Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS fail-safe CPUs

  • Заказные данные
    (2)
  • Аксессуары
    (14)
  • Информационные материалы

    Информационные материалы

    The fail-safe SIPLUS S7-1200 Controllers are based on the S7-1200 standard CPUs and offer additional safety-related functions.

    They can be used for safety-oriented tasks according to IEC 61508 up to SIL 3 and ISO 13849-1 up to PL e.

    Safety-related programs are created in the TIA Portal. The STEP 7 Safety engineering tool offers commands, operations and blocks for safety-related programs in the LAD and FBD languages. To this end, there is a library with pre-configured, TÜV-approved blocks for safety-related functions.

    • Standard controller with integrated safety functions:
      • Standardized and convenient diagnostic functions for standard and safety
      • Uniform symbols, data consistency, ...
    • Modular system with scalable range of CPUs and expandable I/O quantity structure:
      • One engineering for standard and fail-safe automation
      • Use of the standard I/O modules together with the fail-safe I/O modules in the central system
      • Integrated standard PROFINET functionalities for PROFINET controllers and PROFINET iDevice services
      • Connection of distributed standard I/O via field bus such as PROFINET or PROFIBUS
      • F-library certified by the German Technical Inspectorate (TÜV) for all common safety functions
      • Free programming of the safety logic using FBD and LAD
      • Standard-compliant printout of the F-program
    • One integrated engineering for both standard and safety from S7-1200 to S7-300/400/1500 and WinAC RTX F:
      • STEP 7 Safety Basic for easy engineering of the CPU 1200 FC
      • STEP 7 Safety Advanced for the entire fail-safe SIMATIC S7 portfolio
    • Integrated system diagnosis of the CPUs, for standard and safety:
      • Consistent plain text display of system diagnostic information in the TIA Portal, HMI and web server
      • Messages are updated even if the CPU is in STOP state
      • System diagnostics integrated in the CPU firmware. Configuration by user not required
      • The diagnostics is automatically updated on configuration changes.
    • 2 fail-safe compact controllers with graded performances in the versions DC/DC/DC and DC/DC/relay

    Characteristics

    SIPLUS CPU 1214 FC

    Variants

    DC/DC/DC, DC/DC/relay

    Main memory, integrated

    125 KB

    Load memory, integrated

    4 MB

    Memory card

    SIMATIC memory card (optional)

    Standard digital inputs/outputs, integrated

    14/10

    Standard analog inputs, integrated

    2

    Standard analog outputs, integrated

    -

    Process image

    1024 bytes for inputs, 1024 bytes for outputs

    Expansion by signal board

    Max. 1

    Expansion by signal modules

    Max. 8

    Expansion by communication modules

    Max. 3



    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the corresponding standard products. SIPLUS extreme-specific information was added.

    Область применения

    SIMATIC S7-1200 is the ideal controller for local and distributed automation solutions with safety requirements in the central system.

    Via the engineering, the fail-safe SIMATIC S7-1200 makes preassembled, tested and TÜV-certified blocks available for implementing all common safety functions, such as emergency stop or protective door monitoring with or without interlocking.

    • CPU 1212FC:
      The ideal compact solution for standard and fail-safe applications
    • CPU 1214 FC:
      The compact CPU for standard and fail-safe applications
    • CPU 1215 FC:
      The compact CPU with two PROFINET ports for standard and fail-safe applications

    Дизайн

    Mechanical features

    • Horizontal or vertical mounting on DIN rail or direct mounting in the cabinet using integral drill holes (not horizontal).
    • Terminal block for independent wiring for all CPUs and associated components.

    Технические данные

    Order number

    6AG1214-1AF40-5XB0

    6AG1214-1HF40-5XB0

    SIPLUS S7-1200 CPU 1214FC DC/DC/DC

    SIPLUS S7-1200 CPU 1214FC DC/DC/RLY

    General information

     

     

    Product type designation

    CPU 1214FC DC/DC

    CPU 1214FC DC/DC/Relay

    Supply voltage

     

     

    Rated value (DC)

    • 24 V DC

    Yes

    Yes

    Encoder supply

     

     

    24 V encoder supply

     

     

    • 24 V

    L+ minus 4 V DC min.

