SM 1238 Energy Meter 480 V AC analog input module

  • Заказные данные
    (1)
  • Аксессуары
    (4)
  • Информационные материалы

    Информационные материалы

    • Energy management based on SIMATIC S7-1200
    • Data acquisition of electrical characteristics in 1 and 3-phase networks up to 480 V AC
    • Direct connection of voltage inputs
    • Current measurement performed by 1 A and 5 A current transformers
    • Can be used in TN and TT networks
    • Data backup of measurement data in the event of a power failure

    Область применения

    The SM 1238 Energy Meter 480 V AC is designed for use at machine level in an S7-1200 system. It registers various electrical and other measured values. This makes it possible to acquire transparency about the energy requirements of individual components of the production system starting at the machine-level.

    The measured values provided by the SM 1238 Energy Meter 480 V AC can be used to determine energy requirements, power consumption and efficiency as well as make demand forecasts. Measurement data about power consumption are vital for load management and maintenance. They can also be used for emission reporting and calculating the CO2 footprint.

    Дизайн

    The signal modules have the same design features as the basic units.

    • Installation on DIN rails:
      The modules are snapped onto the rail next to the CPU on the right and are electrically and mechanically connected to each other and to the CPU by the integral slide mechanism.
    • Direct installation:
      Horizontal or vertical mounting on DIN rail or direct mounting in the cabinet using integral lugs.

    Функции

    • Measurement of electrical variables from one, two or three-phase supply networks
    • Max. nominal voltage between two line conductors 480 V AC
    • Retentive storage of counter readings
    • Detection of:
      • Voltages
      • Currents
      • Phase angles
      • Services
      • Energy / electrical work
      • Frequencies
      • Minimum and maximum values
      • Performance factors
      • Operating hours

    The module supports the following system functions:

    • Firmware update
    • Calibration during runtime
    • I&M identification data
    • Reconfiguration in RUN
    • Diagnostics and hardware interrupts

    Технические данные

    Order number

    6ES7238-5XA32-0XB0

    SM 1238 Energy Meter 480V AC

    General information

     

    Product type designation

    SM 1238 AI Energy Meter 480 VAC

    Product function

     

    • Voltage measurement

    Yes

    • Voltage measurement with voltage transformers

    Yes

    • Current measurement

    Yes

    • Phase current measurement without current transformers

    No

    • Phase current measurement with current transformers

    Yes

    • Energy measurement

    Yes

    • Frequency measurement

    Yes

    • Power measurement

    Yes

    • Active power measurement

    Yes

    • Reactive power measurement

    Yes

    • I&M data

    Yes; I&M 0

    • Isochronous mode

    No

    Engineering with

     

    • STEP 7 TIA Portal configurable/integrated as of version

    V13 SP1

    Operating mode

     

    • cyclic measurement

    Yes

    • acyclic measurement

    Yes

    • Acyclic measured value access

    Yes

    • Fixed measured value sets

    Yes

    • Freely definable measured value sets

    Yes

    CiR – Configuration in RUN

     

    Reparameterization possible in RUN

    Yes

    Calibration possible in RUN

    Yes

    Installation type/mounting

     

    Mounting position

    Horizontal, vertical

    Supply voltage

     

    Design of the power supply

    Supply via voltage measurement channel L1

    Type of supply voltage

    AC 100 - 277 V

    permissible range, lower limit (AC)

    90 V

    permissible range, upper limit (AC)

    293 V

    Line frequency

     

    • permissible range, lower limit

    47 Hz

    • permissible range, upper limit

    63 Hz

    Power loss

     

    Power loss, typ.

    0.6 W

    Address area

     

    Address space per module

     

    • Address space per module, max.

    124 byte; 112 byte input / 12 byte output

    Analog inputs

     

    Cycle time (all channels), typ.

