    The self-commutated infeed/regenerative feedback units with IGBTs generate a regulated DC link voltage. This means that the connected Motor Modules are decoupled from the line voltage. Line voltage fluctuations within the permissible supply tolerances have no effect on the motor voltage.

    If required, the Active Line Modules can also provide reactive power compensation.

    Active Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.

    Active Line Modules are always operated together with the associated Active Interface Modules. These include the necessary pre-charging circuit as well as a Clean Power Filter.

    Дизайн

    The Active Line Modules have the following interfaces as standard:

    • 1 line supply connection
    • 1 connection for the 24 V DC electronics power supply
    • 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules
    • 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
    • 3 DRIVE-CLiQ sockets
    • 1 temperature sensor input for KTY84‑130, Pt1000, PTC or Pt100 (Pt1000 can be used from firmware V4.7 HF17)
    • 2 PE connections

    The status of the Active Line Modules is indicated via three LEDs.

    The scope of supply of the Active Line Modules includes:

    • DRIVE-CLiQ cable to connect to a Control Unit
    • DRIVE-CLiQ cable to connect the Control Unit to the first Motor Module
    • 1 set of warning labels in 30 languages
      (BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

    Интеграция

    The Active Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate the Active Line Modules.

    Connection example of an Active Line Module

    Технические данные

    General technical specifications

    Electrical specifications

    Line power factor

     

    • Basic fundamental (cos φ1)

    1 (factory setting),
    can be altered by inputting a reactive current setpoint

    • Total (λ)

    1 (factory setting)

    Efficiency

    >97.5 % (including Active Interface Module)

    DC link voltage

    The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
    Factory setting of the DC link voltage: 1.5 × line voltage

    Radio interference suppression

     
    • Standard (Active Line Module with Active Interface Module)

    Category C3 to EN 61800‑3

    • With line filter

    Category C2 to EN 61800‑3



    Line voltage 380 ... 480 V 3 AC

    Active Line Modules

     

    6SL3330-7TE32-1AA3

    6SL3330-7TE32-6AA3

    6SL3330-7TE33-8AA3

    6SL3330-7TE35-0AA3

    6SL3330-7TE36-1AA3

    Rated power

     

     

     

     

     

     

    • At Irated DC (50 Hz 400 V)

    kW

    132

    160

    235

    300

    380

    • At IH DC (50 Hz 400 V)

    kW

    115

    145

    210

    270

    335

    • At Irated DC (60 Hz 460 V)

    hp

    200

    250

    400

    500

    600

    • At IH DC (60 Hz 460 V)

    hp

    150

    200

    300

    400

    500

    DC link current

     

     

     

     

     

     

    • Rated current Irated DC

    A

    235

    291

    425

    549

    678

    • Base-load current IH DC1)

    A

    209

    259

    378

    489

    603

    • Maximum current Imax DC

    A

    352

    436

    637

    823

    1017

    Infeed/regenerative feedback current

     

     

     

     

     

     

    • Rated current Irated I

    A

    210

    260

    380

    490

    605

    • Maximum current Imax I

    A

    315

    390

    570

    735

    907

    Current demand

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.1

    1.1

    1.35

    1.35

    1.4

    • 400 V AC

    A

    0.63

    1.13

    1.8

    1.8

    3.6

    DC link capacitance

     

     

     

     

     

     

    • Active Line Module

    μF

    4200

    5200

    7800

    9600

    12600

    • Drive line-up, max.

    μF

    41600

    41600

    76800

    76800

    134400

    Power loss, max. 2)

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    2.2

    2.7

    3.9

    4.8

    6.2

    • At 60 Hz 460 V

    kW

    2.3

    2.9

    4.2

    5.1

    6.6

    Cooling air requirement

    m3/s (ft3/s)

    0.17 (6.0)

    0.23 (8.1)

    0.36 (12.7)

    0.36 (12.7)

    0.78 (27.5)

    Sound pressure level LpA 3)

    (1 m) at 50/60 Hz

    dB

    64/67

    71/71

    69/73

    69/73

    70/73

    Line connection

    U1, V1, W1

     

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M10 screw

    Flat connector for M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 × 185

    2 × 185

    2 × 240

    2 × 240

    4 × 240

    DC link connection

    DCP, DCN

     

    M10 screw

    M10 screw

    M10 screw

    M10 screw

    4 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    2 × 185

    2 × 185

    2 × 240

    2 × 240

    Busbar

    PE1/GND connection

     

    M10 screw

    M10 screw

    M10 screw

    M10 screw

    M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 × 185

    2 × 185

    2 × 240

    2 × 240

    240

    PE2/GND connection

     

    M10 screw

    M10 screw

    M10 screw

    M10 screw

    2 × M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 × 185

    2 × 185

    2 × 240

    2 × 240

    2 × 240

    Cable length, max. 4)

     

     

     

     

     

     

