Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS S7-1500 CPU 1511-1 PN T1 RAIL

  • Заказные данные
    (1)
  • Аксессуары
    (6)
  • Информационные материалы

    Информационные материалы

    • Entry-level CPU in the SIPLUS extreme RAIL S7-1500 controller product range
    • Approved in accordance with the railway standards EN 50155, EN 15121, EN 50124, EN 50125 and EN 45545 for use in rail traffic
    • Suitable for applications with medium requirements for program scope and processing speed
    • PROFINET IO IRT interface with 2-port switch
    • PROFINET IO Controller for operating distributed I/O on PROFINET
    • PROFINET I-Device for connecting the CPU as an intelligent PROFINET device under a SIMATIC or non-Siemens PROFINET IO Controller
    • Isochronous mode
    • SIMATIC memory card required for operation of the CPU

    Область применения

    The SIPLUS S7-1500 CPU 1511-1 PN T1 RAIL is the most cost-effective entry-level CPU for applications with medium requirements for processing speed and speed of response. The CPU can be used as a PROFINET IO Controller or as distributed intelligence (PROFINET I-Device). The integrated PROFINET IO IRT interface is designed as a 2-port switch so that a linear topology can be set up. In addition, the CPU offers comprehensive control functionalities via easy-to-configure blocks as well as the ability to connect drives via standardized PLC-open blocks.

    Дизайн

    The SIPLUS S7-1500 CPU 1511-1 PN T1 RAIL has:

    • A powerful processor:
      The CPU achieves command execution times as low as 60 ns per binary instruction.
    • A large work memory:
      150 KB for program, 1 MB for data
    • SIMATIC Memory Cards as load memory;
      permit additional functions such as datalog and archives
    • Flexible expansion capability:
      single-tier configuration with max. 32 modules (CPU + 31 modules)
    • PROFINET IO IRT interface for connecting distributed I/O via PROFINET

    Функции

    • Performance
      • Faster command processing, depending on the CPU type, language extensions and new data types
      • Even shorter response times of the CPUs due to considerably faster backplane bus
      • Powerful network connection:
        each CPU is equipped with PROFINET IO IRT (2-port switch) as standard interface.
    • Integrated technology
      • Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)
      • Support of speed-controlled and positioning axes as well as external encoders, positionally precise gearing between axes.
      • Trace functions for all CPU tags, both for diagnostics in real time as well as for sporadic error detection
      • Comprehensive control functionalities, e.g. easily configurable blocks for automatic optimization of the control parameters for optimum control quality
    • Security Integrated
      • Password-based know-how protection against unauthorized read-out and modification of program blocks
      • Copy protection for tying individual blocks to the serial number of the SIMATIC Memory Card: The block can only run if the configured memory card is inserted into the CPU.
      • 4-level authorization concept:
        Communication to the HMI devices can also be restricted.
      • Manipulation protection:
        The controller recognizes changed or unauthorized transmissions of the engineering data.
    • Integrated system diagnostics
      • System diagnostics information is displayed consistently and in plain text in the TIA Portal, HMI devices and Web server, even for messages from the drives, and is updated even if the CPU is in STOP mode.
      • Integrated into the firmware of the CPU, no special configuration is required
    • SIMATIC Memory Card (required for operation of the CPU)
      • Used as a plug-in load memory or for updating the firmware.
      • Also for storing additional documents or csv files (for recipes and archives)
      • Creation of data blocks for storage/reading of data via SFCs of the user program
    • Datalog (archives) and recipes
      • Storage of csv files for recipes and archives on the SIMATIC Memory Card;
        easy access to plant-relevant operating data using Office tools or via a Web server
      • Easy access to machine configuration data by means of a Web browser or SD card reader (two-way data exchange from and to the controller)
    • Programming
      • Programming with STEP 7 Professional

    Технические данные

    Order number

    6AG2511-1AK01-1AB0

    SIPLUS S7-1500 CPU 1511-1 PN T1 RAIL

    General information

     

    Product type designation

    CPU 1511-1 PN

    Supply voltage

     

    Type of supply voltage

    24 V DC

    Power loss

     

    Power loss, typ.

