cover)
    IP54/UL Type 12 with IOP

    IP20/UL Open Type
    (Standard or Push Through variants)

    Power (low overload LO)

    0.37 ... 90 kW

    0.37 ... 75 kW

    Rated output current (low overload LO)

    1.3 ... 178 A

    1.3 ... 145 A

    Power (high overload HO)

    0.25 ... 75 kW

    0.25 ... 55 kW

    Rated output current (high overload HO)

    0.9 ... 145 A

    0.9 ... 110 A

    System operating voltage

    380 ... 480 V ±10 % 3 AC

    Grid requirement
    Short-circuit power RSC

    >100

    Input frequency

    47 ... 63 Hz

    Output frequency

     

    • Control mode V/f

    0 ... 550 Hz

    • Control type Vector

    0 ... 240 Hz

    Pulse frequency

    4 kHz
    for higher pulse frequencies up to 16 kHz, see derating data

    Power factor λ

    0.9

    Output voltage, max.

    as % of input voltage

    95%

    Overload capability

     

    • Low overload (LO)

    Note: When the overload capability is used, the base-load current IL is not reduced.

    • Frame sizes FSA to FSC

    1.5 × base-load current IL (i. e. 150 % overload) for 3 s plus
    1.1 × base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s

    • Frame sizes FSD to FSF

    1.1 × base-load current IL (i. e. 110 % overload) for 60 s within a cycle time of 300 s

    • High overload (HO)

    Note: When the overload capability is used, the base-load current IH is not reduced.

    • Frame sizes FSA to FSC

    2 × base-load current IH (i. e. 200 % overload) for 3 s plus
    1.5 × base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s

    • Frame sizes FSD to FSF

    1.5 × base-load current IH (i. e. 150 % overload) for 60 s within a cycle time of 300 s

    Electromagnetic compatibility

    • Devices with line filter class A for applications according to Categories C3 and C2
    • Devices with line filter class B for applications according to Category C2 and compliance with conducted interference requirements of Category C1
    • Devices without line filter
    • Devices with line filter class A for applications according to Categories C3 and C2
    • Devices with line filter class B for applications according to Category C2 and compliance with conducted interference requirements of Category C1

    Possible braking methods

    DC braking

    Operating temperature

     

    • Low overload (LO)

    Frame sizes FSA to FSC: -10 ... +40 °C (14 ... 104 °F) without derating
    Frame sizes FSD to FSF: 0 ... 40 °C (32 ... 104 °F) without derating

    >40 ... 60 °C (104 ... 140 °F) see derating characteristics

    • High overload (HO)

    Frame sizes FSA to FSC: -10 ... +50 °C (14 ... 122 °F) without derating
    Frame sizes FSD to FSF: 0 ... 50 °C (32 ... 122 °F) without derating

    >50 ... 60 ℃ (122 ... 140 °F) see derating characteristics

    Storage temperature

    -40 ... +70 °C (-40 ... +158 °F)

    Relative humidity

    <95 %, condensation not permissible

    Cooling

    Power units with increased air cooling using integrated fans

    Installation altitude

    Up to 1000 m (3281 ft) above sea level without derating,
    > 1000 m (3281 ft) see derating characteristics

    Protection functions

    • Undervoltage
    • Overvoltage
    • Overcurrent/overload
    • Overtemperature
    • Ground fault
    • Short-circuit
    • Stall protection
    • Motor blocking protection
    • Motor overtemperature
    • Inverter overtemperature
    • Parameter locking

    Compliance with standards

    UL 1), cUL 2), CE, RCM, SEMI F47

    Rated short-circuit current SCCR (Short Circuit Current Rating) 3)

    Frame sizes FSA to FSC: 40 kA
    Frame sizes FSD to FSF: 65 kA

    65 kA

    CE marking

    According to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU



    1) For degree of protection IP55/UL Type 12, the UL approval only applies to frame sizes FSA to FSC.

    2) Applies to PM230 Power Modules, frame sizes FSA to FSC.