    • Shielded

    m (ft)

    2700 (8859)

    2700 (8859)

    2700 (8859)

    2700 (8859)

    3900 (12796)

    • Unshielded

    m (ft)

    4050 (13288)

    4050 (13288)

    4050 (13288)

    4050 (13288)

    5850 (19194)

    Degree of protection

     

    IP20

    IP20

    IP20

    IP20

    IP00

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    326 (12.8)

    326 (12.8)

    326 (12.8)

    326 (12.8)

    503 (19.8)

    • Height

    mm (in)

    1400 (55.1)

    1400 (55.1)

    1533 (60.3)

    1533 (60.3)

    1475 (58.1)

    • Depth

    mm (in)

    356 (14.0)

    356 (14.0)

    545 (21.5)

    545 (21.5)

    540 (21.3)

    Weight, approx.

    kg (lb)

    95 (209)

    95 (209)

    136 (300)

    136 (300)

    290 (639)

    Frame size

     

    FX

    FX

    GX

    GX

    HX

    Minimum short-circuit current 5)

    A

    6200

    10500

    10500

    8000

    9200



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    3) Total sound pressure level of Active Interface Module and Active Line Module.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    5) Current required for reliably triggering protective devices.

    Line voltage 380 ... 480 V 3 AC

    Active Line Modules

     

    6SL3330-7TE37-5AA3

    6SL3330-7TE38-4AA3

    6SL3330-7TE41-0AA3

    6SL3330-7TE41-2AA3

    6SL3330-7TE41-4AA3

    Rated power

     

     

     

     

     

     

    • At Irated DC (50 Hz 400 V)

    kW

    450

    500

    630

    800

    900

    • At IH DC (50 Hz 400 V)

    kW

    400

    465

    545

    690

    780

    • At Irated DC (60 Hz 460 V)

    hp

    600

    700

    900

    1000

    1250

    • At IH DC (60 Hz 460 V)

    hp

    600

    700

    800

    900

    1000

    DC link current

     

     

     

     

     

     

    • Rated current Irated DC

    A

    835

    940

    1103

    1412

    1574

    • Base-load current IH DC 1)

    A

    700

    837

    982

    1255

    1401

    • Maximum current Imax DC

    A

    1252

    1410

    1654

    2120

    2361

    Infeed/regenerative feedback current

     

     

     

     

     

     

    • Rated current Irated I

    A

    745

    840

    985

    1260

    1405

    • Maximum current Imax I

    A

    1117

    1260

    1477

    1890

    2107

    Current demand

     

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.4

    1.4

    1.5

    1.7

    1.7

    • 400 V AC

    A

    3.6

    3.6

    5.4

    5.4

    5.4

    DC link capacitance

     

     

     

     

     

     

    • Active Line Module

    μF

    15600

    16800

    18900

    26100

    28800

    • Drive line-up, max.

    μF

    134400

    134400

    230400

    230400

    230400

    Power loss, max. 2)

     

     

     

     

     

     

    • At 50 Hz 400 V

    kW

    7.3

    7.7

    10.1

    12.1

    13.3

    • At 60 Hz 460 V

    kW

    7.7

    8.2

    10.8

    13.0

    14.2

    Cooling air requirement

    m3/s (ft3/s)

    0.78 (27.5)

    0.78 (27.5)

    1.08 (38.1)

    1.08 (38.1)

    1.08 (38.1)

    Sound pressure level LpA 3)

    (1 m) at 50/60 Hz

    dB

    70/73

    70/73

    71/73

    71/73

    71/73

    Line connection

    U1, V1, W1

     

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    4 × 240

    4 × 240

    6 × 240

    6 × 240

    6 × 240

    DC link connection

    DCP, DCN

     

    4 × hole for M12

    4 × hole for M12

    4 × hole for M12

    4 × hole for M12

    4 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    Busbar

    Busbar

    Busbar

    Busbar

    Busbar

    PE1/GND connection

     

    M12 screw

    M12 screw

    M12 screw

    M12 screw

    M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    240

    PE2/GND connection

     

    2 × M12 screw

    2 × M12 screw

    3 × M12 screw

    3 × M12 screw

    3 × M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 × 240

    2 × 240

    3 × 240

    3 × 240

    3 × 240

    Cable length, max. 4)

     

     

     

     

     

     

    • Shielded

    m (ft)

    3900 (12796)

    3900 (12796)

    3900 (12796)

    3900 (12796)

    3900 (12796)

    • Unshielded

    m (ft)

    5850 (19194)

    5850 (19194)

    5850 (19194)

    5850 (19194)

    5850 (19194)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

     

    • Width

    mm (in)

    503 (19.8)

    503 (19.8)

    704 (27.7)

    704 (27.7)

    704 (27.7)

    • Height

    mm (in)

    1475 (58.1)

    1475 (58.1)

    1480 (58.3)

    1480 (58.3)

    1480 (58.3)

    • Depth

    mm (in)

    540 (21.3)

    540 (21.3)

    550 (21.6)

    550 (21.6)

    550 (21.6)

    Weight, approx.

    kg (lb)

    290 (639)

    290 (639)

    450 (992)

    450 (992)

    450 (992)

    Frame size

     

    HX

    HX

    JX

    JX

    JX

    Minimum short-circuit current 5)

    A

    8800

    10400

    16000

    21000

    21000



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    3) Total sound pressure level of Active Interface Module and Active Line Module.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    5) Current required for reliably triggering protective devices.

