Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS extreme RAIL analog input modules

  • Заказные данные
    (2)
  • Информационные материалы

    Информационные материалы

    • 8-channel analog input modules
    • Approved in accordance with the railway standards EN 50155, EN 15121, EN 50124, EN 50125 and EN 45545 for use in rail traffic.
    • Optionally with extremely short conversion times
    • For the connection of analog sensors without additional amplifiers
    • Even solves more complex automation tasks

    Область применения

    Analog input modules record process signals such as pressure or temperature and forward them in digitalized format (16-bit format) to the control. They are suitable for measuring current (2-wire and 4-wire transducers), voltage, and resistance, as well as for the connection of resistance thermometers and thermocouples (measurement types depend on the module).

    Дизайн

    • Installation on the S7-1500 mounting rail using one single screw
    • Standardized 40-pin front connector using screw terminal or push-in technology
    • Connectable core cross-sections: 0.25 mm2 to 1.5 mm2 (AWG24 to 16), regardless of the front connector used
    • Front connector can be set to prewiring position
    • Front flap with expandable cable compartment, even if fully wired
    • Integrated shielding concept
    • Unambiguous labeling on front of module:
      • Module type
      • Article No.
      • Hardware and firmware version
      • Channel numbers labeling
      • Cabling diagram

    Included in the scope of delivery:

    • Infeed element, shield clamp, and shield terminal
    • One labeling strip for manual labeling
    • One U connector
    • Printed front door

    Функции

    • Uniform display and diagnostics concept:
      • Module status display for ERROR (red LED) and RUN (green LED)
      • Channel status display (channel activated or deactivated, green LED) or diagnostics display (red LED)
      • Display for monitoring the 24 V DC supply voltage (green LED)
    • Supported functions:
      • Consistently high resolution of 16 bits
      • Identification and maintenance data IM0 to IM3
      • Firmware update
      • Channel-specific parameter assignment
      • Hardware interrupts; two upper and two lower limits can be parameterized
      • Channel-granular diagnostics (depends on measurement type/measuring range)
      • Isochronous mode (dependent on the module)
      • Calibration during runtime

    Технические данные

    Order number

    6AG2531-7NF10-1AB0

    6AG2531-7KF00-1AB0

    SIPLUS S7-1500 AI 8xU/I HS T1 RAIL

    SIPLUS S7-1500 AI 8xU/I/RTD/TC T1 RAIL

    General information

     

     

    Product type designation

    AI 8xU/I HS

    AI 8xU/I/RTD/TC ST

    Product function

     

     

    • I&M data

    Yes; I&M0 to I&M3

    Yes; I&M0 to I&M3

    • Measuring range scalable

    No

    Operating mode

     

     

    • Oversampling

    No

    • MSI

    Yes

    CiR – Configuration in RUN

     

     

    Reparameterization possible in RUN

    Yes

    Yes

    Calibration possible in RUN

    Yes

    Yes

    Supply voltage

     

     

    Type of supply voltage

    DC

    DC

    Rated value (DC)

    24 V

    24 V

    Reverse polarity protection

    Yes

    Analog inputs

     

     

    Number of analog inputs

    8

    8

    • For current measurement

    8

    8

    • For voltage measurement

    8

    8

    • For resistance/resistance thermometer measurement

    4

    • For thermocouple measurement

    8

    permissible input voltage for voltage input (destruction limit), max.

    28.8 V

    28.8 V

    permissible input current for current input (destruction limit), max.

    40 mA

    40 mA

    Technical unit for temperature measurement adjustable

    Yes

    Input ranges (rated values), voltages

     

     

    • 1 V to 5 V

    Yes

    Yes

    • -1 V to +1 V

    Yes

    • -10 V to +10 V

    Yes

    Yes

    • -2.5 V to +2.5 V

    Yes

    • -250 mV to +250 mV

    Yes

    • -5 V to +5 V

    Yes

    Yes

    • -50 mV to +50 mV

    Yes

    • -500 mV to +500 mV

    Yes

    • -80 mV to +80 mV

    Yes

    Input ranges (rated values), currents

     

     

    • 0 to 20 mA

    Yes

    Yes

    • -20 mA to +20 mA

    Yes

    Yes

    • 4 mA to 20 mA

    Yes

    Yes

    Input ranges (rated values), thermocouples

     

     

    • Type B

    Yes

    • Type E

    Yes

    • Type J

    Yes

    • Type K

    Yes

    • Type N

    Yes

    • Type R

    Yes

    • Type S

    Yes

    • Type T

    Yes

    Input ranges (rated values), resistance thermometer

     

     

    • Ni 100

    Yes; Standard/climate

    • Ni 1000

    Yes; Standard/climate

    • LG-Ni 1000

    Yes; Standard/climate

    • Pt 100

    Yes; Standard/climate

    • Pt 1000

    Yes; Standard/climate

    • Pt 200

    Yes; Standard/climate

    • Pt 500

    Yes; Standard/climate

    Input ranges (rated values), resistors

     

     

    • 0 to 150 ohms

    Yes

    • 0 to 300 ohms

    Yes

    • 0 to 600 ohms

    Yes

    • 0 to 6000 ohms

    Yes

    • PTC

    Yes

    Thermocouple (TC)

     

     

    Temperature compensation

     

     

    • parameterizable

    Yes

    Cable length

     

     

    • shielded, max.

