Товаров
  
корзина пуста
  • Каталог оборудования Siemens

CPU 414H

  • Заказные данные
    (3)
  • Аксессуары
    (30)
  • Информационные материалы

    Информационные материалы

    • CPU for SIMATIC S7-400H and S7-400F/FH
    • Can be used in S7-400H high-availability systems
    • Can be used with F runtime license as F-capable CPU in S7-400F/FH safety-related systems
    • With integrated PROFIBUS DP master and combined MPI/PROFIBUS DP master interface
    • With integrated PROFINET interface (2-port switch)
    • Features 2 slots for sync modules

    Область применения

    The CPU 414-5H can be used for the SIMATIC S7-400H and S7-400F/FH. It enables the establishment of an S7-400H high-availability system. It can also be used for the S7-400F/FH fail-safe automation system in conjunction with the F runtime license.

    The integrated PROFIBUS DP interfaces enable direct connection as master to the PROFIBUS DP fieldbus.

    The integrated PROFINET interface with switch functionality forms the basis for providing 2 externally accessible PROFINET ports. In this way, linear or ring structures can be implemented.

    Дизайн

    The CPU 414-5H has:

    • A powerful processor:
      The CPU achieves command execution times as low as 18.75 ns per binary command.
    • 4 MB main memory (2 MB for programs, 2 MB for data);
      load memory for user programs and configuration data for the S7-400H F/FH automation system; fast main memory for subroutines of the user program that are relevant to the process
    • A memory card:
      For expanding the integrated load memory. In addition to the program itself, the information contained in the load memory also includes configuration data for the S7-400H F/FH, which is why it requires about twice as much memory space. The result is that:
      • The integrated load memory is not sufficient for large programs, which is why the memory card is often required.
        RAM and FEPROM cards are available (FEPROM for saving data even when power supply is disconnected).
    • Flexible expansion options:
      Up to 131 072 digital and 81 932 analog inputs/outputs.
    • Multi-point interface MPI:
      The MPI enables the creation of a simple network with up to 32 nodes and a data transfer rate of 187.5 kbit/s. The CPU can establish up to 64 connections to nodes on the communication bus (C bus) and the MPI.
      Note:
      If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:
      • With socket: 6ES7 972-0BB42-0XA0
      • Without socket: 6ES7 972-0BA42-0XA0
    • PROFIBUS DP interface:
      The PROFIBUS DP interface allows a redundant, distributed automation configuration offering high speed and ease of use. From the user's point of view, the distributed I/Os are treated like centralized I/Os (same configuring, addressing and programming).
    • PROFINET interface with 2 ports (switch):
      Support of system redundancy and MRP (Media Redundancy Protocol)
    • Mode selector:
      Designed as a toggle switch.
    • Diagnostics buffer:
      The last 120 alarm and interrupt events are stored in a ring buffer for diagnostic purposes.
    • Real-time clock:
      Diagnostics reports from the CPU are provided with the date and time.
    • PROFIBUS DP interface:
      The CPU 414-5H with PROFIBUS DP master interface enables distributed automation to be established at high speed and with easy operation. From the user's point of view, the distributed I/Os are treated like centralized I/Os (same configuring, addressing and programming).
      Note:
      If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:
      • With socket: 6ES7 972-0BB42-0XA0
      • Without socket: 6ES7 972-0BA42-0XA0

    Функции

    • Block protection:
      In addition to the keylock switch, a password concept protects the user program from unauthorized access. User blocks can also be protected by an encryption process.
    • Integrated HMI services:
      In the case of HMI devices, the user only has to specify the source and destination of the data. These are automatically transferred cyclically by the system.
    • Integrated communications functions:
      • PG/OP communication
      • Extended communication (simple and high-availability)
    • Master-spare switchover programmed by user.
    Parameterizable properties

    With the STEP 7 tool "Hardware Configuration" and the installed option package S7-400H, the properties and behavior of the S7-400H including the CPUs can be parameterized, e.g.:

    • Multi-point interface MPI:
      • Determining node addresses.
      • Startup/cyclic behavior.
      • Definition of maximum cycle time and communication load.
    • Address assignment:
      Addressing of the I/O modules.
    • Retentive areas:
      Definition of the number of retentive bit memories, counters, timers, data blocks and clock memories.
    • Protection level:
      Definition of access authorization to program and data.
    • System diagnostics:
      Determination of handling and scope of diagnostics messages.
    • Watchdog interrupts:
      Setting the periodicity.
    • Configuring of H stations.
    Safety-related functions

    With the F runtime license, the safety-related F user program can be compiled and run on the CPU. One license is required for each S7-400F/FH system. The scope of delivery includes 2 TÜV (German technical inspectorate) adhesive labels.

