Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS S7-400 CPU 417

  • Заказные данные
    (1)
  • Аксессуары
    (16)
  • Информационные материалы

    Информационные материалы

    The most powerful SIMATIC S7-400 CPU

    • Applicable for plants with maximum requirements in the high-end performance range
    • With 2 plug-in slots for IF modules
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Technical documentation on SIPLUS can be found here:
    http://www.siemens.de/siplus-extreme

    Область применения

    The CPU 417-4 is the most powerful SIMATIC S7-400 CPU. The integral PROFIBUS DP interfaces permit direct connection to the PROFIBUS DP fieldbus as master or slave.

    Two further DP master systems can be connected via the IF 964-DP interface submodules.

    Note:
    Only the interface module 6ES7 964-2AA04-0AB0 can be used.

    Дизайн

    The CPU 417-4 has:

    • Powerful processor:
      The CPU achieves instruction execution times as low as 0.018 µs per binary instruction.
    • 30 MB RAM (of which 15 MB each for program and data);
      fast RAM for parts of the user program relevant to execution.
    • Flexible expansion:
      Up to 262144 digital and 16384 analog inputs/outputs.
    • Multi-point interface MPI:
      With the MPI it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 Mbit/s. The CPU can establish up to 44 connections to stations of the communications bus (C bus) and the MPI.
      Note:
      If the PROFIBUS DP interface and MPI interface are operated simultaneously, it is only possible to connect the following bus connector to the MPI interface:
      • With socket: 6ES7 972-0BB42-0XA0
      • Without socket: 6ES7 972-0BA42-0XA0
    • Mode selector switch:
      Designed as toggle switch.
    • Diagnostics buffer:
      The last 120 fault and interrupt events are retained in a ring buffer for diagnostic purposes (extendable).
    • Real-time clock:
      The date and time are appended to diagnostic messages of the CPU.
    • Memory card:
      For expansion of the integrated load memory. The information in the load memory comprises S7-400 parameterization data in addition to the program and therefore requires twice as much memory space. The result is that:
      • The integral load memory is not sufficient for large programs, therefore a memory card is frequently required.
        RAM and FEPROM cards (FEPROM for retentive storage) are available
    • PROFIBUS DP interface:
      The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. From the user's point of view, the distributed I/O is treated as central I/O (same configuring, addressing, and programming).
      Mixed configuration: SIMATIC S5 with SIMATIC S7 as PROFIBUS master to EN 50170.
      Note:
      If the PROFIBUS DP and MPI interface are operated simultaneously, it is only possible to connect the following bus connectors to the MPI interface:
      • With socket: 6ES7 972-0BB42-0XA0
      • Without socket: 6ES7 972-0BA42-0XA0
    • Two additional slots:
      Two additional PROFIBUS DP master systems can be connected via IF 964-DP interface modules.

    Функции

    • Block protection:
      a password concept also protects the user program from unauthorized access
    • Integrated HMI services:
      The user only has to specify the source and destination of the data with HMI devices. The data are then transported cyclically and automatically by the system.
    • Integrated communication functions:
      • PG/OP communication
      • Global data communication
      • S7 standard communication
      • S7 communication
    Configurable Attributes

    The STEP 7 tool "Hardware configuration" can be used to program the properties and response of the S7-400 including the CPUs, e.g.

    • Multipoint interface MPI:
      • Definition of node addresses
      • Startup/cycle behavior
      • Stipulation of the maximum cycle time and communication load
    • Address allocation:
      Addressing of I/O modules
    • Retentive area:
      Definition of the number of retentive bit memories, counters, timers, data blocks, and clock memories
    • Size of the process image, local data
    • Length of the diagnostics buffer
    • Protection level:
      Definition of access authorizations to program and data
    • System diagnostics:
      Definition of the handling and scope of diagnostics messages
    • Timed interrupts:
      Setting of periods
    • Configuring
    Reporting functions
    • Status and fault indicators:
      LEDs indicate internal and external faults and operating modes such RUN, STOP, restart, test function, etc.
    • Test functions:
      The PG can be used to display signal states in program execution, modify process tags irrespective of the user program, read out the contents of stack memories, run separate program steps and inhibit program components.
    • Information functions:
      The PG can be used to provide the user with information about the memory capacity and operating mode of the CPU, and the current utilization of the working and load memories.

