Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS extreme RAIL digital output modules

  • Заказные данные
    (2)
  • Информационные материалы

    Информационные материалы

    • 8 and 16-channel digital output modules
    • Approved in accordance with the railway standards EN 50155, EN 15121, EN 50124, EN 50125 and EN 45545 for use in rail traffic
    • For flexible adaptation of the controller to the corresponding task
    • For subsequent expansion of the system with additional outputs

    Область применения

    Digital output modules switch 24 V DC or 230 V AC voltages in the plant and thus transfer internal signals from the controller to the plant. Solenoid valves, DC contactors, and indicator lights can be connected.

    The output modules have settable parameters and diagnostic functions and can thus be adapted flexibly to the respective process requirements.

    Дизайн

    • Installation on the S7-1500 mounting rail using one single screw
    • Standardized 40-pin front connector using screw terminal or push-in technology
    • Standardized, harmonized front connector assignment for easier wiring
    • Connectable core cross-sections: 0.25 mm2 to 1.5 mm2 (AWG24 to 16)
    • Integrated potential bridges for flexible creation of potential groups
    • Front connector can be set to prewiring position
    • Front flap with expandable cable compartment, even if fully wired
    • Unambiguous labeling on front of module:
      • Module type
      • Article No.
      • Hardware and firmware version
      • Channel numbers labeling
      • Cabling diagram

    Included in the scope of delivery:

    • One labeling strip for manual labeling
    • One U connector
    • Printed front door

    Функции

    • Uniform display and diagnostics concept:
      • Module status display for ERROR (red LED) and RUN (green LED)
      • Channel status indicator for signal state log. “0” and log. "1" (green LED) or indication of short-circuit (red LED)
      • Display for monitoring the 24 V DC supply voltage (green LED)
    • Supported functions:
      • Identification and maintenance data IM0 to IM3
      • Firmware update
      • Channel-granular parameter assignment (HF modules only)
      • Channel-granular diagnostics (HF modules only)
      • Isochronous mode (dependent on the module)
      • Substitute values can be parameterized for the outputs

    Технические данные

    Order number

    6AG2522-1BH01-4AB0

    6AG2522-5HF00-1AB0

    SIPLUS S7-1500 DQ 16x24VDC HF TX RAIL

    SIPLUS S7-1500 DQ 8x230VAC ST 5A T1 RAIL

    General information

     

     

    Product type designation

    DQ 16x24VDC/0.5A HF

    DQ 8x230 V AC/5 A ST (relay)

    Product function

     

     

    • I&M data

    Yes; I&M0 to I&M3

    Yes; I&M0 to I&M3

    Operating mode

     

     

    • MSO

    Yes

    Supply voltage

     

     

    Type of supply voltage

    DC

    DC

    Rated value (DC)

    24 V

    24 V

    Reverse polarity protection

    Yes; through internal protection with 7 A per group

    Digital outputs

     

     

    Type of digital output

    Transistor

    Relays

    Number of digital outputs

    16

    8

    Current-sourcing

    Yes

    Digital outputs, parameterizable

    Yes

    Yes

    Short-circuit protection

    Yes; Clocked electronically

    Open-circuit detection

    Yes

    Limitation of inductive shutdown voltage to

    L+ (-53 V)

    Controlling a digital input

    Yes

    possible

    Switching capacity of the outputs

     

     

    • with resistive load, max.

    0.5 A

    • on lamp load, max.

    5 W

    1 500 W; 10 000 operating cycles

    • Low energy/fluorescent lamps with electronic control gear

    10x 58 W (25 000 operating cycles)

    • Fluorescent tubes, conventionally compensated

    1x 58 W (25 000 operating cycles)

    • Fluorescent tubes, uncompensated

    10x 58 W (25 000 operating cycles)

    Load resistance range

     

     

    • lower limit

    48 Ω

    • upper limit

    12 kΩ

    Output voltage

     

     

    • Type of output voltage

    DC

    • for signal "1", min.

    L+ (-0.8 V)

    Output current

     

     

    • for signal "1" rated value

    0.5 A

    5 A

    • for signal "0" residual current, max.

    0.5 mA

    0 A

    Output delay with resistive load

     

     

    • "0" to "1", max.

    100 µs

    • "1" to "0", max.

    100 µs; at rated load

    Parallel switching of two outputs

     

     

    • for logic links

    Yes

    Yes

    • for uprating

    Yes

    No

    • for redundant control of a load

    Yes

    Yes

    Switching frequency

     

     

    • with resistive load, max.

    100 Hz

    2 Hz

    • with inductive load, max.

    0.5 Hz; According to IEC 60947-5-1, DC-13

    0.5 Hz

    • on lamp load, max.

