Товаров
  
корзина пуста
  • Каталог оборудования Siemens

IM 151-8 PN/DP CPU

  • Заказные данные
    (1)
  • Аксессуары
    (25)
  • Информационные материалы

    Информационные материалы

    Information on SIMATIC ET 200S

    Introduced in 2012, the successor system of the tried and tested SIMATIC ET 200S, the SIMATIC ET 200SP, brings a number of advantages.

    For this reason, we recommend the use of the successor system SIMATIC ET 200SP for new automation concepts.

    In addition to the well-known good system properties of the SIMATIC ET 200S such as

    • Finely modular design for adaptation to the automation task in hand
    • Permanent wiring (replacement of the I/O modules without affecting the wiring, even during operation)
    • Connection to PROFINET and PROFIBUS

    SIMATIC ET 200SP offers further innovative system advantages compared to SIMATIC ET 200S:

    Faster and more compact setup

    • Up to 50 % reduced space requirements in the control cabinet, with unchanged cross-section area
    • No tools needed for one-handed wiring thanks to push-in terminals
    • Reduced part variance with increased scope of functions
    • System-integrated self-assembling load group formation without power modules
    • Up to 16 channels per module and 1024 channels per station
    • Flexible PROFINET connection via BusAdapter (RJ45, FastConnect, plastic or glass fiber-optic cables), also as integrated media converter
    • System-integrated shielded connection

    Increased performance

    • Short response times and isochronous mode for motion applications
    • High-speed data acquisition (digital from 1 µs, analog from 50 µs) and transmission (up to 100 Mbps):
      for digital signals with time-based I/O for precisely timed controlling independent of bus cycles;
      for analog and digital signal oversampling, n-fold acquisition or output of signals within a PN cycle.

    Additional functions

    • Measurement of machine consumption, e.g. current, using an integrated energy meter (up to 480 V)
    • Comprehensive diagnostics function (wire break and short-circuit) integrated by default even in Standard-class modules
    • System-integrated fail-safe modules (PROFIsafe) with simplified switchless address setting
    • Enhanced configuration control for easy option handling
    • Operation with gaps
    • Multi hot swapping
    • Larger module range (AS-i, AS-i Safety, additional CPU versions, Open Controller, etc.)
    • MSI/MSO: Simultaneous access to input and output data from up to 4 controllers
    • Adaptation of measuring range: Increased resolution by adapting the measuring range to a limited section of a measuring range supported by the analog input module
    • Station expansion through system-integrated IP67 components (ET 200AL)
    • Block I/O to IP20 degree of protection with 32 channels, comprising terminal block and electronic block
    • Discretely modular expansion to maximum of 128 channels or 12 modules
    • The complete ET 200S module spectrum can be used (with the exception of PROFIsafe modules)
    • Separation of connections and electronics with permanent wiring
    • Screw-type and spring-loaded terminal connections
    • Standard terminal block with 2-wire connection system; 3-wire and 4-wire systems available using additional terminals
    • Installation on a mounting rail
    • Hot swapping of expansion modules
    • Communication via PROFIBUS
    • Up to 100 bytes inputs and outputs (address space)

    Технические данные

    Order number

    6ES7151-8AB01-0AB0

    ET200S, IM151-8 PN/DP CPU, 192 KB

    General information

     

    Engineering with

     

    • Programming package

    STEP 7 V5.5 or higher

    Supply voltage

     

    Rated value (DC)

    24 V

    Power loss

     

    Power loss, typ.

    5.5 W

    Memory

     

    Work memory

     

    • integrated

    192 kbyte

    • Size of retentive memory for retentive data blocks

    64 kbyte

    Load memory

     

    • Plug-in (MMC), max.

    8 Mbyte

    CPU processing times

     

    for bit operations, typ.

    0.06 µs

    for word operations, typ.

    0.12 µs

    for fixed point arithmetic, typ.

    0.16 µs

    for floating point arithmetic, typ.

    0.59 µs

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    256

    IEC counter

     

    • present

    Yes

    S7 times

     

    • Number

    256

    IEC timer

     

    • present

    Yes

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    256 byte

    Address area

     

    I/O address area

     

    • Inputs

    2 048 byte

    • Outputs

    2 048 byte

    Process image

     

    • Inputs, adjustable

    2 048 byte

    • Outputs, adjustable

    2 048 byte

    Time of day

     

    Clock

     

    • Hardware clock (real-time)

    Yes

    Operating hours counter

     

    • Number

    1

    1. Interface

     

    Interface type

    PROFINET

    Physics

    Ethernet

    Interface types

     

    • Number of ports

    3; RJ45

    Functionality

     

    • MPI

    No

    • PROFINET IO Controller

    Yes; Also simultaneously with IO-Device functionality

    • PROFINET IO Device

    Yes; Also simultaneously with IO Controller functionality

    • PROFINET CBA

    Yes

    • PROFIBUS DP master

    No

    • PROFIBUS DP slave

    No

    • Point-to-point connection

    No

    PROFINET IO Controller

     

    Services

     

    • Number of connectable IO Devices, max.

    128

    • Of which IO devices with IRT, max.

    64

    • Number of IO Devices with IRT and the option "high flexibility"

    128

    • Number of connectable IO Devices for RT, max.

    128

    2. Interface

     

    Interface type

    External interface via master module 6ES7138-4HA00-0AB0

    Physics

    RS 485

    Functionality

     

    • MPI

    No

    • PROFINET IO Controller

    No

    • PROFINET IO Device

    No

    • PROFINET CBA

    No

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    No

    DP master

     

    • Number of DP slaves, max.

    32; Per station

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    No

    Communication functions

     

    PG/OP communication

    Yes

    Data record routing

    Yes; With DP master module

    Global data communication

     

    • supported

    No

    S7 basic communication

     

    • supported

    Yes; I blocks

    S7 communication

     

    • supported

    Yes

    Open IE communication

     

    • TCP/IP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    8

    • ISO-on-TCP (RFC1006)

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    8

    • UDP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    8

    Web server

     

    • supported

    Yes

    Number of connections

     

    • overall

    12

    Programming

     

    Programming language

     

    • LAD

    Yes

    • FBD

    Yes

    • STL

    Yes

    • SCL

    Yes; Optional

    • CFC

    Yes; Optional

    • GRAPH

    Yes; Optional

    • HiGraph®

    Yes; Optional

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Block encryption

    Yes; With S7 block Privacy

    Dimensions

     

    Width

    120 mm; DP master module: 35 mm

    Height

    119.5 mm

    Depth

    75 mm

    Weights

     

    Weight, approx.

    320 g; DP master module: Approx. 100 g