    3) Applies to industrial control panel installations acc. to NEC Article 409 or UL 508A/508C.

     

    PM230 Power Modules degree of protection IP55/UL Type 12

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules, degree of protection IP55/UL Type 12

    With integrated line filter class A

    6SL3223-0DE13-7AA1

    6SL3223-0DE15-5AA1

    6SL3223-0DE17-5AA1

    6SL3223-0DE21-1AA1

    6SL3223-0DE21-5AA1

    With integrated line filter class B

    6SL3223-0DE13-7BA1

    6SL3223-0DE15-5BA1

    6SL3223-0DE17-5BA1

    6SL3223-0DE21-1BA1

    6SL3223-0DE21-5BA1

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

    • Rated current Irated1)

    A

    1.3

    1.7

    2.2

    3.1

    4.1

    • Base-load current IL1)

    A

    1.3

    1.7

    2.2

    3.1

    4.1

    • Base-load current IH2)

    A

    0.9

    1.3

    1.7

    2.2

    3.1

    • Maximum current Imax

    A

    2

    2.6

    3.4

    4.7

    6.2

    Rated power

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    0.37 (0.5)

    0.55 (0.75)

    0.75 (1)

    1.1 (1.5)

    1.5 (2)

    • Based on IH

    kW (hp)

    0.25 (0.34)

    0.37 (0.5)

    0.55 (0.75)

    0.75 (1)

    1.1 (1.5)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    Efficiency η

     

    0.86

    0.9

    0.92

    0.94

    0.95

    Power loss 3)

    at rated current

    kW

    0.04

    0.043

    0.047

    0.055

    0.064

    Cooling air requirement

    m3/s (ft3/s)

    0.007 (0.2)

    0.007 (0.2)

    0.007 (0.2)

    0.007 (0.2)

    0.007 (0.2)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    61.9

    61.9

    61.9

    61.9

    61.9

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

    • Rated current

    A

    1.3

    1.8

    2.3

    3.2

    4.2

    • Based on IH

    A

    0.9

    1.3

    1.8

    2.3

    3.2

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    Motor cable length, max. 5)

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection 6)

     

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    154 (6.06)

    154 (6.06)

    154 (6.06)

    154 (6.06)

    154 (6.06)

    • Height

    mm (in)

    460 (18.11)

    460 (18.11)

    460 (18.1)

    460 (18.11)

    460 (18.1)

    • Depth

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    • With operator panel, max.

    mm (in)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    Frame size

     

    FSA

    FSA

    FSA

    FSA

    FSA

    Weight, approx.

    kg (lb)

    4.3 (9.48)

    4.3 (9.48)

    4.3 (9.48)

    4.3 (9.48)

    4.3 (9.48)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

    6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

     

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules, degree of protection IP55/UL Type 12

    With integrated line filter class A

    6SL3223-0DE22-2AA1

    6SL3223-0DE23-0AA1

    6SL3223-0DE24-0AA1

    6SL3223-0DE25-5AA1

    6SL3223-0DE27-5AA1

    With integrated line filter class B

    6SL3223-0DE22-2BA1

    6SL3223-0DE23-0BA1

    6SL3223-0DE24-0BA1

    6SL3223-0DE25-5BA1

    6SL3223-0DE27-5BA1

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

    • Rated current Irated1)

    A

    5.9

    7.7

    10.2

    13.2

    18

    • Base-load current IL1)

    A

    5.9

    7.7

    10.2

    13.2

    18

    • Base-load current IH2)

    A

    4.1

    5.9

    7.7

    10.2

    13.2

    • Maximum current Imax

    A

    8.9

    11.8

    15.4

    20.4

    27

    Rated power

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    2.2 (3)

    3 (4.02)

    4 (5)

    5.5 (7.38)

    7.5 (16.5)

    • Based on IH

    kW (hp)

    1.5 (2)

    2.2 (3)

    3 (4.02)

    4 (5)

    5.5 (7.38)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    Efficiency η

     