    L+ minus 4 V DC min.

    Power loss

     

     

    Power loss, typ.

    12 W

    12 W

    Memory

     

     

    Work memory

     

     

    • integrated

    125 kbyte

    125 kbyte

    Load memory

     

     

    • integrated

    4 Mbyte

    4 Mbyte

    • Plug-in (SIMATIC Memory Card), max.

    with SIMATIC memory card

    with SIMATIC memory card

    Backup

     

     

    • without battery

    Yes

    Yes

    CPU processing times

     

     

    for bit operations, typ.

    0.08 µs; / instruction

    0.08 µs; / Operation

    for word operations, typ.

    1.7 µs; / instruction

    1.7 µs; / Operation

    for floating point arithmetic, typ.

    2.3 µs; / Operation

    2.3 µs; / instruction

    Address area

     

     

    I/O address area

     

     

    • Inputs

    1 024 byte

    1 024 byte

    • Outputs

    1 024 byte

    1 024 byte

    Process image

     

     

    • Inputs, adjustable

    1 024 byte

    1 024 byte

    • Outputs, adjustable

    1 024 byte

    1 024 byte

    Time of day

     

     

    Clock

     

     

    • Hardware clock (real-time)

    Yes

    Yes

    Digital inputs

     

     

    Number of digital inputs

    14

    14

    • of which inputs usable for technological functions

    6; HSC (High Speed Counting)

    6; HSC (High Speed Counting)

    Digital outputs

     

     

    Number of digital outputs

    10

    10; Relays

    • of which high-speed outputs

    4; 100 kHz Pulse Train Output

    Analog inputs

     

     

    integrated channels (AI)

    2; 0 to 10V

    2; 0 to 10V

    Input ranges

     

     

    • Voltage

    Yes; 0 to 10V

    Yes; 0 to 10V

    1. Interface

     

     

    Interface type

    PROFINET

    PROFINET

    Physics

    Ethernet

    Ethernet

    Functionality

     

     

    • PROFINET IO Controller

    Yes

    Yes

    • PROFINET IO Device

    Yes

    Yes

    Communication functions

     

     

    S7 communication

     

     

    • supported

    Yes

    Yes

    Open IE communication

     

     

    • TCP/IP

    Yes

    Yes

    • ISO-on-TCP (RFC1006)

    Yes

    Yes

    • UDP

    Yes

    Yes

    Web server

     

     

    • supported

    Yes

    Yes

    Integrated Functions

     

     

    Number of counters

    6

    6

    Counting frequency (counter) max.

    100 kHz

    100 kHz

    Frequency meter

    Yes

    Yes

    controlled positioning

    Yes

    Yes

    PID controller

    Yes

    Yes

    Number of alarm inputs

    4

    4

    Number of pulse outputs

    4

    4

    Limit frequency (pulse)

    100 kHz

    Ambient conditions

     

     

    Ambient temperature during operation

     

     

    • min.

    -25 °C; = Tmin

    -25 °C; = Tmin

    • max.

    55 °C; = Tmax

    55 °C; = Tmax

    Extended ambient conditions

     

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Pollutant concentrations

     

     

    • SO2 at RH < 60% without condensation

    S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

    S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

    Resistance

     

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Configuration

     

     

    Programming

     

     

    Programming language

     

     

    • LAD

    Yes; incl. failsafe

    Yes; incl. failsafe

    • FBD

    Yes; incl. failsafe

    Yes; incl. failsafe

    • SCL

    Yes

    Yes

    Dimensions

     

     

    Width

    110 mm

    110 mm

    Height

    100 mm

    100 mm

    Depth

    75 mm

    75 mm

    Weights

     

     

    Weight, approx.

    415 g

    435 g


    Дальнейшая информация

    Brochures

    Information material for downloading can be found on the Internet: