Товаров
  
корзина пуста
  • Каталог оборудования Siemens

IO-Link master module for ET 200pro

  • Информационные материалы

    Информационные материалы

    For more information, follow the navigation bar.

    Технические данные

    Order number

    6ES7147-4JD00-0AB0

    ET200pro, EM 4 IO-Link HF

    Supply voltage

     

    Rated value (DC)

    24 V

    Reverse polarity protection

    Yes

    Load voltage 2L+

     

    • Rated value (DC)

    24 V

    • Short-circuit protection

    Yes

    • Reverse polarity protection

    Yes; against destruction; load increasing

    Input current

     

    from supply voltage 1L+, max.

    40 mA

    from load voltage 2L+ (without load), max.

    20 mA

    from backplane bus 3.3 V DC, max.

    20 mA

    Encoder supply

     

    Number of outputs

    4

    Short-circuit protection

    Yes; per module, electronic

    Output current

     

    • up to 55 °C, max.

    2 A

    Power loss

     

    Power loss, typ.

    2.6 W

    IO-Link

     

    Number of ports

    4

    • of which simultaneously controllable

    4

    IO-Link protocol 1.0

    Yes

    IO-Link protocol 1.1

    Yes

    Transmission rate

    4.8 kBaud (COM1); 38.4 kBaud (COM2), 230.4 kBaud (COM3)

    Size of process data, input per port

    32 byte

    Size of process data, input per module

    32 byte

    Size of process data, output per port

    32 byte

    Size of process data, output per module

    32 byte

    Memory size for device parameter

    2 kbyte; for each port

    Master backup

    Possible with function block IO_LINK_MASTER

    Cable length unshielded, max.

    20 m

    Operating modes

     

    • IO-Link

    Yes

    • DI

    Yes

    • DQ

    Yes; max. 100 mA

    Connection of IO-Link devices

     

    • Port type A

    Yes; via 3-core cable

    • Port type B

    Yes; Additional device supply: for X1 and X2 max. 2 A in total, for X3 and X4 max. 2 A in total

    Interrupts/diagnostics/status information

     

    Diagnostic functions

    Yes

    Alarms

     

    • Diagnostic alarm

    Yes

    Diagnostic messages

     

    • Diagnostic information readable

    Yes

    • Wire-break

    Yes

    • Short-circuit

    Yes

    Diagnostics indication LED

     

    • Channel status display

    Yes; One green LED for channel status Qn (SIO mode) and port status IO-Ln (IO-Link mode)

    • Group error SF (red)

    Yes

    • Channel fault indicator F (red)

    Yes; combined with the IO-Link port status

    Parameter

     

    Diagnostics wire break

    channel by channel

    Diagnostics short-circuit

    channel by channel

    Potential separation

     

    between the load voltages

    Yes

    between backplane bus and all other circuit components

    Yes

    Potential separation channels

     

    • between the channels

    No

    Isolation

     

    Isolation tested with

    707 V DC (type test)

    Dimensions

     

    Width

    45 mm

    Height

    130 mm

    Depth

    35 mm

    Weights

     

    Weight, approx.

    150 g