    0.96

    0.96

    0.97

    0.97

    0.97

    Power loss 3)

    at rated current

    kW

    0.086

    0.11

    0.137

    0.173

    0.235

    Cooling air requirement

    m3/s (ft3/s)

    0.007 (0.2)

    0.007 (0.2)

    0.009 (0.3)

    0.009 (0.3)

    0.009 (0.3)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    61.9

    61.9

    62.8

    62.8

    62.8

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

    • Rated current

    A

    6.1

    8

    11

    14

    19

    • Based on IH

    A

    4.2

    6.1

    8

    11

    14

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    1 ... 2.5

    2.5 ... 6

    4 ... 6

    4 ... 6

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    1 ... 2.5

    2.5 ... 6

    4 ... 6

    4 ... 6

    Motor cable length, max. 5)

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection 6)

     

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    154 (6.06)

    154 (6.06)

    180 (7.09)

    180 (7.09)

    180 (7.09)

    • Height

    mm (in)

    460 (18.11)

    460 (18.11)

    540 (21.26)

    540 (21.26)

    540 (21.26)

    • Depth

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    • With operator panel, max.

    mm (in)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    Frame size

     

    FSA

    FSA

    FSB

    FSB

    FSB

    Weight, approx.

    kg (lb)

    4.3 (9.48)

    4.3 (9.48)

    6.3 (14)

    6.3 (14)

    6.3 (14)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

    6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

     

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules, degree of protection IP55/UL Type 12

    With integrated line filter class A

    6SL3223-0DE31-1AA1

    6SL3223-0DE31-5AA1

    6SL3223-0DE31-8AA1

    6SL3223-0DE32-2AA0

    6SL3223-0DE33-0AA0

    With integrated line filter class B

    6SL3223-0DE31-1BA1

    6SL3223-0DE31-5BA1

    6SL3223-0DE31-8BA0

    6SL3223-0DE32-2BA0

    6SL3223-0DE33-0BA0

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

     

    • Rated current Irated1)

    A

    26

    32

    38

    38

    45

    60

    • Base-load current IL1)

    A

    26

    32

    38

    38

    45

    60

    • Base-load current IH2)

    A

    18

    26

    32

    32

    38

    45

    • Maximum current Imax

    A

    39

    52

    64

    48

    57

    67

    Rated power

     

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    11 (24.26)

    15 (20.12)

    18.5 (24.81)

    18.5 (24.81)

    22 (29.50)

    30 (40.23)

    • Based on IH

    kW (hp)

    7.5 (16.5)

    11 (24.26)

    15 (20.12)

    15 (20.12)

    18.5 (24.81)

    22 (29.50)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    4

    Efficiency η

     

    0.97

    0.97

    0.98

    0.97

    0.97

    0.97

    Power loss 3)

    at rated current

    kW

    0.299

    0.365

    0.435

    0.478

    0.569

    0.784

    Cooling air requirement

    m3/s (ft3/s)

    0.02 (0.7)

    0.02 (0.7)

    0.02 (0.7)

    0.039 (1.4)

    0.039 (1.4)

    0.039 (1.4)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    66.1

    66.1

    66.1

    56

    56

    56

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

     

    • Rated current

    A

    27

    33

    39

    39

    42

    56

    • Based on IH

    A

    19

    27

    33

    33

    36

    42

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    M6 screw studs

    M6 screw studs

    M6 screw studs

    • Conductor cross-section

    mm2

    6 ... 16

    10 ... 16

    10 ... 16

    16 ... 35

    16 ... 35

    16 ... 35

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    M6 screw studs

    M6 screw studs

    M6 screw studs

    • Conductor cross-section

    mm2

    6 ... 16

    10 ... 16

    10 ... 16

    16 ... 35

    16 ... 35

    16 ... 35

    Motor cable length, max. 5)

     

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection 6)

     

    IP55/UL Type 12

    IP55/UL Type 12

    IP55/UL Type 12

    IP55

    IP55

    IP55

    Dimensions

     

     

     

     

     

     

     

    • Width

    mm (in)

    230 (9.06)

    230 (9.06)

    230 (9.06)

