Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SM 326 F digital input modules - Safety Integrated

  • Заказные данные
    (2)
  • Аксессуары
    (18)
  • Информационные материалы

    Информационные материалы

    • Digital inputs for the fail-safe SIMATIC S7 systems
    • For connecting:
      • Switches and 2-wire proximity switches
      • Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas
    • With integral safety functions for fail-safe operation
    • Can be used in fail-safe operation
      • Centrally: with S7-31xF-2 DP
      • Distributed in ET 200M: with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH
    • In standard operation can be used in the same way as S7-300 modules

    Область применения

    Fail-safe digital input modules are suitable for connecting

    • Switches and 2-wire proximity switches (BEROs)
    • Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas

    The modules are implemented centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O station in combination with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH. They can also be used in non-safety-relevant standard mode and then respond like standard S7-300 modules.

    Дизайн

    Failsafe digital input modules have the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains
      • Green input signal status LEDs
      • Green LED for indicating safety mode
      • Red group fault LED
      • Slot for front connector protected by the front cover
      • Labeling area on the front cover
    • Easy installation:
      Installed in the same way as the other ET 200M I/O modules
    • User-friendly wiring via front connector

    Note:

    Cable guide 6ES7 393-4AA10-0AA0 is required in order to operate 6ES7 326-1RF00-0AB0 failsafe digital input modules in hazardous areas.

    Функции

    Failsafe digital input modules convert the levels of the external digital signals from the process into the internal signal level of the failsafe SIMATIC S7 CPUs.

    The safety functions required for failsafe operation are integrated in the modules.

    Технические данные

    Order number

    6ES7326-1RF01-0AB0

    6ES7326-1BK02-0AB0

    SM326, 8DE, DC24V, FAILSAFE

    SM326, F-DI 24 X DC24V, FAILSAFE

    General information

     

     

    Product type designation

    F-DI 8x24VDC Namur

    Supply voltage

     

     

    Rated value (DC)

    24 V

    Input current

     

     

    from load voltage L+ (without load), max.

    160 mA

    450 mA

    from backplane bus 5 V DC, max.

    90 mA

    100 mA

    Encoder supply

     

     

    Number of outputs

    8

    4; Isolated

    Type of output voltage

    8.2 V DC

    Output current

     

     

    • Rated value

    400 mA

    Power loss

     

     

    Power loss, typ.

    4.5 W

    10 W

    Digital inputs

     

     

    Number of digital inputs

    8

    24

    Number of simultaneously controllable inputs

     

     

    all mounting positions

     

     

    • up to 40 °C, max.

    8

    24

    • up to 60 °C, max.

    8

    24; (at 24 V) or 18 (at 28.8 V)

    Input voltage

     

     

    • Type of input voltage

    DC

    DC

    • Rated value (DC)

    24 V

    • for signal "0"

    -30 to +5V

    • for signal "1"

    +11 to +30V

    Input current

     

     

    • for signal "0", max. (permissible quiescent current)

    0.35 to 1.2 mA

    2 mA

    • for signal "1", typ.

    2.1 to 7 mA

    10 mA

    Input delay (for rated value of input voltage)

     

     

    for standard inputs

     

     

    • at "0" to "1", max.

    3.4 ms

    • at "1" to "0", max.

    3.4 ms

    for NAMUR inputs

     

     

    • at "0" to "1", max.

    1.2 to 3 ms

    • at "1" to "0", max.

    1.2 to 3 ms

    Cable length

     

     

    • shielded, max.

    200 m

    200 m

    • unshielded, max.

    100 m

    100 m

    Encoder

     

     

    Connectable encoders

     

     

    • 2-wire sensor

    Yes; if short-circuit test is deactivated

    • permissible quiescent current (2-wire sensor), max.

    2 mA

    Interrupts/diagnostics/status information

     

     

    Alarms

     

     

    • Diagnostic alarm

    Yes; Parameterizable

    Yes

    Diagnostic messages

     

     

    • Diagnostic information readable

    Yes

    Ex(i) characteristics

     

     

    Module for Ex(i) protection

    Yes

    Maximum values of input circuits (per channel)

     

     

    • Co (permissible external capacity), max.

    3 µF

    • Io (short-circuit current), max.

    13.9 mA

    • Lo (permissible external inductivity), max.

    80 mH

    • Po (power of load), max.

    33.1 mW

    • Uo (output no-load voltage), max.

    10 V

    • Um (fault voltage), max.

    60 V DC/30 V AC

    • Ta (permissible ambient temperature), max.

    60 °C

    60 °C

    Potential separation

     

     

    Potential separation digital inputs

     

     

    • between the channels

    Yes

    Yes

    • between the channels, in groups of

    12

    • between the channels and backplane bus

    Yes

    Yes

    • between the channels and the power supply of the electronics

    Yes

    Isolation

     

     

    Isolation tested with

    500 V DC/350 V AC

    Highest safety class achievable in safety mode

     

     

    • acc. to DIN VDE 0801

    AK 6

    • acc. to EN 954

    Cat. 4

    Cat. 4

    • SIL acc. to IEC 61508

    SIL 2 (single-channel), SIL 3 (two-channel)

    SIL 3

    Use in hazardous areas

     

     

    • Test number KEMA

    99 ATEX 2671 X

    Connection method

     

     

    required front connector

    1x 40-pin

    40-pin

    Dimensions

     

     

    Width

    80 mm

    80 mm

    Height

    125 mm

    125 mm

    Depth

    120 mm

    120 mm

    Weights

     

     

    Weight, approx.

    482 g

    442 g