    • For constructing a fail-safe automation system for plants with increased safety requirements
    • High-performance CPU in the top-end performance range
    • Complies with safety requirements to SIL 3 acc. to IEC 61508 and PL e acc. to ISO 13849.1
    • Standard and safety-related tasks can be performed with a single CPU
    • Multi-processor mode is possible
    • Safety-related communication with distributed I/O devices over PROFIBUS DP with the PROFIsafe profile
    • Fail-safe I/O modules can be connected decentralized over the integrated interfaces (DP and PN with CPU416F-3 PN/DP) and/or through communication modules (CP443-5 Ext. and CP443-1 Adv.)
    • Standard modules for non-safety-related applications can be operated centrally and decentralized

    Область применения

    The CPU 416F-2 and the CPU 416F-3 PN/DP are high-performance CPUs of the SIMATIC S7-400. They allow a fail-safe automation system to be constructed for plants with increased safety requirements.

    The integrated PROFIBUS DP interfaces of CPU 416F-2 support direct connection to the PROFIBUS DP fieldbus as a master or as a slave.

    Another DP master system can be connected in the case of the CPU 416F-3 PN/DP through the IF 964-DP interface module.

    The integrated PROFINET interface of the CPU 416F-3 PN/DP implements switch functionality by using the ERTEC 400 ASIC. This forms the basis for provision of 2 externally accessible PROFINET ports. This means that apart from hierarchic network topologies, line structures can also be implemented with the new S7-400 controllers.

    Note:
    Only interface module 6ES7964-2AA04-0AB0 can be used.

    Fail-safe I/O modules can be connected to all integrated interfaces, to IF 964-DP and/or through communication modules (CP443-5 Ext. and CP443-1 Advanced). Safety-related communication is performed over PROFIBUS DP with the PROFIsafe profile.

    Дизайн

    Both CPUs feature:

    • High-performance processor:
      The CPUs achieve instruction execution times as low as 0.03 µs per binary instruction.
    • CPU 416F-2: 8 MB main memory (of which 4 MB each for program or data);
      CPU 416F-3 PN/DP: 11.2 MB main memory (of which 5.6 MB each for program or data);
      fast main memory for parts of the user program that are significant for execution.
    • Flexible expansion possibilities:
      Max. 262144 digital, 16384 analog inputs/outputs
    • MPI multi-point interface:
      With the MPI it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 Mbps. The CPUs can establish up to 44 connections to stations of the communication bus (C bus) and the MPI.
    • Mode selector:
      Toggle switch design
    • Diagnostics buffer:
      The last 120 error and interrupt events are stored in a ring buffer for diagnostic purposes. The number of entries can be parameterized.
    • Real-time clock:
      Diagnostic alarms of the CPU are tagged with the date and time.
    • Memory card:
      To expand the integrated load memory. RAM and FEPROM cards (FEPROM for saving even at zero voltage).
    • Combined MPI/DP interface and integrated PROFIBUS DP interface (with CPU 416F-2):
      The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. The distributed I/O is treated like a central I/O from the point of view of the user (same configuring, addressing and programming).
      Mixed installation: SIMATIC S5 and SIMATIC S7 as PROFIBUS master acc. to EN 50170.

    CPU 416F-3 PN/DP also features:

    • Submodule socket:
      Using the IF 964-DP interface module, an additional PROFIBUS DP master system can be connected.
    • PROFINET interface with 2 ports (switch):
      • PROFINET IO, 256 IO devices can be connected
      • PROFINET CBA

    Failsafe I/O modules can be connected to all integrated interfaces, to IF 964-DP and/or via communication modules (CP443-5 Ext. and CP443-1 Advanced). Safety-related communication is performed over PROFIBUS DP with the PROFIsafe profile.

    Функции

    • Block protection:
      A password concept protects the user program from unauthorized access.
    • Integrated HMI services:
      For HMI devices, the user only has to specify the source and destination for the data. They are then cyclically transported by the system automatically.
    • Integrated communication functions:
      • PG/OP communication
      • Global data communication
      • S7 basic communication
      • S7 communication
    • Firmware update over the network

    CPU 416F-3 PN/DP additionally:

    • Open communication over TCP/IP, UDP and ISO-on-TCP (RFC1006)
    • Distributed intelligence in Component Based Automation (CBA) on PROFINET
    • Additional diagnostic option with integrated web server
    Parameterizable properties

    Using the STEP 7 hardware configuration tool, properties and responses of the S7-400 including the CPUs can be parameterized, e.g.:

    • MPI multi-point interface:
      • Determining station addresses.
      • Start-up/cyclic response.
      • Determining the maximum cycle time and communication load.
    • Address assignment:
      Addressing the I/O modules.
    • Retentive areas:
      Determining the number of retentive bit memories, counters, timers, data blocks and clock bit memories
    • Size of the process image, local data.
    • Length of the diagnostic buffer.
    • Protection level:
      Specifying the access rights to program and data.
    • System diagnostics:
      Determining handling and scope of the diagnostic alarms.
    • Cyclic interrupts:
      Setting of periodicity

    CPU 416F-3 PN/DP additionally:

    • PROFINET interface
    • Parameterization of time synchronization with NTP procedure
    Information and display functions
    • Status and error LEDs:
      LEDs indicate, for example, internal and external errors and operating states such as RUN, STOP, start-up and test functions.
    • Test functions:
      The PG is used to indicate signal states during program execution, to modify process variables independently of the user program, to output the contents of stack memories, to execute individual program steps, and to block program sections.
    • Information functions:
      The PG can be used to obtain information about the memory capacity and operating mode of the CPU and the current loading of the work and load memory.
    Communication

    The safety related and standard communication between the central controller and the fail-safe ET 200 modules takes place over PROFIBUS DP and/or PROFINET. The specially developed PROFIBUS profile PROFIsafe supports the transfer of user data for the safety functions within the standard data message frame. Additional hardware components, e.g. special safety buses are not required. The necessary software is either integrated in the hardware components as an expansion of the operating system or loaded into the CPU later as a certified software block.

    Mode of operation

    The safety functions of the F-CPU are included in the F program of the CPU and in the fail-safe signal modules.

    The signal modules monitor the output and input signals by means of discrepancy analysis and the injection of test signals.

    The CPU checks the proper operation of the controller by means of periodic self-tests, command tests and logic-based and time-based program execution checks. Furthermore, the I/O is checked using requests for signs of life.

    If an error is diagnosed in the system, the system will be placed in a safe state.

    An F runtime license is not required to operate the CPU 416F-2 and CPU 416F-3 PN/DP.

    Programming

    The CPU 416F-2 and the CPU 416F-3 PN/DP are programmed in the same manner as the other SIMATIC S7 systems. The user program for non-fail-safe plant sections is created using familiar programming tools, e.g. STEP 7.

    Option packages SIMATIC S7 Distributed Safety (Classic) and SIMATIC Safety Advanced V12 (TIA Portal V12)

    The STEP 7 option packages "SIMATIC S7 Distributed Safety" (Classic) or SIMATIC Safety Advanced V12 (TIA Portal V12) are required for programming the safety-related program sections. The packages contain all the functions and blocks required to create an F program.

    The F program with the safety functions is connected in F FBD or F LAD or using special functions from the F library. Use of F FBD or F LAD simplifies configuration and programming of the plant and also acceptance testing thanks to the non-plant-specific uniform presentation form. The programmer can concentrate on configuring the safety-related application without having to use additional tools. The STEP 7 option package "SIMATIC S7 Distributed Safety" is required for programming the safety-related program sections. The package contains all the functions and blocks required to create an F program.

    Технические данные

    Order number

    6ES7416-2FP07-0AB0

    6ES7416-3FS07-0AB0

    CPU 416F-2, MPI, PROFIBUS, 8 MB

    CPU416F-3 PN/DP, 16 MB, 3 INTERFACES

    General information

     

     

    Product type designation

    CPU 416F-2

    CPU416F-3 PN/DP

    Engineering with

     

     

    • Programming package

    STEP 7 V5.4 or higher with HSP 261

    STEP 7 V5.5 or higher with HSP 262

    Supply voltage

     

     

    Rated value (DC)

    • 24 V DC

    No; Power supply via system power supply

    No; Power supply via system power supply

    Power loss

     

     

    Power loss, typ.

    4.5 W

    6.5 W

    Memory

     

     

    Work memory

     

     

    • integrated

    8 Mbyte

    16 Mbyte

    • integrated (for program)

    4 Mbyte

    8 Mbyte

    • integrated (for data)

    4 Mbyte

    8 Mbyte

    Load memory

     

     

    • expandable FEPROM, max.

    64 Mbyte

    64 Mbyte

    • integrated RAM, max.

    1 Mbyte

    1 Mbyte

    • expandable RAM, max.

    64 Mbyte

    64 Mbyte

    CPU processing times

     

     

    for bit operations, typ.

    12.5 ns

    12.5 ns

    for word operations, typ.