    320 (12.60)

    320 (12.60)

    320 (12.60)

    • Height

    mm (in)

    620 (24.41)

    620 (24.41)

    620 (24.41)

    640 (25.20)

    640 (25.20)

    640 (25.20)

    • Depth

     

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    249 (9.80)

    249 (9.80)

    249 (9.80)

    329 (12.95)

    329 (12.95)

    329 (12.95)

    • With operator panel, max.

    mm (in)

    266 (10.47)

    266 (10.47)

    266 (10.47)

    346 (13.62)

    346 (13.62)

    346 (13.62)

    Frame size

     

    FSC

    FSC

    FSC

    FSD

    FSD

    FSD

    Weight, approx.

    kg (lb)

    9.5 (20.95)

    9.5 (20.95)

    9.5 (20.95)

    31 (68.36)

    31 (68.36)

    31 (68.36)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

    6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

     

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules, degree of protection IP55/UL Type 12

    With integrated line filter class A

    6SL3223-0DE33-7AA0

    6SL3223-0DE34-5AA0

    6SL3223-0DE35-5AA0

    6SL3223-0DE37-5AA0

    6SL3223-0DE38-8AA0

    With integrated line filter class B

    6SL3223-0DE33-7BA0

    6SL3223-0DE34-5BA0

    6SL3223-0DE35-5BA0

    6SL3223-0DE37-5BA0

    6SL3223-0DE38-8BA0

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

    • Rated current Irated1)

    A

    75

    90

    110

    145

    178

    • Base-load current IL1)

    A

    75

    90

    110

    145

    178

    • Base-load current IH2)

    A

    60

    75

    90

    110

    145

    • Maximum current Imax

    A

    90

    112

    135

    165

    217

    Rated power

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    37 (49.62)

    45 (60.35)

    55 (73.76)

    75 (100.58)

    90 (120.69)

    • Based on IH

    kW (hp)

    30 (40.23)

    37 (81.59)

    45 (99.23)

    55 (73.76)

    75 (165.38)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    Efficiency η

     

    0.97

    0.97

    0.97

    0.97

    0.97

    Power loss 3)

    at rated current

    kW

    0.855

    1.073

    1.122

    1.542

    1.98

    Cooling air requirement

    m3/s (ft3/s)

    0.039 (1.4)

    0.039 (1.4)

    0.117 (4.1)

    0.117 (4.1)

    0.117 (4.1)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    56

    56

    61

    61

    61

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

    • Rated current

    A

    70

    84

    102

    135

    166

    • Based on IH

    A

    56

    70

    84

    102

    135

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    M6 screw studs

    M6 screw studs

    M8 screw studs

    M8 screw studs

    M8 screw studs

    • Conductor cross-section

    mm2

    25 ... 50

    25 ... 50

    35 ... 120

    35 ... 120

    35 ... 120

    Motor connection

    U2, V2, W2

     

    M6 screw studs

    M6 screw studs

    M8 screw studs

    M8 screw studs

    M8 screw studs

    • Conductor cross-section

    mm2

    25 ... 50

    25 ... 50

    35 ... 120

    35 ... 120

    35 ... 120

    Motor cable length, max. 5)

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection 6)

     

    IP55

    IP55

    IP55

    IP55

    IP55

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    320 (12.60)

    320 (12.60)

    410 (16.14)

    410 (16.14)

    410 (16.14)

    • Height

    mm (in)

    751 (29.57)

    751 (29.57)

    915 (36.02)

    915 (36.02)

    915 (36.02)

    • Depth

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    329 (12.95)

    329 (12.95)

    416 (16.38)

    416 (16.38)

    416 (16.38)

    • With operator panel, max.

    mm (in)

    346 (13.62)

    346 (13.62)

    433 (17.05)

    433 (17.05)

    433 (17.05)

    Frame size

     

    FSE

    FSE

    FSF

    FSF

    FSF

    Weight, approx.

    kg (lb)

    37 (with filter cl. A)
    38 (with filter cl. B)

