Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS CPU 1512SP F-1 PN

  • Заказные данные
    (1)
  • Аксессуары
    (2)
  • Информационные материалы

    Информационные материалы

    • SIPLUS CPU 1512SP F-1 PN for SIPLUS ET 200SP based on S7-1500 CPU 1513F-1 PN
    • For applications with medium requirements in terms of program scope and processing speed, for distributed configurations via PROFINET IO or PROFIBUS DP.
    • Increase in availability of systems and machines
    • Supports PROFIsafe in centralized and distributed configurations
    • PROFINET IO controller for up to 128 IO devices
    • PROFINET I-Device for connecting the CPU as an intelligent PROFINET device with a SIMATIC or third-party PROFINET I/O controller
    • PROFINET Shared I-Device for 4 controllers
    • PROFINET IO IRT interface with integrated 3-port switch
    • Isochronous mode on PROFINET
    • With multiple communication options:
      PG/OP communication, PROFINET IO, open IE communication (TCP, ISO-on-TCP and UDP), Web server and S7 communication (with loadable FBs)
    • Optional PROFIBUS master for 125 PROFIBUS DP slaves (with CM DP module 6ES7545-5DA00-0AB0)
    • Configuration control (option handling)
    • Integrated motion control functionalities for controlling speed-controlled and positioning axes, support for external encoders

    Note

    SIMATIC memory card required for operation of the CPU.

    The bus adapter is not included in the scope of supply and must be ordered separately.

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the corresponding standard products. SIPLUS extreme-specific information was added.

    Область применения

    The CPU 1512SP F-1 PN is the CPU for standard and fail-safe applications with medium requirements in terms of processing performance and response speed in discrete production technology. The CPU 1512SP F-1 PN can be used as a PROFINET IO controller or as distributed intelligence (PROFINET I-Device). The integrated PROFINET IO IRT interface is designed as a 3-port switch so that a linear topology can be set up in the system via port 1 and 2, and so that a PG/PC or HMI device can also be connected via port 3.

    When used as an I-Device, the CPU 1512SP F-1 PN enables distributed preprocessing of process data locally and only delivers the information actually required to the higher-level controller. This has the following advantages:

    • Offloading of central controller
    • Short response times to critical local signals
    • Less load on the bus system due to smaller data volumes
    • Faster set-up thanks to pretested units and parallel commissioning
    • Increased availability and flexibility due to autonomous machine units
    • Clear-cut configuration

    The CPU 1512SP F-1 PN operates completely independently of the central controller. If it fails, the CPU 1512SP F-1 PN simply continues running.

    The bit-modular configuration of the ET 200SP I/O system, together with the CPU 1512SP F-1 PN, enables functionally oriented station configuration.

    In addition, the CPU offers comprehensive control functionalities via easy-to-configure blocks as well as the ability to connect drives via standardized PLC-open blocks.

    Дизайн

    The CPU 1512SP F-1 PN is snapped directly onto the standard mounting rail and has the following:

    • A powerful processor:
      The CPU achieves command execution times as low as 48 ns per binary instruction.
    • Large work memory:
      300 KB for program, 1 MB for data.
    • SIMATIC memory cards as load memory;
      permitting additional functions such as firmware update, datalog and archives.
    • Bit-modular expandability for maximum flexibility;
      up to 64 I/O modules (I/O, technology, and communication modules) in any combination. Station width up to 1 m.
    • PROFINET IO IRT interface with 3 integrated switch ports:
      • Port 1 and 2 via BusAdapter (the CPU 1512SP F-1 PN is supplied without a BusAdapter and can also be operated without one). The appropriate BusAdapter (BA 2xRJ45 or BA 2xFC) is to be ordered separately if needed).
      • Port 3 via integrated RJ45 socket.
    • Integrated communication functions:
      • PG/OP communication
      • PROFINET IO
      • Open IE communication (TCP, ISO-on-TCP and UDP)
      • Web server
      • S7 communication
      • S7 routing
      • Data record routing
    • Maintenance-free data backup without battery
    • Diagnostics displays for errors (Error), operation (RUN/Stop), maintenance (MT), power supply (PWR) and one link LED per port
    • Optional labeling using light gray or yellow labeling strips. There is a choice of 2 materials:
      • Foil and roll with 500 strips, for thermal transfer roll printer
      • Paper (280 g/m2), DIN A4 sheets with 100 strips each, for laser printer
    • The ET 200SP CPU can be equipped with a reference ID label.
    • Different connection types of PROFINET by means of BusAdapter
      • Under standard ambient conditions, BA 2xRJ45 for connection via RJ45 plug
      • In the case of mechanical loading during operation and/or increased EMC requirements, BA 2xFC for direct connection of the PROFINET cable
    • Dark BaseUnit as first BaseUnit behind the ET200SP CPU when using an AC I/O module or an AI Energy Meter ST as the first I/O module

