Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS S7-300 SM 326 - Safety Integrated

  • Заказные данные
    (3)
  • Аксессуары
    (15)
  • Информационные материалы

    Информационные материалы

    • Digital inputs for the fail-safe SIPLUS S7 systems
    • For connecting:
      • Switches and 2-wire proximity switches
      • Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas
    • With integral safety functions for fail-safe operation
    • Can be used in fail-safe operation
      • Centrally: With S7-31xF-2 DP
      • Distributed in ET 200M: With SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH
    • In standard operation can be used in the same way as S7-300 modules
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Область применения

    Fail-safe digital input modules are suitable for connecting

    • Switches and 2-wire proximity switches (BEROs)
    • Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas

    The modules are implemented centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O station in combination with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH. They can also be used in non-safety-relevant standard mode and then respond like standard S7-300 modules.

    Дизайн

    Failsafe digital input modules have the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains
      • Green input signal status LEDs
      • Green LED for indicating safety mode
      • Red group fault LED
      • Slot for front connector protected by the front cover
      • Labeling area on the front cover
    • Easy installation:
      Installed in the same way as the other ET 200M I/O modules
    • User-friendly wiring via front connector

    Note:

    Cable guide 6ES7 393-4AA10-0AA0 is required in order to operate 6ES7 326-1RF00-0AB0 failsafe digital input modules in hazardous areas.

    Функции

    Failsafe digital input modules convert the levels of the external digital signals from the process into the internal signal level of the failsafe SIMATIC S7 CPUs.

    The safety functions required for failsafe operation are integrated in the modules.

    Технические данные

    Order number

    6AG1326-1BK02-2AB0

    6AG1326-1BK02-2AY0

    6AG1326-1RF01-4AB0

    SIPLUS S7-300 SM326F DI24

    SIPLUS S7-300 SM326F DI24

    SIPLUS S7-300 SM326F DI8 NAMUR

    General information

     

     

     

    Product type designation

    F-DI 8x24VDC Namur

    Supply voltage

     

     

     

    Rated value (DC)

    24 V

    24 V

    Input current

     

     

     

    from load voltage L+ (without load), max.

    450 mA

    450 mA

    160 mA

    from backplane bus 5 V DC, max.

    100 mA

    100 mA

    90 mA

    Encoder supply

     

     

     

    Number of outputs

    4; Isolated

    4; Isolated

    8

    Type of output voltage

    8.2 V DC

    Output current

     

     

     

    • Rated value

    400 mA

    400 mA

    Power loss

     

     

     

    Power loss, typ.

    10 W

    10 W

    4.5 W

    Digital inputs

     

     

     

    Number of digital inputs

    24

    24

    8

    Number of simultaneously controllable inputs

     

     

     

    all mounting positions

     

     

     

    • up to 40 °C, max.

    24

    24

    8

    • up to 60 °C, max.

    24; (at 24 V) or 18 (at 28.8 V)

    24; (at 24 V) or 18 (at 28.8 V)

    8

    Input voltage

     

     

     

    • Type of input voltage

    DC

    DC

    • Rated value (DC)

    24 V

    24 V

    • for signal "0"

    -30 to +5V

    -28.8 ... +5V

    • for signal "1"

    +11 to +30V

    +11 to +28.8V

    Input current

     

     

     

    • for signal "0", max. (permissible quiescent current)

    2 mA

    2 mA

    0.35 to 1.2 mA

    • for signal "1", typ.

    10 mA

    10 mA

    2.1 to 7 mA

    Input delay (for rated value of input voltage)

     

     

     

    for standard inputs

     

     

     

    • at "0" to "1", max.

    3.4 ms

    3.4 ms

    • at "1" to "0", max.

    3.4 ms

    3.4 ms

    for NAMUR inputs

     

     

     

    • at "0" to "1", max.

    1.2 to 3 ms

    • at "1" to "0", max.

    1.2 to 3 ms

    Cable length

     

     

     

    • shielded, max.

    200 m

    200 m

    200 m

    • unshielded, max.

    100 m

    100 m

    100 m

    Encoder

     

     

     

    Connectable encoders

     

     

     

    • 2-wire sensor

    Yes; if short-circuit test is deactivated

    Yes; if short-circuit test is deactivated

    • permissible quiescent current (2-wire sensor), max.

    2 mA

    2 mA

    Interrupts/diagnostics/status information

     

     

     

    Alarms

     

     

     

    • Diagnostic alarm

    Yes

    Yes

    Yes; Parameterizable

    Diagnostic messages

     

     

     

    • Diagnostic information readable

    Yes

    Yes

    Ex(i) characteristics

     

     

     

    Module for Ex(i) protection

    Yes

    Maximum values of input circuits (per channel)

     

     

     

    • Co (permissible external capacity), max.

    3 µF

    • Io (short-circuit current), max.

    13.9 mA

    • Lo (permissible external inductivity), max.

    80 mH

    • Po (power of load), max.

    33.1 mW

    • Uo (output no-load voltage), max.

    10 V

    • Um (fault voltage), max.

    60 V DC/30 V AC

    • Ta (permissible ambient temperature), max.

    60 °C

    60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155

    60 °C

    Potential separation

     

     

     

    Potential separation digital inputs

     

     

     

    • between the channels

    Yes

    Yes

    Yes

    • between the channels, in groups of

    12

    12

    • between the channels and backplane bus

    Yes

    Yes

    Yes

    • between the channels and the power supply of the electronics

    Yes

    Isolation

     

     

     

    Isolation tested with

    500 V DC/350 V AC

    500V AC for 1 min (internal voltage limiting to ±120V)

    Standards, approvals, certificates

     

     

     

    CE mark

    Yes

    Yes

    Yes

    UL approval

    Yes; File E239877

    Yes; File E239877

    FM approval

    Yes; CofC 3028431

    Yes; CofC 3028431

    RCM (formerly C-TICK)

    Yes

    KC approval

    Yes

    EAC (formerly Gost-R)

    Yes

    Railway application

     

     

     

    • EN 50155

    Yes; T1 Category 1 Class A/B horizontal mounting position

    Highest safety class achievable in safety mode

     

     

     

    • acc. to DIN VDE 0801

    AK 6

    AK 6

    • acc. to EN 954

    Cat. 4

    Cat. 4

    Cat. 4

    • SIL acc. to IEC 61508

    SIL 3

    SIL 3

    SIL 2 (single-channel), SIL 3 (two-channel)

    Ambient conditions

     

     

     

    Ambient temperature during operation

     

     

     

    • min.

    -25 °C; = Tmin

    -25 °C; = Tmin

    0 °C; = Tmin

    • max.

    60 °C; = Tmax; *+70 °C where forced convection with a minimum air velocity of 0.7 m/s through the modules and rated voltage of 24 V ±5 % are ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer.

    60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155

    60 °C; = Tmax

    Extended ambient conditions

     

     

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

     

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

     

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Connection method

     

     

     

    required front connector

    40-pin

    40-pin

    1x 40-pin

    Dimensions

     

     

     

    Width

    80 mm

    80 mm

    80 mm

    Height

    125 mm

    125 mm

    125 mm

    Depth

    120 mm

    120 mm

    120 mm

    Weights

     

     

     

    Weight, approx.

    442 g

    442 g

    482 g