    50 ms; Time for consistent update of all measured and calculated values (cyclic und acyclic data)

    Interrupts/diagnostics/status information

     

    Alarms

     

    • Diagnostic alarm

    Yes

    • Limit value alarm

    Yes

    • Hardware interrupt

    No

    Diagnostics indication LED

     

    • Monitoring of the supply voltage (PWR-LED)

    Yes

    • Channel status display

    Yes; Green LED

    • for channel diagnostics

    Yes; red Fn LED

    • for module diagnostics

    Yes; green/red DIAG LED

    Integrated Functions

     

    Measuring functions

     

    • Measuring procedure for voltage measurement

    TRMS

    • Measuring procedure for current measurement

    TRMS

    • Type of measured value acquisition

    seamless

    • Curve shape of voltage

    Sinusoidal or distorted

    • Buffering of measured variables

    Yes

    • Parameter length

    74 byte

    • Bandwidth of measured value acquisition

    2 kHz; Harmonics: 39 / 50 Hz, 32 / 60 Hz

    Operating mode for measured value acquisition

     

    • automatic detection of line frequency

    No; Parameterizable

    Measuring range

     

    • Frequency measurement, min.

    45 Hz

    • Frequency measurement, max.

    65 Hz

    Measuring inputs for voltage

     

    • Measurable line voltage between phase and neutral conductor

    277 V

    • Measurable line voltage between the line conductors

    480 V

    • Measurable line voltage between phase and neutral conductor, min.

    90 V

    • Measurable line voltage between phase and neutral conductor, max.

    293 V

    • Measurable line voltage between the line conductors, min.

    155 V

    • Measurable line voltage between the line conductors, max.

    508 V

    • Measurement category for voltage measurement in accordance with IEC 61010-2-030

    CAT II; CAT III in case of guaranteed protection level of 1.5 kV

    • Internal resistance line conductor and neutral conductor

    3.4 MΩ

    • Power consumption per phase

    20 mW

    • Impulse voltage resistance 1,2/50µs

    1 kV

    Measuring inputs for current

     

    • measurable relative current (AC), min.

    1 %; Relative to the secondary rated current 5 A

    • measurable relative current (AC), max.

    100 %; Relative to the secondary rated current 5 A

    • Continuous current with AC, maximum permissible

    5 A

    • Apparent power consumption per phase for measuring range 5 A

    0.6 V·A

    • Rated value short-time withstand current restricted to 1 s

    100 A

    • Input resistance measuring range 0 to 5 A

    25 mΩ; At the terminal

    • Zero point suppression

    Parameterizable: 2 - 250 mA, default 50 mA

    • Surge strength

    10 A; for 1 minute

    Accuracy class according to IEC 61557-12

     

    • Measured variable voltage

    0,2

    • Measured variable current

    0,2

    • Measured variable apparent power

    0.5

    • Measured variable active power

    0.5

    • Measured variable reactive power

    1

    • Measured variable power factor

    0.5

    • Measured variable active energy

    0.5

    • Measured variable reactive energy

    1

    • Measured variable neutral current

    0.5; calculated

    • Measured variable phase angle

    ±1 °; not covered by IEC 61557-12

    • Measured variable frequency

    0.05

    Potential separation

     

    Potential separation channels

     

    • between the channels and backplane bus

    Yes; 3 700V AC (type test) CAT III

    Isolation

     

    Isolation tested with

    2 300V AC for 1 min. (type test)

    Ambient conditions

     

    Ambient temperature during operation

     

    • horizontal installation, min.

    -20 °C

    • horizontal installation, max.

    60 °C

    • vertical installation, min.

    -20 °C

    • vertical installation, max.

    50 °C

    Dimensions

     

    Width

    45 mm

    Height

    100 mm

    Depth

    75 mm

    Weights

     

    Weight (without packaging)

    165 g

    Data for selecting a current transformer

     

    • Burden power current transformer x/1A, min.

    As a function of cable length and cross section, see device manual

    • Burden power current transformer x/5A, min.

    As a function of cable length and cross section, see device manual