    5.7 W

    Memory

     

    Work memory

     

    • integrated (for program)

    150 kbyte

    • integrated (for data)

    1 Mbyte

    Load memory

     

    • Plug-in (SIMATIC Memory Card), max.

    32 Gbyte

    CPU processing times

     

    for bit operations, typ.

    60 ns

    for word operations, typ.

    72 ns

    for fixed point arithmetic, typ.

    96 ns

    for floating point arithmetic, typ.

    384 ns

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    2 048

    IEC counter

     

    • Number

    Any (only limited by the main memory)

    S7 times

     

    • Number

    2 048

    IEC timer

     

    • Number

    Any (only limited by the main memory)

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    16 kbyte

    Address area

     

    I/O address area

     

    • Inputs

    32 kbyte; All inputs are in the process image

    • Outputs

    32 kbyte; All outputs are in the process image

    Time of day

     

    Clock

     

    • Type

    Hardware clock

    1. Interface

     

    Interface types

     

    • Number of ports

    2

    • integrated switch

    Yes

    • RJ 45 (Ethernet)

    Yes; X1

    Functionality

     

    • PROFINET IO Controller

    Yes

    • PROFINET IO Device

    Yes

    • SIMATIC communication

    Yes

    • Open IE communication

    Yes

    • Web server

    Yes

    • Media redundancy

    Yes

    Protocols

     

    Supports protocol for PROFINET IO

    Yes

    PROFIsafe

    No

    PROFIBUS

    No

    Number of connections

     

    • Number of connections, max.

    96; via integrated interfaces of the CPU and connected CPs / CMs

    PROFINET IO Controller

     

    Services

     

    • Number of connectable IO Devices, max.

    128; In total, up to 256 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET

    • Of which IO devices with IRT, max.

    64

    • Number of connectable IO Devices for RT, max.

    128

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    Yes; With minimum OB 6x cycle of 625 µs

    Supported technology objects

     

    Motion Control

    Yes; Note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER

    Controller

    • PID_Compact

    Yes; Universal PID controller with integrated optimization

    • PID_3Step

    Yes; PID controller with integrated optimization for valves

    • PID-Temp

    Yes; PID controller with integrated optimization for temperature

    Counting and measuring

    • High-speed counter

    Yes

    Isolation

     

    Isolation tested with

    707 V DC (type test) and according to EN 50155 (routine test)

    Standards, approvals, certificates

     

    Railway application

     

    • EN 50121-3-2

    Yes; EMC for rail vehicles

    • EN 50121-4

    Yes; EMC for signal and telecommunications systems

    • EN 50124-1

    Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

    • EN 50125-1

    Yes; Rail vehicles - see ambient conditions

    • EN 50125-2

    Yes; Stationary electrical equipment - see ambient conditions

    • EN 50125-3

    Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

    • EN 50155

    Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2

    • EN 61373

    Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

    • Fire protection acc. to EN 45545-2

    Yes; Rail vehicles - verification on request

    Ambient conditions

     

    Ambient temperature during operation

     

    • horizontal installation, min.

    -40 °C; = Tmin

    • horizontal installation, max.

    60 °C; = Tmax; +70 °C for 10 min (T1 acc. to EN 50155)

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against biologically active substances/conformity with EN 60721-3-5

    Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances/conformity with EN 60721-3-5

    Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances/conformity with EN 60721-3-5

    Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Configuration

     

    Programming

     

    Programming language

     

    • LAD

    Yes

    • FBD

    Yes

    • STL

    Yes

    • SCL

    Yes

    • GRAPH

    Yes

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Copy protection

    Yes

    • Block protection

    Yes

    Access protection

     

    • Password for display

    Yes

    • Protection level: Write protection

    Yes

    • Protection level: Read/write protection

    Yes

    • Protection level: Complete protection

    Yes

    Dimensions

     

    Width

    35 mm

    Height

    147 mm

    Depth

    129 mm

    Weights

     

    Weight, approx.

    430 g

    Other

     

    Note:

    For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776