    Display and information functions
    • Status and fault indicators:
      LEDs indicate, for example, internal and external faults and operating statuses such as RUN, STOP, startup, "Master" operating mode, redundancy errors, and test function.
    • Test functions:
      The programming device can be used to display signal states in the program execution sequence, modify process variables independently of the user program, output contents of stack memories, run through program steps individually, and disable program sections.
    • Information functions:
      The user can obtain information about the memory capacity and operating mode of the CPU, and the current utilization of the RAM and load memory.

    Технические данные

    Order number

    6ES7414-5HM06-0AB0

    CPU414-5H PN/DP, 4MB F. S7-400H/F/FH

    General information

     

    Product type designation

    CPU 414-5H PN/DP

    Engineering with

     

    • Programming package

    As of STEP 7 V5.5 SP2 with HF1

    Supply voltage

     

    Rated value (DC)

    • 24 V DC

    No; Power supply via system power supply

    Power loss

     

    Power loss, typ.

    7.5 W

    Memory

     

    Work memory

     

    • integrated

    4 Mbyte

    • integrated (for program)

    2 Mbyte

    • integrated (for data)

    2 Mbyte

    Load memory

     

    • expandable FEPROM, max.

    64 Mbyte

    • integrated RAM, max.

    512 kbyte

    • expandable RAM, max.

    64 Mbyte

    CPU processing times

     

    for bit operations, typ.

    18.75 ns

    for word operations, typ.

    18.75 ns

    for fixed point arithmetic, typ.

    18.75 ns

    for floating point arithmetic, typ.

    37.5 ns

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    2 048

    IEC counter

     

    • present

    Yes

    S7 times

     

    • Number

    2 048

    IEC timer

     

    • present

    Yes

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    8 192 byte

    Address area

     

    I/O address area

     

    • Inputs

    8 kbyte

    • Outputs

    8 kbyte

    Process image

     

    • Inputs, adjustable

    8 kbyte

    • Outputs, adjustable

    8 kbyte

    Time of day

     

    Clock

     

    • Hardware clock (real-time)

    Yes

    Operating hours counter

     

    • Number

    16

    Interfaces

     

    Number of RS 485 interfaces

    2

    Number of other interfaces

    2; Fiber-optic interface

    1. Interface

     

    Interface type

    Integrated

    Physics

    RS 485 / PROFIBUS + MPI

    Functionality

     

    • MPI

    Yes

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    No

    DP master

     

    • Number of DP slaves, max.

    32

    2. Interface

     

    Interface type

    PROFINET

    Physics

    Ethernet RJ45

    Interface types

     

    • Number of ports

    2

    Functionality

     

    • PROFINET IO Controller

    Yes

    • PROFINET IO Device

    No

    • PROFINET CBA

    No

    • PROFIBUS DP master

    No

    • PROFIBUS DP slave

    No

    3. Interface

     

    Interface type

    Integrated

    Physics

    RS 485 / PROFIBUS

    Functionality

     

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    No

    DP master

     

    • Number of DP slaves, max.

    96

    4. Interface

     

    Interface type

    Pluggable synchronization submodule (FO)

    Plug-in interface modules

    Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

    5. Interface

     

    Interface type

    Pluggable synchronization submodule (FO)

    Plug-in interface modules

    Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    No

    Communication functions

     

    PG/OP communication

    Yes

    Data record routing

    Yes

    S7 routing

    Yes

    Global data communication

     

    • supported

    No

    S7 basic communication

     

    • supported

    No

    S7 communication

     

    • supported

    Yes

    S5 compatible communication

     

    • supported

    Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

    Standard communication (FMS)

     

    • supported

    Yes; Via CP and loadable FB

    Open IE communication

     

    • TCP/IP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    62

    • ISO-on-TCP (RFC1006)

    Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

    • Number of connections, max.

    62

    • UDP

    Yes; via integrated PROFINET interface and loadable FBs

    • Number of connections, max.

    62

    Web server

     

    • supported

    No

    Number of connections

     

    • overall

    64

    Configuration

     

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Block encryption

    Yes; With S7 block Privacy

    Dimensions

     

    Width

    50 mm

    Height

    290 mm

    Depth

    219 mm

    Weights

     

    Weight, approx.

    995 g