Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Bearing guard

  • Заказные данные
    (1)
  • Информационные материалы

    Дизайн

    The Bearing Guard consists of four terminal blocks A, B, C and D, a display, and associated control elements. The terminal blocks are coded and therefore constitute non-interchangeable connection elements.

    Функции

    The Bearing Guard reliably analyzes the status of machines and rolling-contact bearings and signals limit violations via floating contacts.

    Functions:

    • Low-cost monitoring of rolling-contact bearings
    • Diagnostics procedure in accordance with VDI 3832 and DIN ISO 10816‑3
    • Monitoring of motors with fixed speed
    • Easy commissioning by means of teach-in (learning mode) via LC display
    • Adjustable limits for warning and alarm
    • Limit signaling via two floating contacts

    Технические данные

    Order number

    6AT8001-1AA00

    SIPLUS CMS1000 Bearing Guard

    General information

     

    Product brand name

    SIPLUS

    Product designation

    SIPLUS CMS1000 Bearing Guard

    Product description

    Device for monitoring mechanical vibrations based on characteristic values

    Installation type/mounting

     

    Mounting type

    standard rail

    Mounting position

    vertical

    Recommended mounting position

    vertical

    Required clearance

     

    • for side-by-side mounting at the top

    25 mm

    • for side-by-side mounting at the front

    80 mm

    • for side-by-side mounting at the side

    0 mm

    • for side-by-side mounting at the bottom

    25 mm

    Supply voltage

     

    Type of supply voltage

    AC/DC

    Rated value (DC)

    24 V

    Permissible range, lower limit (50 Hz AC)

    115 V

    Permissible range, upper limit (50 Hz AC)

    240 V

    Permissible range, lower limit (60 Hz AC)

    240 V

    Permissible range, upper limit (60 Hz AC)

    115 V

    Input current

     

    Current consumption (at 24 V DC), typ.

    210 mA

    Digital inputs

     

    Number of disable inputs

    1

    Input voltage

     

    • At the 24 V DC disable input

    Yes

    Digital outputs

     

    Number of signaling outputs

    2

    Design of signaling outputs

    Relay output

    Speed input

     

    Number of speed inputs

    1

    Protocols

     

    • 24 V DC digital

    Yes

    • -10 V to +10 V

    Yes

    Protocols

     

    • 0 to 20 mA

    No

    • 4 mA to 20 mA

    Yes

    Sensor input

     

    Number of IEPE sensor inputs

    0

    Number of MEMS sensor inputs

    1

    Protocols

     

    Bus communication

    No

    Integrated Functions

     

    Monitoring functions

     

    • Vibration characteristic monitoring via RMS value of the vibration speed

    Yes

    • Vibration characteristic monitoring via diagnostic characteristic value

    Yes

    • Frequency-selective monitoring via vibration speed spectrum

    No

    • Frequency-selective monitoring via vibration acceleration spectrum

    No

    • Frequency-selective monitoring via envelope curve analysis

    No

    Degree and class of protection

     

    IP degree of protection

    IP20

    Standards, approvals, certificates

     

    Certificate of suitability

    CE

    Standard for interference immunity

    IEC 61326-1, IEC 61326-2-3

    Standard for safety

    IEC 61010-1

    Equipment marking according to EN 61346-2

    P

    Equipment marking according to DIN 40719, expanded according to IEC 204-2, according to IEC 750

    P

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    -25 °C

    • max.

    60 °C

    Ambient temperature during storage/transportation

     

    • Storage, min.

    -25 °C

    • Storage, max.

    60 °C

    • Transportation, min.

    -25 °C

    • Transportation, max.

    60 °C

    Relative humidity

     

    • Operation without condensation, min.

    5 %

    • Operation without condensation, max.

    95 %

    Connection method

     

    Design of electrical connection for auxiliary and control circuit

    Screw connection

    • Connectable conductor cross-section, solid or stranded, min.

    0.5 mm²

    • Connectable conductor cross-section, solid or stranded, max.

    4 mm²

    • Connectable conductor cross-section, finely stranded with end sleeve, min.

    0.5 mm²

    • Connectable conductor cross-section, finely stranded with end sleeve, max.

    2.5 mm²

    • Connectable cable cross-section finely stranded without end sleeve, min.

    0.5 mm²

    • Connectable cable cross-section finely stranded without end sleeve, max.

    2.5 mm²

    Terminals

     

    • Removable terminal for main circuit

    Yes

    • Removable terminal for auxiliary and control circuit

    Yes

    Connection I/O signals

     

    Mounting

     

    • Size of screwdriver bit

    Size 2 and Pozidriv 2

    • Design of thread of connection screw

    M3

    • Tightening torque, min.

    0.8 N·m

    • Tightening torque, max.

    1.2 N·m

    Mechanics/material

     

    Material of housing

    plastic

    Dimensions

     

    Width

    45 mm

    Height

    106 mm

    Depth

    86 mm

    Weights

     

    Weight

    300 g