    The SIMATIC CP 1543-1 communications processor securely connects the new SIMATIC S7-1500 controller to Industrial Ethernet networks. By combining a variety of security features such as an SPI (Stateful Packet Inspection) firewall, VPN and data encryption protocols such as FTPS and SNMPv3, the communications processor protects individual S7-1500 stations or even entire automation cells against unauthorized access.

    The CP can also be used for linking the S7-1500 station into an IPv6-based network. All functions are configured by means of STEP 7 Professional V12 (TIA Portal) or higher.

    The CP 1543-1 supports the following communications services:

    • PG/OP communication
    • S7 communication
    • Open communication (SEND/RECEIVE, FETCH/WRITE)
    • IT communication
      • FTP functions (File Transfer Protocol FTP/FTPS) for file management and access to data blocks in the CPU (client and server function)
      • Sending e-mails via SMTP or ESMTP with "SMTP-Auth" for authentication on an e-mail server (also with IPv6)
    • Security functions
      • Stateful Packet Inspection (layers 3 and 4) firewall
      • Secure communication via VPN (IPsec)
      • Secure access to the Web server of the CPU via the HTTPS protocol
      • Secure file transfer using FTPS
      • Secure transfer of the time of day (NTP)
      • SNMPv3 for tap-proof transfer of network analysis information
    • Integration of the S7-1500 into IPv6-based networks;
      An IPv6-compliant IP address can be used for the following communication services:
      • FETCH/WRITE access (CP as server)
      • FTP server mode
      • FTP client mode with addressing by program block
      • E-mail transfer with addressing by program block

    Note

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Область применения

    The CP 1543-1 is used to connect the SIMATIC S7-1500 to Industrial Ethernet networks. With its own processor, it relieves the CPU of communications tasks and facilitates additional connections.

    The CP 1543-1 provides communication options with:

    • PGs/PCs,
    • master computers
    • operator control and monitoring systems,
    • other SIMATIC S5/S7 systems.

    This can be used to protect the SIMATIC S7-1500 from unauthorized access from an Ethernet network. The CP 1543-1 allows safe remote access via a LAN and allows data transfer between devices or network segments to be protected from data manipulation/espionage.

    Protection of the SIMATIC S7-1500 system from unauthorized access from the Industrial Ethernet network

    Дизайн

    The CP 1543-1 features all the advantages of the SIMATIC S7-1500 design:

    • Compact design:
      • One RJ45 jack for connecting to Industrial Ethernet;
        automatic data rate detection using autosensing, autocrossing and autonegotiation;
        the connection is made via the IE FC RJ45 Plug 180 with 180° cable outlet or via a standard patch cable
      • The module is supplied with power via the integrated backplane bus
      • Three LEDs for displaying the operational and communications status of the module and one LED under the front cover for the Ethernet interface to display ACTIVITY and LINK.
    • Simple installation:
      The CP 1543-1 is mounted on the rail of the S7-1500 and connected to the adjacent modules by means of the bus connectors.
    • The CP 1543-1 can be operated without a fan; no backup battery is required.
    • The module can be replaced without the need for a programming device.

    Функции

    • Gigabit interface with RJ45 connector with 10/100/1000 Mbps full/half duplex with autosensing functionality
    • Communication services:
      • Open communication (TCP/IP, UDP, ISO):
        Multicast with UDP
      • PG/OP communication: Inter-network with S7 routing
      • S7 communication (client, server)
      • IT communication:
        HTTP communication grants access to the web server of the S7-1500 system. With the CP 1543-1, HTTPS communication is also possible.
        The e-mail client function allows e-mails to be sent directly from the user program.
        FTP communication allows program-controlled FTP client communication.
        Access to data blocks in the CPU via FTP server.
      • IP address assignment using DHCP with IPv4 or by entering the address directly in the engineering software
        STEP 7 Professional V12 (TIA Portal) or higher
    • Diagnostics and network management:
      • Extensive diagnostic functions for all modules in the S7-1500 system
      • Integration in network management systems due to support of SNMP V1/V3
    • Security mechanisms:
      • Access protection with firewall for filtering connections on the basis of their IP and MAC addresses
      • Secure communication via VPN (IPsec)
      • Encrypted HTML pages using SSL (HTTPS)
      • Secure file transfer (FTPS)
      • Tap-proof transfer of network analysis information to the network management system (SNMPv3)
      • Secure transfer of the time of day (NTP)
      • Certification as per the Achilles Level II Standard
        http://www.wurldtech.com/product_services/certifications/certified_products/
    • Configuration of all functions with STEP 7 Professional V14 (TIA Portal) or higher
    • Module replacement without programming device: All information can be stored on the memory card of the CPU.