    Scope of supply

    CPU 1512SP F-1 PN including server module, 24 V DC connector and cover for BusAdapter port (BusAdapter must be ordered separately)

    Функции

    • Performance
      • High-speed command processing
      • High-performance network connection:
        CPU comes equipped with a PROFINET IO IRT interface (3-port switch) as standard.
    • Integrated technology
      • Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)
      • Support of speed-controlled and positioning axes as well as external encoders
      • Precise position gearing for synchronous operation between axes
      • Trace functions for all CPU variables, both for diagnostics in real time as well as for sporadic error detection
      • Comprehensive control functionalities, e.g. easily configurable blocks for automatic optimization of the control parameters for optimum control quality
    • Isochronous mode
      • Synchronous coupling of distributed signal acquisition, signal transmission, and program execution to the PROFINET cycle with constant bus cycle time
    • Security Integrated
      • Password-based know-how protection against unauthorized read-out and modification of program blocks
      • Copy protection for tying individual blocks to the serial number of the SIMATIC memory card:
        The block can only run if the configured memory card is inserted into the CPU.
      • 4-stage authorization concept:
        Communication to HMI devices can also be restricted.
      • Manipulation protection:
        The controller recognizes changed or unauthorized transmissions of the engineering data.
    • Integrated system diagnostics
      • System diagnostics information is displayed consistently and in plain text in TIA Portal, HMI devices and Web server, even for messages from the drives, and updated even if the CPU is in STOP mode.
      • Integrated into the firmware of the CPU, no special configuration is required
    • Configuration control (option handling) in central setup
      • Various hardware configurations can be stored in the controller:
        Modification of the configuration in the user program (startup OB100)
        Retrofitting of options at end of configuration
        Use of placeholder modules is possible.
    • SIMATIC memory card (required for operation of the CPU)
      • Used as a plug-in load memory or for updating the firmware
      • Also for storing additional documents or .csv files (for recipes and archives)
      • Creation of data blocks for storage/reading of data via SFCs of the user program
    • Datalog (archives) and recipes
      • Storage of .csv files for recipes and archives on the SIMATIC memory card;
        easy access to plant-relevant operating data using Office tools or via a Web server.
      • Easy access to machine configuration data by means of a Web browser or SD card reader (two-way data exchange from and to the controller)
    • Programming of the standard program section
      • Programming with STEP 7 Professional, V13 SP1 and higher
    • Programming of the fail-safe program section
      • Programming of the safety-related program section with the "STEP 7 Safety Advanced" option package

    Технические данные

    Order number

    6AG1512-1SK01-2AB0

    SIPLUS ET 200SP CPU 1512SP F-1PN

    General information

     

    Product type designation

    CPU 1512SP F-1 PN

    Engineering with

     

    • STEP 7 TIA Portal configurable/integrated as of version

    V13 SP1 Update 4

    Supply voltage

     

    Type of supply voltage

    24 V DC

    Power loss

     

    Power loss, typ.

    5.6 W

    Memory

     

    Work memory

     

    • integrated (for program)

    300 kbyte

    • integrated (for data)

    1 Mbyte

    Load memory

     

    • Plug-in (SIMATIC Memory Card), max.