    37 (with filter cl. A)
    38 (with filter cl. B)

    70

    70

    70



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

    6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

     

    PM230 Power Modules degree of protection IP20 standard variant

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules degree of protection IP20 standard variant

    Without integrated line filter

    6SL3210-1NE11-3UL1

    6SL3210-1NE11-7UL1

    6SL3210-1NE12-2UL1

    6SL3210-1NE13-1UL1

    6SL3210-1NE14-1UL1

    With integrated line filter class A

    6SL3210-1NE11-3AL1

    6SL3210-1NE11-7AL1

    6SL3210-1NE12-2AL1

    6SL3210-1NE13-1AL1

    6SL3210-1NE14-1AL1

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

    • Rated current Irated1)

    A

    1.3

    1.7

    2.2

    3.1

    4.1

    • Base-load current IL1)

    A

    1.3

    1.7

    2.2

    3.1

    4.1

    • Base-load current IH2)

    A

    0.9

    1.3

    1.7

    2.2

    3.1

    • Maximum current Imax

    A

    2

    2.6

    3.4

    4.7

    6.2

    Rated power

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    0.37 (0.5)

    0.55 (0.75)

    0.75 (1)

    1.1 (1.5)

    1.5 (2)

    • Based on IH

    kW (hp)

    0.25 (0.34)

    0.37 (0.5)

    0.55 (0.75)

    0.75 (1)

    1.1 (1.5)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    Efficiency η

     

    0.89

    0.93

    0.93

    0.94

    0.95

    Power loss 3)

    at rated current

    kW

    0.031

    0.034

    0.041

    0.049

    0.06

    Cooling air requirement

    m3/s (ft3/s)

    0.002 (0.1)

    0.002 (0.1)

    0.005 (0.2)

    0.005 (0.2)

    0.005 (0.2)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    <50

    <50

    <50

    <50

    <50

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

    • Rated current

    A

    1.3

    1.8

    2.3

    3.2

    4.2

    • Based on IH

    A

    0.9

    1.3

    1.8

    2.3

    3.2

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    1 ... 2.5

    Motor cable length, max. 5)

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    73 (2.87)

    73 (2.87)

    73 (2.87)

    73 (2.87)

    73 (2.87)

    • Height

    mm (in)

    196 (7.72)

    196 (7.72)

    196 (7.72)

    196 (7.72)

    196 (7.72)

    • Depth

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    • With operator panel, max.

    mm (in)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    Frame size

     

    FSA

    FSA

    FSA

    FSA

    FSA

    Weight, approx.

     

     

     

     

     

     

    • Without integrated line filter

    kg (lb)

    1.4 (3.09)

    1.4 (3.09)

    1.4 (3.09)

    1.4 (3.09)

    1.4 (3.09)

    • With integrated line filter

    kg (lb)

    1.6 (3.53)

    1.6 (3.53)

    1.6 (3.53)

    1.6 (3.53)

    1.6 (3.53)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

     

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules degree of protection IP20 standard variant

    Without integrated line filter

    6SL3210-1NE15-8UL1

    6SL3210-1NE17-7UL1

    6SL3210-1NE21-0UL1

    6SL3210-1NE21-3UL1

    6SL3210-1NE21-8UL1

    With integrated line filter class A

    6SL3210-1NE15-8AL1

    6SL3210-1NE17-7AL1

    6SL3210-1NE21-0AL1

    6SL3210-1NE21-3AL1

    6SL3210-1NE21-8AL1

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

    • Rated current Irated1)

    A

    5.9

    7.7

    10.2

    13.2

    18

    • Base-load current IL1)

    A

    5.9

    7.7

    10.2

    13.2

    18

    • Base-load current IH2)

    A

    4.1

    5.9

    7.7

    10.2

    13.2

    • Maximum current Imax

    A

    8.9

    11.8

    15.4

    20.4

    27

    Rated power

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    2.2 (3)

    3 (4.02)

    4 (5)

    5.5 (7.38)

    7.5 (16.5)

    • Based on IH

    kW (hp)

    1.5 (2)

