Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS S7-400 SM 431

  • Заказные данные
    (1)
  • Аксессуары
    (9)
  • Информационные материалы

    Информационные материалы

    • Analog inputs for SIMATIC S7-400
    • For connection of voltage and current sources
    • Resolution 13 to 16 bit
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Technical documentation on SIPLUS can be found here:
    http://www.siemens.de/siplus-extreme

    Область применения

    Analog input modules allow the connection of the controller to analog signals of the process. They are suitable for connection of voltage sensors and current sensors, thermo elements, resistors and resistance thermometers.

    Дизайн

    The analog input modules feature the following mechanical characteristics:

    • Compact design:
      The rugged plastic enclosure contains:
      • Plug-in option for the front connector.
      • Labeling strips.
    • Easy installation.
    • User-friendly wiring:

    The modules are wired via a plug-in front connector.

    Функции

    The analog input modules convert analog signals from the process to digital values for internal processing in the S7-400.

    The modules feature:

    • Resolution of 13 to 16 bits
    • Different measurement ranges:
    • Interrupt capability
    • Diagnostics

    Технические данные

    Order number

    6AG1431-0HH00-4AB0

    SIPLUS_SM431_16AE

    Supply voltage

     

    Load voltage L+

     

    • Rated value (DC)

    24 V; Only required for supplying 2-wire transmitters

    • Reverse polarity protection

    Yes

    Input current

     

    from load voltage L+ (without load), max.

    400 mA; for 16 connected, fully controlled 2-wire transmitters

    from backplane bus 5 V DC, max.

    100 mA

    Power loss

     

    Power loss, typ.

    2 W

    Analog inputs

     

    Number of analog inputs

    16

    • For voltage/current measurement

    16

    permissible input voltage for voltage input (destruction limit), max.

    20 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20)

    permissible input current for current input (destruction limit), max.

    40 mA

    Input ranges (rated values), voltages

     

    • 1 V to 5 V

    Yes

    • -1 V to +1 V

    Yes

    • -10 V to +10 V

    Yes

    Input ranges (rated values), currents

     

    • -20 mA to +20 mA

    Yes

    • 4 mA to 20 mA

    Yes

    Cable length

     

    • shielded, max.

    200 m

    Analog value generation for the inputs

     

    Integration and conversion time/resolution per channel

     

    • Resolution with overrange (bit including sign), max.

    13 bit

    • Integration time, parameterizable

    Yes

    • Basic conversion time (ms)

    55 / 65 ms

    • Integration time (ms)

    50 / 60 ms

    • Interference voltage suppression for interference frequency f1 in Hz

    50 / 60 Hz

    Encoder

     

    Connection of signal encoders

     

    • for voltage measurement

    Yes; possible

    • for current measurement as 4-wire transducer

    Yes

    Errors/accuracies

     

    Operational error limit in overall temperature range

     

    • Voltage, relative to input range, (+/-)

    0.65 %; 1.0% at 1 to 5 V; 0.65% at +/-1 V, +/-10 V

    • Current, relative to input range, (+/-)

    0.65 %

    Basic error limit (operational limit at 25 °C)

     

    • Voltage, relative to input range, (+/-)

    0.25 %; 0.5% at 1 to 5 V; 0.25% at +/-1 V, +/-10 V

    • Current, relative to input range, (+/-)

    0.25 %; at +/-20 mA, 4 to 20 mA

    Potential separation

     

    Potential separation analog inputs

     

    • Potential separation analog inputs

    No

    • between the channels

    No

    Isolation

     

    Isolation tested with

    500 V DC between bus and local ground

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    0 °C; = Tmin

    • max.

    60 °C; = Tmax

    Ambient temperature during storage/transportation

     

    • min.

    -40 °C

    • max.

    70 °C

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Dimensions

     

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Weights

     

    Weight, approx.

    500 g