    32 Gbyte

    CPU processing times

     

    for bit operations, typ.

    48 ns

    for word operations, typ.

    58 ns

    for fixed point arithmetic, typ.

    77 ns

    for floating point arithmetic, typ.

    307 ns

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    2 048

    IEC counter

     

    • Number

    Any (only limited by the main memory)

    S7 times

     

    • Number

    2 048

    IEC timer

     

    • Number

    Any (only limited by the main memory)

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    16 kbyte

    Address area

     

    I/O address area

     

    • Inputs

    32 kbyte; All inputs are in the process image

    • Outputs

    32 kbyte; All outputs are in the process image

    Address space per module

     

    • Address space per module, max.

    32 byte; For input and output data respectively

    Address space per station

     

    • Address space per station, max.

    1 280 byte; for central inputs and outputs; depending on configuration

    Time of day

     

    Clock

     

    • Type

    Hardware clock

    1. Interface

     

    Interface types

     

    • Number of ports

    3; 1. integr. + 2. via BusAdapter

    • integrated switch

    Yes

    • RJ 45 (Ethernet)

    Yes; X1

    • BusAdapter (PROFINET)

    Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC

    Functionality

     

    • PROFINET IO Controller

    Yes

    • PROFINET IO Device

    Yes

    • SIMATIC communication

    Yes

    • Open IE communication

    Yes

    • Web server

    Yes

    • Media redundancy

    Yes

    2. Interface

     

    Interface types

     

    • Number of ports

    1

    • RS 485

    Yes; Via CM DP module

    Functionality

     

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    Yes

    • SIMATIC communication

    Yes

    Protocols

     

    Number of connections

     

    • Number of connections, max.

    88

    PROFINET IO Controller

     

    Services

     

    • Number of connectable IO Devices, max.

    128; In total, up to 253 distributed I/O devices can be connected via PROFIBUS or PROFINET

    • Of which IO devices with IRT, max.

    64

    • Number of connectable IO Devices for RT, max.

    128

    PROFIBUS DP master

     

    Services

     

    • Number of DP slaves

    125

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    Yes; Only with PROFINET; with minimum OB 6x cycle of 625 µs

    Supported technology objects

     

    Motion Control

    Yes

    • Speed-controlled axis

    • Number of speed-controlled axes, max.

    6; Max. number of speed-controlled axes (requirement: there must be no other motion technology objects created)

    • Positioning axis

    • Number of positioning axes, max.

    6; Max. number of positioning axes (requirement: there must be no other motion technology objects created)

    • Synchronized axes (relative gear synchronization)

    • Number of axes, max.

    3; Max. number of synchronous axes (requirement: there must be no other motion technology objects created)

    • External encoders

    • Number of external encoders, max.

    6; Max. number of external encoders (requirement: there must be no other motion technology objects created)

    Controller

    • PID_Compact

    Yes; Universal PID controller with integrated optimization

    • PID_3Step

    Yes; PID controller with integrated optimization for valves

    • PID-Temp

    Yes; PID controller with integrated optimization for temperature

    Counting and measuring

    • High-speed counter

    Yes

    Ambient conditions

     

    Ambient temperature during operation

     

    • horizontal installation, min.

    -25 °C; = Tmin

    • horizontal installation, max.

    60 °C; = Tmax

    • vertical installation, min.

    -25 °C; = Tmin

    • vertical installation, max.

    50 °C; = Tmax

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Configuration

     

    Programming

     

    Programming language

     

    • LAD

    Yes; incl. failsafe

    • FBD

    Yes; incl. failsafe

    • STL

    Yes

    • SCL

    Yes

    • GRAPH

    Yes

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Copy protection

    Yes

    • Block protection

    Yes

    Access protection

     

    • Protection level: Write protection

    Yes

    • Protection level: Read/write protection

    Yes

    • Protection level: Complete protection

    Yes

    Dimensions

     

    Width

    100 mm

    Height

    117 mm

    Depth

    75 mm

    Weights

     

    Weight, approx.

    310 g