    2.2 (3)

    3 (4.02)

    4 (5)

    5.5 (7.38)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    Efficiency η

     

    0.96

    0.96

    0.97

    0.97

    0.97

    Power loss 3)

    at rated current

    kW

    0.078

    0.102

    0.13

    0.165

    0.224

    Cooling air requirement

    m3/s (ft3/s)

    0.005 (0.2)

    0.005 (0.2)

    0.009 (0.3)

    0.009 (0.3)

    0.009 (0.3)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    <50

    <50

    <62

    <62

    <62

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

    • Rated current

    A

    6.1

    8

    11

    14

    19

    • Based on IH

    A

    4.2

    6.1

    8

    11

    14

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1.5 ... 2.5

    1.5 ... 2.5

    1.5 ... 6

    1.5 ... 6

    1.5 ... 6

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1.5 ... 2.5

    1.5 ... 2.5

    1.5 ... 6

    1.5 ... 6

    1.5 ... 6

    Motor cable length, max. 5)

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    73 (2.87)

    73 (2.87)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    • Height

    mm (in)

    196 (7.72)

    196 (7.72)

    292 (11.50)

    292 (11.50)

    292 (11.50)

    • Depth

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    • With operator panel, max.

    mm (in)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    Frame size

     

    FSA

    FSA

    FSB

    FSB

    FSB

    Weight, approx.

     

     

     

     

     

     

    • Without integrated line filter

    kg (lb)

    1.4 (3.09)

    1.4 (3.09)

    2.8 (6.17)

    2.8 (6.17)

    2.8 (6.17)

    • With integrated line filter

    kg (lb)

    1.6 (3.53)

    1.6 (3.53)

    3 (4.02)

    3 (4.02)

    3 (4.02)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

     

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules degree of protection IP20 standard variant

    Without integrated line filter

    6SL3210-
    1NE22-6UL1

    6SL3210-
    1NE23-2UL1

    6SL3210-
    1NE23-8UL1

    6SL3210-
    1NE24-5UL0

    6SL3210-
    1NE26-0UL0

    With integrated line filter class A

    6SL3210-
    1NE22-6AL1

    6SL3210-
    1NE23-2AL1

    6SL3210-
    1NE23-8AL1

    6SL3210-
    1NE24-5AL0

    6SL3210-
    1NE26-0AL0

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

     

    • Rated current Irated1)

    A

    26

    32

    38

    45

    60

    • Base-load current IL1)

    A

    26

    32

    38

    45

    60

    • Base-load current IH2)

    A

    18

    26

    32

    38

    45

    • Maximum current Imax

    A

    39

    52

    64

    57

    67

    Rated power

     

     

     

     

     

     

    • Based on IL

    kW (hp)

    11 (14.8)

    15 (20.1)

    18.5 (24.8)

    22 (29.5)

    30 (40.2)

    • Based on IH

    kW (hp)

    7.5 (10.1)

    11 (14.8)

    15 (20.1)

    18.5 (24.8)

    22 (29.5)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    4

    Efficiency η

     

    0.97

    0.97

    0.98

    0.98

    0.97

    Power loss 3)

    at rated current

    kW

    0.291

    0.355

    0.423

    0.539

    0.726

    Cooling air requirement

    m3/s (ft3/s)

    0.019 (0.7)

    0.019 (0.7)

    0.019 (0.7)

    0.08 (2.8)

    0.08 (2.8)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    <65

    <65

    <65

    <60

    <60

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

     

    • Rated current

    A

    27

    33

    39

    42

    56

    • Based on IH

    A

    19

    27

    33

    36

    42

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    M6 screw studs

    M6 screw studs

    • Conductor cross-section

    mm2

    6 ... 16

    6 ... 16

    6 ... 16

    16 ... 35

    16 ... 35

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    M6 screw studs

    M6 screw studs

    • Conductor cross-section

    mm2

    6 ... 16

    6 ... 16

    6 ... 16

    16 ... 35

    16 ... 35

    Motor cable length, max. 5)

     