    10 Hz

    2 Hz

    Total current of the outputs

     

     

    • Current per channel, max.

    0.5 A; see additional description in the manual

    8 A; see additional description in the manual

    • Current per group, max.

    4 A; see additional description in the manual

    8 A; see additional description in the manual

    • Current per module, max.

    8 A; see additional description in the manual

    64 A; see additional description in the manual

    Relay outputs

     

     

    • Number of relay outputs

    8

    • Rated supply voltage of relay coil L+ (DC)

    24 V

    • Current consumption of relays (coil current of all relays), max.

    80 mA

    • external protection for relay outputs

    With miniature circuit breaker with characteristic B for: cos φ 1.0: 600 A cos φ 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1000 A

    • Contact connection (internal)

    No

    • Size of motor starters according to NEMA, max.

    5

    • Number of operating cycles, max.

    4 000 000; see additional description in the manual

    • Relay approved acc. to UL 508

    Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300

    Switching capacity of contacts

     

     

    • with inductive load, max.

    see additional description in the manual

    • with resistive load, max.

    see additional description in the manual

    Cable length

     

     

    • shielded, max.

    1 000 m

    1 000 m

    • unshielded, max.

    600 m

    600 m

    Isochronous mode

     

     

    Isochronous operation (application synchronized up to terminal)

    Yes

    No

    Execution and activation time (TCO), min.

    70 µs

    Bus cycle time (TDP), min.

    250 µs

    Interrupts/diagnostics/status information

     

     

    Diagnostics function

    Yes

    Yes

    Substitute values connectable

    Yes

    Yes

    Alarms

     

     

    • Diagnostic alarm

    Yes

    Yes

    Diagnostic messages

     

     

    • Monitoring the supply voltage

    Yes

    Yes

    • Wire-break

    Yes

    No

    • Short-circuit

    Yes

    No

    • Fuse blown

    No

    Diagnostics indication LED

     

     

    • RUN LED

    Yes; Green LED

    Yes; Green LED

    • ERROR LED

    Yes; Red LED

    Yes; Red LED

    • Monitoring of the supply voltage (PWR-LED)

    Yes; Green LED

    Yes; Green LED

    • Channel status display

    Yes; Green LED

    Yes; Green LED

    • for channel diagnostics

    Yes; Red LED

    No

    • for module diagnostics

    Yes; Red LED

    Yes; Red LED

    Potential separation

     

     

    Potential separation channels

     

     

    • between the channels and backplane bus

    Yes

    Yes

    Isolation

     

     

    Isolation tested with

    707 V DC (type test) and according to EN 50155 (routine test)

    Between the channels: 2 500 V DC; between the channels and backplane bus: 2 500 V DC; between L+ and backplane bus 707 V DC (type test) and according to EN 50155 (routine test)

    Standards, approvals, certificates

     

     

    Suitable for safety functions

    No

    No

    Suitable for safety-oriented group deactivation

    No

    Railway application

     

     

    • EN 50121-3-2

    Yes; EMC for rail vehicles

    Yes; EMC for rail vehicles

    • EN 50121-4

    Yes; EMC for signal and telecommunications systems

    Yes; EMC for signal and telecommunications systems

    • EN 50124-1

    Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

    Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

    • EN 50125-1

    Yes; Rail vehicles - see ambient conditions

    Yes; Rail vehicles - see ambient conditions

    • EN 50125-2

    Yes; Stationary electrical equipment - see ambient conditions

    Yes; Stationary electrical equipment - see ambient conditions

    • EN 50125-3

    Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

    Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

    • EN 50155

    Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2

    Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2

    • EN 61373

    Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

    Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

    • Fire protection acc. to EN 45545-2

    Yes; Rail vehicles - verification on request

    Yes; Rail vehicles - verification on request

    Ambient conditions

     

     

    Ambient temperature during operation

     

     

    • horizontal installation, min.

    -40 °C; = Tmin

    -25 °C; = Tmin

    • horizontal installation, max.

    70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A; +85 °C for 10 minutes (Tx acc. to EN 50155)

    60 °C; = Tmax; +70 °C for 10 min (T1 acc. to EN 50155)

    Extended ambient conditions

     

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against biologically active substances/conformity with EN 60721-3-5

    Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances/conformity with EN 60721-3-5

    Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

    Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances/conformity with EN 60721-3-5

    Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Decentralized operation

     

     

    Fast Startup supported

    Yes; 500 ms

    Prioritized startup

    Yes

    Dimensions

     

     

    Width

    35 mm

    35 mm

    Height

    147 mm

    147 mm

    Depth

    129 mm

    129 mm

    Weights

     

     

    Weight, approx.

    230 g

    350 g

    Other

     

     

    Note:

    For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776

    For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776