    12.5 ns

    12.5 ns

    for fixed point arithmetic, typ.

    12.5 ns

    12.5 ns

    for floating point arithmetic, typ.

    25 ns

    25 ns

    Counters, timers and their retentivity

     

     

    S7 counter

     

     

    • Number

    2 048

    2 048

    IEC counter

     

     

    • present

    Yes

    Yes

    S7 times

     

     

    • Number

    2 048

    2 048

    IEC timer

     

     

    • present

    Yes

    Yes

    Data areas and their retentivity

     

     

    Flag

     

     

    • Number, max.

    16 kbyte; Size of bit memory address area

    16 kbyte; Size of bit memory address area

    Address area

     

     

    I/O address area

     

     

    • Inputs

    16 kbyte

    16 kbyte

    • Outputs

    16 kbyte

    16 kbyte

    Process image

     

     

    • Inputs, adjustable

    16 kbyte

    16 kbyte

    • Outputs, adjustable

    16 kbyte

    16 kbyte

    Time of day

     

     

    Clock

     

     

    • Hardware clock (real-time)

    Yes

    Yes

    Operating hours counter

     

     

    • Number

    16

    16

    Interfaces

     

     

    Interfaces/bus type

    1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

    1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

    Number of RS 485 interfaces

    2; Combined MPI / PROFIBUS DP and PROFIBUS DP

    1; Combined MPI / PROFIBUS DP

    Number of other interfaces

    1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

    1. Interface

     

     

    Interface type

    Integrated

    Integrated

    Physics

    RS 485 / PROFIBUS + MPI

    RS 485 / PROFIBUS + MPI

    Functionality

     

     

    • MPI

    Yes

    Yes

    • PROFIBUS DP master

    Yes

    Yes

    • PROFIBUS DP slave

    Yes

    Yes

    DP master

     

     

    • Number of DP slaves, max.

    32

    32

    2. Interface

     

     

    Interface type

    Integrated

    PROFINET

    Physics

    RS 485 / PROFIBUS

    Ethernet RJ45

    Interface types

     

     

    • Number of ports

    2

    Functionality

     

     

    • PROFINET IO Controller

    Yes

    • PROFINET IO Device

    Yes

    • PROFINET CBA

    Yes

    • PROFIBUS DP master

    Yes

    No

    • PROFIBUS DP slave

    Yes

    No

    DP master

     

     

    • Number of DP slaves, max.

    125

    3. Interface

     

     

    Interface type

    Pluggable interface module (IF)

    Plug-in interface modules

    IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

    Physics

    RS 485 / PROFIBUS

    Functionality

     

     

    • MPI

    No

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    Yes

    DP master

     

     

    • Number of DP slaves, max.

    125

    Isochronous mode

     

     

    Isochronous operation (application synchronized up to terminal)

    Yes; For PROFIBUS only

    Yes; Via PROFIBUS DP or PROFINET interface

    Communication functions

     

     

    PG/OP communication

    Yes

    Yes

    Data record routing

    Yes

    Yes

    Global data communication

     

     

    • supported

    Yes

    Yes

    S7 basic communication

     

     

    • supported

    Yes

    Yes

    S7 communication

     

     

    • supported

    Yes

    Yes

    S5 compatible communication

     

     

    • supported

    Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

    Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

    Standard communication (FMS)

     

     

    • supported

    Yes; Via CP and loadable FB

    Yes; Via CP and loadable FB

    Open IE communication

     

     

    • TCP/IP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    94

    • ISO-on-TCP (RFC1006)

    Via CP 443-1 and loadable FB

    Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

    • Number of connections, max.

    94

    • UDP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    94

    Web server

     

     

    • supported

    No

    Yes

    Number of connections

     

     

    • overall

    96

    96

    Standards, approvals, certificates

     

     

    Use in hazardous areas

     

     

    • ATEX

    ATEX II 3G Ex nA IIC T4 Gc

    ATEX II 3G Ex nA IIC T4 Gc

    Ambient conditions

     

     

    Ambient temperature during operation

     

     

    • min.

    0 °C

    0 °C

    • max.

    60 °C

    60 °C

    Configuration

     

     

    Know-how protection

     

     

    • User program protection/password protection

    Yes

    Yes

    • Block encryption

    Yes; With S7 block Privacy

    Yes; With S7 block Privacy

    Dimensions

     

     

    Width

    25 mm

    50 mm

    Height

    290 mm

    290 mm

    Depth

    219 mm

    219 mm

    Weights

     

     

    Weight, approx.

    700 g

    900 g