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    140 (5.51)

    140 (5.51)

    140 (5.51)

    275 (10.83)

    275 (10.83)

    • Height

     

     

     

     

     

     

    • Without integrated line filter

    mm (in)

    355 (13.98)

    355 (13.98)

    355 (13.98)

    419 (16.50)

    419 (16.50)

    • With integrated line filter

    mm (in)

    355 (13.98)

    355 (13.98)

    355 (13.98)

    512 (20.16)

    512 (20.16)

    • Depth

     

     

     

     

     

     

    • Without operator panel

    mm (in)

    165 (6.50)

    165 (6.50)

    165 (6.50)

    204 (8.03)

    204 (8.03)

    • With operator panel, max.

    mm (in)

    245 (9.65)

    245 (9.65)

    245 (9.65)

    275 (10.83)

    275 (10.83)

    Frame size

     

    FSC

    FSC

    FSC

    FSD

    FSD

    Weight, approx.

     

     

     

     

     

     

    • Without integrated line filter

    kg (lb)

    4.5 (9.92)

    4.5 (9.92)

    4.5 (9.92)

    11 (24.26)

    11 (24.26)

    • With integrated line filter

    kg (lb)

    5.1 (11.25)

    5.1 (11.25)

    5.1 (11.25)

    14 (30.87)

    14 (30.87)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

     

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules degree of protection IP20 standard variant

    Without integrated line filter

    6SL3210-1NE27-5UL0

    6SL3210-1NE28-8UL0

    6SL3210-1NE31-1UL0

    6SL3210-1NE31-5UL0

    With integrated line filter class A

    6SL3210-1NE27-5AL0

    6SL3210-1NE28-8AL0

    6SL3210-1NE31-1AL0

    6SL3210-1NE31-5AL0

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

     

    • Rated current Irated1)

    A

    75

    90

    110

    145

    • Base-load current IL1)

    A

    75

    90

    110

    145

    • Base-load current IH2)

    A

    60

    75

    90

    110

    • Maximum current Imax

    A

    90

    112

    135

    165

    Rated power

     

     

     

     

     

    • Based on IL

    kW (hp)

    37 (49.6)

    45 (60.3)

    55 (73.8)

    75 (101)

    • Based on IH

    kW (hp)

    30 (40.23)

    37 (49.62)

    45 (60.35)

    55 (73.8)

    Rated pulse frequency

    kHz

    4

    4

    4

    4

    Efficiency η

     

    0.97

    0.97

    0.97

    0.97

    Power loss 3)

    at rated current

    kW

    0.791

    0.976

    1.237

    1.69

    Cooling air requirement

    m3/s (ft3/s)

    0.08 (2.8)

    0.08 (2.8)

    0.15 (5.3)

    0.15 (5.3)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    <60

    <60

    <60

    <60

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    1

    Input current 4)

     

     

     

     

     

    • Rated current

    A

    70

    84

    102

    135

    • Based on IH

    A

    56

    70

    84

    102

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    M6 screw studs

    M6 screw studs

    M8 screw studs

    M8 screw studs

    • Conductor cross-section

    mm2

    25 ... 50

    25 ... 50

    35 ... 120

    35 ... 120

    Motor connection

    U2, V2, W2

     

    M6 screw studs

    M6 screw studs

    M8 screw studs

    M8 screw studs

    • Conductor cross-section

    mm2

    25 ... 50

    25 ... 50

    35 ... 120

    35 ... 120

    Motor cable length, max. 5)

     

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    275 (10.83)

    275 (10.83)

    350 (13.78)

    350 (13.78)

    • Height

     

     

     

     

     

    • Without integrated line filter

    mm (in)

    499 (19.65)

    499 (19.65)

    634 (24.96)

    634 (24.96)

    • With integrated line filter

    mm (in)

    635 (25)

    635 (25)

    934 (36.77)

    934 (36.77)

    • Depth

     

     

     

     

     

    • Without operator panel

    mm (in)

    204 (8.03)

    204 (8.03)

    316 (12.44)

    316 (12.44)

    • With operator panel, max.

    mm (in)

    275 (10.83)

    275 (10.83)

    387 (15.24)

    387 (15.24)

    Frame size

     

    FSE

    FSE

    FSF

    FSF

    Weight, approx.

