Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SM 326 F digital output modules - Safety Integrated

  • Заказные данные
    (2)
  • Аксессуары
    (19)
  • Информационные материалы

    Информационные материалы

    • Digital outputs for the fail-safe SIMATIC S7 systems
    • Two versions (1 x current sourcing, 1 x current sinking)
    • For connecting solenoid valves, DC contactors and indicator lights
    • With integral safety functions for fail-safe operation
    • Can be used in fail-safe operation
      • Centrally: with S7-31xF DP, S7-31xF PN/DP
      • Distributed in ET 200M: with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-41xF-2 and S7-400F/FH

    Область применения

    Fail-safe digital output modules are used centrally with SIMATIC S7-31xF-2 DP, and in the ET 200M distributed I/O device together with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH.

    The modules are, for example, suitable for connecting solenoid valves, DC contactors and indicator lights.

    In the case of the SM 326 F-DO 10 x DC 24V/2A PP (6ES7 326-2BF10-0AB0), the function "Keep last valid value" can be used optionally in safety mode too. Together with the diagnostics capability of the module, this can be used for cost-optimized implementation of applications in, for example, the area of fire and gas alarm systems (in accordance with EN 54-2/-4 or NFPA72).

    Дизайн

    Fail-safe digital output modules have the following mechanical features:

    • Compact design:
      • 2 connections per output for single-channel or redundant actuator control
      • Green LEDs for indicating signal states at the outputs
      • Green LED for indicating safety operation
      • Red LED for group error display
      • Connection options for the front connector, protected behind the front door
      • Labeling field on the front door
    • Simple installation:
      installation is the same as for the other I/O modules of the ET 200M
    • User-friendly wiring via the front connector
    • Module width:
      • SM 326 F-DO 10 x DC 24V/2A PP (6ES7 326-2BF10-0AB0) single-width (40mm)
      • SM 326 F-DO 8 x DC 24V/2A PM (6ES7 326-2BF41-0AB0) double-width (80 mm)

    Функции

    Failsafe digital output modules convert the internal signal level of the failsafe SIMATIC S7 CPUs into the external signal levels required for the process. The safety functions required for failsafe operation are integrated in the modules.

    Технические данные

    Order number

    6ES7326-2BF10-0AB0

    6ES7326-2BF41-0AB0

    SM326, F-DO10XDC24V/2A PP, FAILSAFE

    SM 326, F-DO 8 X DC 24V/2A PM

    Supply voltage

     

     

    Rated value (DC)

    24 V; 1L+

    24 V; 1L+

    Load voltage L+

     

     

    • Rated value (DC)

    24 V; 2L+, 3L+

    24 V; 2L+, 3L+

    Input current

     

     

    from supply voltage 1L+, max.

    100 mA

    75 mA

    from load voltage 2L+ (without load), max.

    100 mA

    100 mA

    from load voltage 3L+ (without load), max.

    100 mA

    100 mA

    from backplane bus 5 V DC, max.

    100 mA

    100 mA

    Power loss

     

     

    Power loss, typ.

    6 W

    12 W

    Digital outputs

     

     

    Number of digital outputs

    10

    8

    Short-circuit protection

    Yes

    Yes

    Limitation of inductive shutdown voltage to

    L+ (-33 V)

    Switching capacity of the outputs

     

     

    • on lamp load, max.

    5 W

    5 W

    Output voltage

     

     

    • for signal "1" without series diode, min.

    L+ (-1.0 V)

    Output current

     

     

    • for signal "1" rated value

    2 A

    2 A

    • for signal "1" permissible range for 0 to 40 °C, min.

    7 mA

    7 mA

    • for signal "1" permissible range for 0 to 40 °C, max.

    2.4 A

    2 A; 2 A for horizontal installation, 1 A for vertical installation

    • for signal "1" permissible range for 40 to 60 °C, min.

    7 mA

    7 mA

    • for signal "1" permissible range for 40 to 60 °C, max.

    2.4 A

    1 A; for horizontal installation

    • for signal "0" residual current, max.

    0.5 mA

    0.5 mA

    Switching frequency

     

     

    • with resistive load, max.

    25 Hz

    30 Hz

    • with inductive load, max.

    25 Hz

    2 Hz

    • on lamp load, max.

    10 Hz

    10 Hz

    Total current of the outputs (per group)

     

     

    horizontal installation

     

     

    • up to 40 °C, max.

    10 A

    7.5 A

    • up to 60 °C, max.

    6 A

    5 A

    vertical installation

     

     

    • up to 40 °C, max.

    5 A

    5 A

    Cable length

     

     

    • shielded, max.

    1 000 m

    200 m; 200 m for SIL3, AK 6, Cat 4

    • unshielded, max.

    600 m

    200 m

    Interrupts/diagnostics/status information

     

     

    Alarms

     

     

    • Diagnostic alarm

    Yes

    Yes; Parameterizable

    Diagnostic messages

     

     

    • Diagnostic information readable

    Yes

    Yes

    Potential separation

     

     

    Potential separation digital outputs

     

     

    • between the channels

    Yes

    Yes

    • between the channels, in groups of

    5

    4

    • between the channels and backplane bus

    Yes

    Yes

    • between the channels and the power supply of the electronics

    Yes

    Yes

    Isolation

     

     

    Isolation tested with

    370V for 1 min

    500 V DC/350 V AC

    Highest safety class achievable in safety mode

     

     

    • acc. to DIN VDE 0801

    AK 5 and 6

    • acc. to EN 954

    Cat. 4

    Cat. 4

    • SIL acc. to IEC 61508

    SIL 3

    SIL 3

    Connection method

     

     

    required front connector

    40-pin

    40-pin

    Dimensions

     

     

    Width

    40 mm

    80 mm

    Height

    125 mm

    125 mm

    Depth

    120 mm

    120 mm

    Weights

     

     

    Weight, approx.

    330 g

    465 g