    • Transceiver for the transition from a redundant PROFIBUS DP master system to a single-channel PROFIBUS DP master system
    • To connect devices with a single PROFIBUS DP interface to the redundant PROFIBUS DP master system of the SIMATIC S7-400H

    Область применения

    The Y-Link is a transceiver for the transition from a redundant PROFIBUS master system to a single-channel PROFIBUS DP master system. It is used to connect devices with a single PROFIBUS DP interface as switched I/O to S7-400H.

    Дизайн

    The Y-link comprises:

    • 2 IM 153-2 High Feature Outdoor interface modules
    • 1 Y coupler
    • 1 BM IM/IM bus module
    • 1 BM Y-coupler bus module

    Snapped on mounting rails for setup with active bus modules.

    Configuration options and limitations

    A redundant PROFIBUS DP master system can be extended by means of Y links in the following way:

    • The number of Y links on a redundant DP master system is only limited by the maximum number of stations. The maximum number of connectable slaves depends on the length of the user data and configuration message frames. The total length of each may not exceed 244 bytes (see slave technical data). Generally, the following applies:
      • Max. 64 stations in the lower-level DP master system
      • Max. 236 slots in the lower-level DP master system
    • Y link configuration and user data message frames comprise message frame contents of the lower-level slaves. The maximum frame length is therefore 244 bytes.
    • Direct communication and equidistance not possible in the lower-level master system

    Функции

    Y link

    • Transmission rates for the redundant master system:
      9.6 Kbit/s to 12 Mbit/s
    • Bumpless switchover of the redundant PROFIBUS DP master system's active channel.
    • Supports system changes on a SIMATIC S7-400H during operation
    • Diagnostics via LEDs and the user program

    Y coupler

    • Transmission rates for the lower-level master system (independent of redundant DP master system):
      187.5 Kbit/s to 12 Mbit/s
    • Electrical isolation between lower-level DP master system and power supply via the coupler
    • IP20 degree of protection
    Principle of operation

    The Y link maps the lower-level DP master system on the redundant PROFIBUS DP master system as a switched PROFIBUS DP slave .

    The Y coupler and the lower-level DP master system form an independent bus system and operate decoupled from the redundant bus system.

    The Y link as a DP slave on the redundant DP master system acts as a proxy for the stations on the lower-level DP master system with regard to data.

    Configuration

    The Y link can be configured with STEP 7 as of Version 5.4. It is not necessary to configure the Y coupler.

    When STEP 7 calculates the bus parameters, the stations connected on the lower-level DP master system as well as the Y link itself are taken into account.

    Parameter assignment of the DP slaves

    The redundant DP master system assigns the parameters for the DP slaves in the lower-level DP master system via the Y link.

    Технические данные

    Order number

    6ES7153-2BA70-0XB0

    ET200M, INTERFACE IM153-2 HF OUTDOOR

    General information

     

    Vendor identification (VendorID)

    801Eh

    Supply voltage

     

    Rated value (DC)

    • 24 V DC

    Yes

    permissible range (ripple included), lower limit (DC)

    20.4 V

    permissible range (ripple included), upper limit (DC)

    28.8 V

    external protection for power supply lines (recommendation)

    2,5 A

    Mains buffering

     

    • Mains/voltage failure stored energy time

    5 ms

    Input current

     

    Current consumption, max.

    650 mA

    Inrush current, typ.

    3 A

    I²t

    0.1 A²·s

    Output current

     

    for backplane bus (5 V DC), max.

    1.5 A

    Power loss

     

    Power loss, typ.

    5.5 W

    Address area

     

    Addressing volume

     

    • Inputs

    244 byte

    • Outputs

    244 byte

    Hardware configuration

     

    Number of modules per DP slave interface, max.

    12

    Time stamping

     

    Accuracy

    1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules

    Number of message buffers

    15

    Messages per message buffer

    20

    Number of stampable digital inputs, max.

    128; Max. 128 signals/station; max. 32 signals/slot

    Time format

    RFC 1119

    Time resolution

    0.466 ns

    Time interval for transmitting the message buffer if a message is present

    1 000 ms

    Time stamp on signal change

    rising / falling edge as signal entering or exiting

    Interfaces

     

    Interface physics, RS 485

    Yes

    Interface physics, FOC

    No

    PROFIBUS DP

     

    • Node addresses

    1 to 125 permitted

    • automatic detection of transmission rate

    Yes

    • Output current, max.

    70 mA

    • Transmission rate, max.

    12 Mbit/s

    • Transmission procedure

    RS 485

    • SYNC capability

    Yes

    • FREEZE capability

    Yes

    • Direct data exchange (slave-to-slave communication)

    Yes; as publisher with all IO, as subscriber with F-IO only

    • Connector type

    9-pin sub D

    1. Interface

     

    DP slave

     

    • GSD file

    SI05801E.GSG

    • automatic baud rate search

    Yes

    Protocols

     

    Bus protocol/transmission protocol

    PROFIBUS DP to EN 50170

    Isolation

     

    Isolation tested with

    Isolation voltage 500 V

    Degree and class of protection

     

    Degree of protection acc. to EN 60529

    • IP20

    Yes

    Air pressure acc. to IEC 60068-2-13

     

    • Installation altitude above sea level, max.

    3 000 m

    Configuration

     

    Configuration software

     

    • STEP 7

    Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file

    Dimensions

     

    Width

    40 mm

    Height

    125 mm

    Depth

    117 mm

    Weights

     

    Weight, approx.

    360 g


    Order number

    6ES7197-1LB00-0XA0

    Y-COUPLER F. BUILDING Y-LINK, REDUNDANT

    General information

     

    Requirements for DP master system

     

    • Length of parameter assignment telegram

    244 byte

    Supply voltage

     

    Design of the power supply

    via bus module

    permissible range, lower limit (DC)

    20.4 V

    permissible range, upper limit (DC)

    28.8 V

    Interfaces

     

    PROFIBUS DP

     

    Properties of the lower-level DP master system

     

    • Transmission rate, max.

    12 Mbit/s; 45.45 kbit/s to 12 Mbit/s

    • Termination of lower-level DP master system

    Active terminating resistor (Bus Terminator)

    • Use of OLM/OBT

    Yes

    • Use of RS 485 repeaters, max.

    9

    • Number of DP slaves, max.

    31; 64 when using RS 485 repeaters or OLM/OBT

    Protocols

     

    PROFIBUS DP

    Yes

    Interrupts/diagnostics/status information

     

    Status indicator

    No

    Alarms

    No

    Diagnostic functions

    Yes

    Potential separation

     

    to lower-level DP master system

    Yes

    Dimensions

     

    Width

    40 mm

    Height

    125 mm

    Depth

    130 mm

    Weights

     

    Weight, approx.

    200 g