     

     

     

     

     

    • Without integrated line filter

    kg (lb)

    15 (20.12)

    15 (20.12)

    34 (74.97)

    34 (74.97)

    • With integrated line filter

    kg (lb)

    22 (29.50)

    22 (29.50)

    46 (101.43)

    46 (101.43)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.

     

    PM230 Power Modules degree of protection IP20 push-through variant

    Line voltage 380 ... 480 V 3 AC

    PM230 Power Modules degree of protection IP20 push-through variant

    Without integrated line filter

    6SL3211-1NE17-7UL1

    6SL3211-1NE21-8UL1

    6SL3211-1NE23-8UL1

    With integrated line filter class A

    6SL3211-1NE17-7AL1

    6SL3211-1NE21-8AL1

    6SL3211-1NE23-8AL1

    Output current

    at 50 Hz 400 V 3 AC

     

     

     

     

    • Rated current Irated1)

    A

    7.7

    18

    38

    • Base-load current IL1)

    A

    7.7

    18

    38

    • Base-load current IH2)

    A

    5.9

    13.2

    32

    • Maximum current Imax

    A

    11.8

    27

    64

    Rated power

     

     

     

     

    • Based on IL

    kW (hp)

    3 (4.02)

    7.5 (10.1)

    18.5 (24.8)

    • Based on IH

    kW (hp)

    2.2 (2.95)

    5.5 (7.38)

    15 (20.12)

    Rated pulse frequency

    kHz

    4

    4

    4

    Efficiency η

     

    0.96

    0.97

    0.98

    Power loss 3)

    at rated current

    kW

    0.102

    0.224

    0.423

    Cooling air requirement

    m3/s (ft3/s)

    0.005 (0.2)

    0.009 (0.3)

    0.019 (0.7)

    Sound pressure level

    LpA (1 m/3.28 ft)

    dB

    <56

    <62

    <65

    24 V DC power supply

    for Control Unit

    A

    1

    1

    1

    Input current 4)

     

     

     

     

    • Rated current

    A

    8

    19

    39

    • Based on IH

    A

    6.1

    14

    33

    Line supply connection

    U1/L1, V1/L2, W1/L3

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1.5 ... 2.5

    4 ... 6

    6 ... 16

    Motor connection

    U2, V2, W2

     

    Screw terminals, plug-in

    Screw terminals, plug-in

    Screw terminals, plug-in

    • Conductor cross-section

    mm2

    1 ... 2.5

    4 ... 6

    10 ... 16

    Motor cable length, max. 5)

     

     

     

     

    • Shielded

    m (ft)

    25 (82.03)

    25 (82.03)

    25 (82.03)

    • Unshielded

    m (ft)

    100 (328.10)

    100 (328.10)

    100 (328.10)

    Degree of protection

     

    IP20

    IP20

    IP20

    Dimensions

     

     

     

     

    • Width

    mm (in)

    126 (4.96)

    154 (6.06)

    200 (7.87)

    • Height

    mm (in)

    238 (9.37)

    345 (13.58)

    411 (16.18)

    • Depth

     

     

     

     

    • Without operator panel

    mm (in)

    171 (6.73)

    171 (6.73)

    171 (6.73)

    • With operator panel, max.

    mm (in)

    251 (9.88)

    251 (9.88)

    251 (9.88)

    Frame size

     

    FSA

    FSB

    FSC

    Weight, approx.

    With integrated line filter

     

     

     

     

    • Without integrated line filter

    kg (lb)

    1.7 (3.75)

    3.4 (7.50)

    5.4 (11.91)

    • With integrated line filter

    kg (lb)

    1.9 (4.19)

    3.6 (7.94)

    6 (13.23)



    1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

    2) The base-load current IH is based on the duty cycle for high overload (HO).

    3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

    4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

    5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.