    800 m

    800 m; for U/I, 200 m for R/RTD, 50 m for TC

    Analog value generation for the inputs

     

     

    Integration and conversion time/resolution per channel

     

     

    • Resolution with overrange (bit including sign), max.

    16 bit

    • Basic execution time of the module (all channels released)

    62.5 µs; independent of number of activated channels

    Smoothing of measured values

     

     

    • parameterizable

    Yes

    Encoder

     

     

    Connection of signal encoders

     

     

    • for voltage measurement

    Yes

    Yes

    • for current measurement as 2-wire transducer

    Yes

    Yes

    • Burden of 2-wire transmitter, max.

    820 Ω

    820 Ω

    • for current measurement as 4-wire transducer

    Yes

    Yes

    • for resistance measurement with two-wire connection

    Yes; Only for PTC

    • for resistance measurement with three-wire connection

    Yes; All measuring ranges except PTC; internal compensation of the cable resistances

    • for resistance measurement with four-wire connection

    Yes; All measuring ranges except PTC

    Errors/accuracies

     

     

    Basic error limit (operational limit at 25 °C)

     

     

    • Voltage, relative to input range, (+/-)

    0.2 %

    0.1 %

    • Current, relative to input range, (+/-)

    0.2 %

    0.1 %

    • Resistance, relative to input range, (+/-)

    0.1 %

    • Resistance thermometer, relative to input range, (+/-)

    Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K

    • Thermocouple, relative to input range, (+/-)

    Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K

    Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

     

     

    • Series mode interference (peak value of interference < rated value of input range), min.

    40 dB

    • Common mode voltage, max.

    10 V

    10 V

    • Common mode interference, min.

    60 dB; at 400 Hz: 50 dB

    60 dB

    Isochronous mode

     

     

    Isochronous operation (application synchronized up to terminal)

    Yes

    Filtering and processing time (TCI), min.

    80 µs

    Bus cycle time (TDP), min.

    250 µs

    Interrupts/diagnostics/status information

     

     

    Diagnostics function

    Yes

    Yes

    Alarms

     

     

    • Diagnostic alarm

    Yes

    Yes

    • Limit value alarm

    Yes; two upper and two lower limit values in each case

    Yes; two upper and two lower limit values in each case

    Diagnostic messages

     

     

    • Monitoring the supply voltage

    Yes

    Yes

    • Wire-break

    Yes; only for 1 ... 5 V and 4 ... 20 mA

    Yes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD

    • Overflow/underflow

    Yes

    Yes

    Diagnostics indication LED

     

     

    • RUN LED

    Yes; Green LED

    • ERROR LED

    Yes; Red LED

    • Monitoring of the supply voltage (PWR-LED)

    Yes; Green LED

    Yes; Green LED

    • Channel status display

    Yes; Green LED

    Yes; Green LED

    • for channel diagnostics

    Yes; Red LED

    Yes; Red LED

    • for module diagnostics

    Yes; Red LED

    Yes; Red LED

    Potential separation

     

     

    Potential separation channels

     

     

    • between the channels and backplane bus

    Yes

    Yes

    Isolation

     

     

    Isolation tested with

    707 V DC (type test) and according to EN 50155 (routine test)

    707 V DC (type test) and according to EN 50155 (routine test)

    Standards, approvals, certificates

     

     

    Railway application

     

     

    • EN 50121-3-2

    Yes; EMC for rail vehicles

    Yes; EMC for rail vehicles

    • EN 50121-4

    Yes; EMC for signal and telecommunications systems

    Yes; EMC for signal and telecommunications systems

    • EN 50124-1

    Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

    Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

    • EN 50125-1

    Yes; Rail vehicles - see ambient conditions

    Yes; Rail vehicles - see ambient conditions

    • EN 50125-2

    Yes; Stationary electrical equipment - see ambient conditions

    Yes; Stationary electrical equipment - see ambient conditions

    • EN 50125-3

    Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

    Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

    • EN 50155

    Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2

    Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2

    • EN 61373

    Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

    Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

    • Fire protection acc. to EN 45545-2

    Yes; Rail vehicles - verification on request

    Yes; Rail vehicles - verification on request

    Ambient conditions

     

     

    Ambient temperature during operation

     

     

    • horizontal installation, min.

    -40 °C; = Tmin; Startup @ -25 °C

    -40 °C; = Tmin; Startup @ -25 °C

    • horizontal installation, max.

    70 °C; = Tmax; > +60 °C max. 4x ±20 mA or 4x ±10 V permissible

    70 °C; = Tmax; > +60 °C max. 2x ±20 mA or 4x ±10 V or 4x RTD permissible

    Extended ambient conditions

     

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against biologically active substances/conformity with EN 60721-3-5

    Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances/conformity with EN 60721-3-5

    Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

    Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances/conformity with EN 60721-3-5

    Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

    Decentralized operation

     

     

    Fast Startup supported

    No

    Prioritized startup

    No

    Dimensions

     

     

    Width

    35 mm

    35 mm

    Height

    147 mm

    147 mm

    Depth

    129 mm

    129 mm

    Weights

     

     

    Weight, approx.

    200 g

    310 g

    Other

     

     

    Note:

    For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776