    Standard assignment of inputs/outputs

    The following table shows the default assignments of the interface for a "standard" application.

    Signal designation

    Function

    Digital input signals of module "CB08"

    Internal digital input 8

    Controller enable global 1

    Internal digital input 9

    Freely parameterizable

    Internal digital input 10

    Speed ON remote

    Internal digital input 11

    Freely parameterizable

    Internal digital input 12

    Local/remote, remote=1

    Internal digital input 13

    External fault

    Internal digital input 14

    Remote reset

    Internal digital input 15

    Rapid stop global 1

    Internal digital input 16

    Reverse remote

    Internal digital input 27

    PTC thermistor trip (not for explosion-proof motors)

    Internal digital input 28

    PTC thermistor prewarning (not for explosion-proof motors)

    Internal digital input 29

    External warning

    Digital output signals of module "CB08"

    Internal digital output 37, 38, 39

    Relay 1: "Ready"

    Internal digital output 41, 42

    Relay 2: "Operation"

    Internal digital output 30, 31

    Relay 3: "Alarm"

    Internal digital output 32, 33

    Relay 4: Not assigned

    Internal digital output 34, 35, 36

    "Converter fault"

    Analog input signals of module "CB08"

    Internal analog input 50, 51, 52

    Speed setpoint

    Internal analog input 53, 54

    User-assignable connection

    Analog output signals of module "CB08"

    Internal analog output 60, 61

    Motor speed

    Internal analog output 62, 63

    Motor current



    NAMUR-compliant assignment of inputs/outputs

    The following table shows the default assignments of the interface for a "NAMUR" application.

    Signal designation

    Function

    Digital input signals of module "CB08"

    Internal digital input 8

    Main contactor checkback

    Internal digital input 9

    Test/Normal switch on converter

    Internal digital input 10

    ON/OFF static; ON dynamic (controller enable ON)

    Internal digital input 11

    OFF dynamic (controller enable OFF)

    Internal digital input 12

    Fast (motorized potentiometer UP)

    Internal digital input 13

    Slow (motorized potentiometer DOWN)

    Internal digital input 14

    Reset normal

    Internal digital input 15

    Interlock (controller disable)

    Internal digital input 16

    Reverse normal

    Internal digital input 27

    Freely parameterizable

    Internal digital input 28

    Freely parameterizable

    Internal digital input 29

    Freely parameterizable

    Digital output signals of module "CB08"

    Internal digital output 37, 38, 39

    Relay 1: "Group prewarning"

    Internal digital output 41, 42

    Relay 2: "Main(line)contactor closed"

    Internal digital output 30, 31

    Relay 3: "Ready"

    Internal digital output 32, 33

    Relay 4: "Motor turning"

    Internal digital output 34, 35, 36

    "Converter fault"

    Analog input signals of module "CB08"

    Internal analog input 50, 51, 52

    Speed setpoint (terminal 50/51 or 52/51)

    Internal analog input 53, 54

    Actual process value/user-assignable input (terminal 53/51 or 54/51)

    Analog output signals of module "CB08"

    Internal analog output 60, 61

    Motor speed

    Internal analog output 62, 63

    Motor current