    Line voltage 500 ... 690 V 3 AC

    Active Line Modules

     

    6SL3330-7TG35-8AA3

    6SL3330-7TG37-4AA3

    6SL3330-7TG41-0AA3

    6SL3330-7TG41-3AA3

    Rated power

     

     

     

     

     

    • At Irated DC (50 Hz 690 V)

    kW

    630

    800

    1100

    1400

    • At IH DC (50 Hz 690 V)

    kW

    620

    705

    980

    1215

    • At Irated DC (50 Hz 500 V)

    kW

    447

    560

    780

    965

    • At IH DC (50 Hz 500 V)

    kW

    450

    510

    710

    880

    • At Irated DC (60 Hz 575 V)

    hp

    675

    900

    1250

    1500

    • At IH DC (60 Hz 575 V)

    hp

    506

    600

    1000

    1250

    DC link current

     

     

     

     

     

    • Rated current Irated DC

    A

    644

    823

    1148

    1422

    • Base-load current IH DC1)

    A

    573

    732

    1022

    1266

    • Maximum current Imax DC

    A

    966

    1234

    1722

    2133

    Infeed/regenerative feedback current

     

     

     

     

     

    • Rated current Irated I

    A

    575

    735

    1025

    1270

    • Maximum current Imax I

    A

    862

    1102

    1537

    1905

    Current demand

     

     

     

     

     

    • 24 V DC auxiliary power supply

    A

    1.4

    1.5

    1.7

    1.7

    • 500 V AC

    A

    3.0

    4.4

    4.4

    4.4

    • 690 V AC

    A

    2.1

    3.1

    3.1

    3.1

    DC link capacitance

     

     

     

     

     

    • Active Line Module

    μF

    7400

    11100

    14400

    19200

    • Drive line-up, max.

    μF

    59200

    153600

    153600

    153600

    Power loss, max. 2)

     

     

     

     

     

    • At 50 Hz 690 V

    kW

    6.8

    10.2

    13.6

    16.5

    • At 60 Hz 575 V

    kW

    6.2

    9.6

    12.9

    15.3

    Cooling air requirement

    m3/s (ft3/s)

    0.78 (27.5)

    1.08 (38.1)

    1.08 (38.1)

    1.08 (38.1)

    Sound pressure level LpA 3)

    (1 m) at 50/60 Hz

    dB

    70/73

    71/73

    71/73

    71/73

    Line connection

    U1, V1, W1

     

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    Flat connector for M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    4 × 240

    6 × 240

    6 × 240

    6 × 240

    DC link connection

    DCP, DCN

     

    4 × hole for M12

    4 × hole for M12

    4 × hole for M12

    4 × hole for M12

    • Conductor cross section, max. (IEC)

    mm2

    Busbar

    Busbar

    Busbar

    Busbar

    PE1/GND connection

     

    M12 screw

    M12 screw

    M12 screw

    M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    240

    240

    240

    240

    PE2/GND connection

     

    2 × M12 screw

    3 × M12 screw

    3 × M12 screw

    3 × M12 screw

    • Conductor cross section, max. (IEC)

    mm2

    2 x 240

    3 x 240

    3 x 240

    3 x 240

    Cable length, max. 4)

     

     

     

     

     

    • Shielded

    m (ft)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    2250 (7382)

    • Unshielded

    m (ft)

    3375 (11073)

    3375 (11073)

    3375 (11073)

    3375 (11073)

    Degree of protection

     

    IP00

    IP00

    IP00

    IP00

    Dimensions

     

     

     

     

     

    • Width

    mm (in)

    503 (19.8)

    704 (27.7)

    704 (27.7)

    704 (27.7)

    • Height

    mm (in)

    1475 (58.1)

    1480 (58.3)

    1480 (58.3)

    1480 (58.3)

    • Depth

    mm (in)

    540 (21.3)

    550 (21.6)

    550 (21.6)

    550 (21.6)

    Weight, approx.

    kg (lb)

    290 (639)

    450 (992)

    450 (992)

    450 (992)

    Frame size

     

    HX

    JX

    JX

    JX

    Minimum short-circuit current 5)

    A

    8400

    10500

    16000

    20000



    1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

    2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

    3) Total sound pressure level of Active Interface Module and Active Line Module.

    4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

    5) Current required for reliably triggering protective devices.