    Интеграция

    Connection to a higher-level network with network separation and access protection (firewall function)

    Connection to higher-level network and network separation of automation cells

    Особенности

    • Reachability of the SIMATIC S7-1500 station from an IPv6-based infrastructure
    • Optimum support of maintenance due to
      • Simple diagnostics via the central Web server
      • Remote programming via LAN
      • Monitoring with IT network management tools (SNMP)
      • Module replacement without a PG
    • Securing the system against unauthorized access with
      • Central access protection for any S7 station
      • Secure access to the central Web server
    • Network separation for setting up identical machines with the same IP address
    • Simple alerting by e-mail and transfer of production data to master computer using FTP
    • Protection of investment thanks to simple integration of the SIMATIC S7-1500 system in existing networks with SIMATIC S7-300 / S7-400 / S5 via Industrial Ethernet using the CP 1543-1

    Технические данные

    Order number

    6GK7543-1AX00-0XE0

    Product type designation

    CP 1543-1

    Transmission rate

     

    Transfer rate

     

    • at the 1st interface

    10 ... 1 000 Mbit/s

    Interfaces

     

    Number of interfaces acc. to Industrial Ethernet

    1

    Number of electrical connections

     

    • at the 1st interface acc. to Industrial Ethernet

    1

    Type of electrical connection

     

    • at the 1st interface acc. to Industrial Ethernet

    RJ45 port

    Supply voltage, current consumption, power loss

     

    Type of voltage of the supply voltage

    DC

    Supply voltage 1 from backplane bus

    15 V

    Relative symmetrical tolerance at DC

     

    • at 15 V

    3 %

    Consumed current

     

    • from backplane bus at DC at 15 V typical

    0.35 A

    Power loss [W]

    5.3 W

    Permitted ambient conditions

     

    Ambient temperature

     

    • for vertical installation during operation

    0 ... 40 °C

    • for horizontally arranged busbars during operation

    0 ... 60 °C

    • during storage

    -40 ... +70 °C

    • during transport

    -40 ... +70 °C

    Relative humidity at 25 °C without condensation during operation maximum

    95 %

    Protection class IP

    IP20

    Design, dimensions and weight

     

    Module format

    Compact module S7-1500 single width

    Width

    35 mm

    Height

    142 mm

    Depth

    129 mm

    Net weight

    0.35 kg

    Mounting type

     

    • S7-1500 rail mounting

    Yes

    Product properties, functions, components general

     

    Number of units

     

    • per CPU maximum

    8

    • Note

    depending on CPU type

    Performance data open communication

     

    Number of possible connections for open communication

     

    • by means of T blocks maximum

    118; depending on the system upper limit

    Amount of data

     

    • as user data per ISO on TCP connection for open communication by means of T blocks maximum

    65 536 byte

    Number of Multicast stations

    118

    Performance data S7 communication

     

    Number of possible connections for S7 communication

     

    • maximum

    118

    • Note

    depending on the system upper limit

    Performance data multi-protocol mode

     

    Number of active connections with multi-protocol mode

    118

    Performance data IT functions

     

    Number of possible connections

     

    • as client by means of FTP maximum

    32

    • as server by means of FTP maximum

    16

    • as server by means of HTTP maximum

    4

    • as e-mail client maximum

    1

    Amount of data as user data for email maximum

    64 Kibyte

    Performance data telecontrol

     

    Protocol is supported

     

    • TCP/IP

    Yes

    Product function MIB support

    Yes

    Protocol is supported

     

    • SNMP v1

    Yes

    • DCP

    Yes

    • LLDP

    No

    Configuration software

     

    • required

    STEP 7 Professional V12 (TIA Portal) or higher

    Identification & maintenance function

     

    • I&M0 - device-specific information

    Yes

    • I&M1 – higher-level designation/location designation

    Yes

    Product functions Diagnosis

     

    Product function Web-based diagnostics

    Yes; yes, via S7-1500 CPU

    Product functions Routing

     

    Product function

     

    • Static IP routing

    Yes

    • Static IP routing IPv6

    No

    • dynamic IP routing

    No

    • dynamic IP routing IPv6

    No

    Protocol is supported

     

    • RIP v1

    No

    • RIPv2

    No

    • RIPnG for IPv6

    No

    • OSPFv2

    No

    • OSPFv3 for IPv6

    No

    • VRRP

    No

    • VRRP for IPv6

    No

    • BGP

    No

    • PPP

    No

    • PPoE via DSL

    No

    Product functions Security

     

    Firewall version

    stateful inspection

    Product function with VPN connection

    IPSec

    Type of encryption algorithms with VPN connection

    AES-256, AES-192, AES-128, 3DES-168, DES-56

    Type of authentication procedure with VPN connection

    Preshared key (PSK), X.509v3 certificates

    Type of hashing algorithms with VPN connection

    MD5, SHA-1

    Number of possible connections with VPN connection

    16

    Product function

     

    • password protection for Web applications

    No

    • ACL - IP-based

    No

    • ACL - IP-based for PLC/routing

    No

    • switch-off of non-required services

    Yes

    • Blocking of communication via physical ports

    No

    • log file for unauthorized access

    Yes

    Product functions Time

     

    Product function SICLOCK support

    Yes

    Product function pass on time synchronization

    Yes

    Protocol is supported

     

    • NTP

    Yes


    Дальнейшая информация

    You will find more information on SIMATIC S7-1500 at http://www.siemens.com/simatic-s7-1500

    The SIMATIC NET Selection Tool is available to assist in selecting the right Industrial Ethernet switches as well as the configuration of modular variants:

    Online version:
    http://www.siemens.com/snst

    Offline version:
    http://www.siemens.com/snst-download

    You will find more information on the topic of Industrial Security on the Internet at:

    http://www.siemens.com/industrialsecurity