    Технические данные

    Order number

    6AG1417-4XT07-7AB0

    SIPLUS S7-400 CPU 417-4 V7

    General information

     

    Product type designation

    CPU 417-4

    Engineering with

     

    • Programming package

    STEP 7 V5.4 or higher with HSP 261

    Supply voltage

     

    Rated value (DC)

    • 24 V DC

    No; Power supply via system power supply

    Power loss

     

    Power loss, typ.

    6.5 W

    Memory

     

    Work memory

     

    • integrated

    32 Mbyte

    • integrated (for program)

    16 Mbyte

    • integrated (for data)

    16 Mbyte

    Load memory

     

    • expandable FEPROM, max.

    64 Mbyte

    • integrated RAM, max.

    1 Mbyte

    • expandable RAM, max.

    64 Mbyte

    CPU processing times

     

    for bit operations, typ.

    7.5 ns

    for word operations, typ.

    7.5 ns

    for fixed point arithmetic, typ.

    7.5 ns

    for floating point arithmetic, typ.

    15 ns

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    2 048

    IEC counter

     

    • present

    Yes

    S7 times

     

    • Number

    2 048

    IEC timer

     

    • present

    Yes

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    16 kbyte; Size of bit memory address area

    Address area

     

    I/O address area

     

    • Inputs

    16 kbyte

    • Outputs

    16 kbyte

    Process image

     

    • Inputs, adjustable

    16 kbyte

    • Outputs, adjustable

    16 kbyte

    Time of day

     

    Clock

     

    • Hardware clock (real-time)

    Yes

    Operating hours counter

     

    • Number

    16

    Interfaces

     

    Interfaces/bus type

    1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 2 x PROFIBUS DP (optionally pluggable)

    Number of RS 485 interfaces

    2; Combined MPI / PROFIBUS DP and PROFIBUS DP

    Number of other interfaces

    2; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

    1. Interface

     

    Interface type

    Integrated

    Physics

    RS 485 / PROFIBUS + MPI

    Functionality

     

    • MPI

    Yes

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    Yes

    DP master

     

    • Number of DP slaves, max.

    32

    2. Interface

     

    Interface type

    Integrated

    Physics

    RS 485 / PROFIBUS

    Functionality

     

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    Yes

    DP master

     

    • Number of DP slaves, max.

    125

    3. Interface

     

    Interface type

    Pluggable interface module (IF), technical data as for 2nd interface

    Plug-in interface modules

    IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

    Physics

    RS 485 / PROFIBUS

    Functionality

     

    • MPI

    No

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    Yes

    DP master

     

    • Number of DP slaves, max.

    125

    4. Interface

     

    Interface type

    Pluggable interface module (IF), technical data as for 2nd interface

    Plug-in interface modules

    IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    Yes; For PROFIBUS only

    Communication functions

     

    PG/OP communication

    Yes

    Data record routing

    Yes

    Global data communication

     

    • supported

    Yes

    S7 basic communication

     

    • supported

    Yes

    S7 communication

     

    • supported

    Yes

    S5 compatible communication

     

    • supported

    Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

    Standard communication (FMS)

     

    • supported

    Yes; Via CP and loadable FB

    Open IE communication

     

    • ISO-on-TCP (RFC1006)

    Via CP 443-1 and loadable FB

    Web server

     

    • supported

    No

    Number of connections

     

    • overall

    120

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    -25 °C; = Tmin

    • max.

    70 °C; = Tmax

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Configuration

     

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Block encryption

    Yes; With S7 block Privacy

    Dimensions

     

    Width

    50 mm

    Height

    290 mm

    Depth

    219 mm

    Weights

     

    Weight, approx.

    900 g